| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | ARE NOT SIGNED, DATED AND SEALED AS REQUIRED PER FS |
| | 471.025 AND FAC 61G15-23.002. |
| | PLEASE SEE ALL 12 COPIES SUBMITTED IN FACT CONTAIN A |
| | RAISED SEAL OVER *PHOTO-COPIED* SIGNATURES. |
| | PLEASE KNOW THAT PLACING A RAISED SEAL OVER THE |
| | REQUIRED ORIGINAL SIGNATURE AND DATE DOES NOT MEET THE |
| | FLORIDA STATUTES AND THE FLORIDA ADMINISTRATIVE CODE. |
| | FBC 103.1.1.1 |
| | |
| | 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS(NEW CODE) |
| | 2005 NFPA-70 (WRONG CODE LISTED ON PLANS) |
| | 2002 NFPA-72 (SHOWN) |
| | 2003 NFPA-101( ON A-SHEETS NOT ON E-SHEETS) |
| | |
| | ** SOME OF THESE ARE LISTED AND SOME NEED TO BE |
| | CORRECTED. |
| | |
| | 3) NOTE: PLEASE SEE THE FAN/HOOD, DISHWASHER AND |
| | DISPOSAL ARE ALL BEING SHOWN WITH J-BOX AS THESE ITEMS |
| | ARE TO BE HARDWIRED. |
| | PLEASE SEE 422.30, 422.31 FOR REQUIRED DISCONNECTING |
| | MEANS. |
| | ARE THESE NOT CORD AND PLUG TYPE APPLIANCES? |
| | |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |