| 2007-10-09 18:56:05 | BUILDING REVIEW FIRST CHECKLIST FOR NEW R2 RESIDENTIAL |
| | BUILDING. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | |
| | 2- ENERGY CALCULATIONS: |
| | A) NEED TO HAVE ENGINEER'S ORIGINAL SIGNATURE AS |
| | REQUIRED BY CHAPTER 471 FLORIDA STATUTE. |
| | |
| | B) CONTRACTOR'S INFORMATION DOESN'T MATCH |
| | CONTRACTOR'S INFORMATION SHOWN ON PERMIT APPLICATION. |
| | |
| | C) REVISE PERMIT NUMBER. |
| | |
| | D) REVISE OWNER INFORMATION. |
| | |
| | 3- PROVIDE THREE COPIES OF SURVEYS. ONLY ONE |
| | SUBMITTED. |
| | |
| | 4- A) SHEET A110. DETAIL #19 CALLS FOR GA SYSTEM WP |
| | 1052, WHILE ON TOP OF DETAIL IT CALLS FOR WP 3240. |
| | REVISE AS REQUIRED TO MATCH. |
| | |
| | B) SHEET A111:FIRE ASSEMBLY DETAIL 16 IS FOR UL |
| | FIRE ASSEMBLY L523 OR L521.TOP OF DETAIL CALLS FOR |
| | L521, WHILE BOTTOM OF DETAIL CALLS FOR L563. REVISE AS |
| | REQUIRED TO MATCH. |
| | |
| | 5- PROVIDE 3 COPIES OF SOIL TEST REPORT. SEC. 1802.1 |
| | FBC 2004. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) 700 SERIES LOUVERED ROOF VENTS. NOA01-0614.05 |
| | SUBMITTED EXPIRED ON 08/16/2006. NEED CURRENT ONE. |
| | ***NOTE:PLEASE MAKE SURE NOAAND FLORIDA PRODUCT |
| | APPROVAL COVER PAGE SUBMITTED CORRESPOND TO EACH OTHER. |
| | OTHERWISE PROVIDE NOA ONLY TO BE ADDED TO THE CITY |
| | PRODUCT APPROVAL REFERENCE LIBRARY. |
| | |
| | B) BENCHMARK DOOR NOA 02-0215.04 SUBMITTED EXPIRED |
| | ON MAY 30, 2007.NEED CURRENT ONE. |
| | ***NOTE: CLARIFY WHY SUBMITTING SEPARATE PRODUCT |
| | APPROVAL FOR DOOR FRAME IF THIS NOAINCLUDES THE DOOR |
| | FRAME?. |
| | |
| | |
| | 7- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL |
| | RE-SUBMITTED PRODUCT APPROVALS AS REQUIRED BY SEC. |
| | 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 8- OWES $17,453.40FOR LOW VALUATION AND RADON FEES. |
| | SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 9- PROVIDE COMPLETE MANUFACTURER SPECS FOR 2 HOUR FIRE |
| | RATED CONCRETE BLOCK. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004 AND SEC. 703 FBC 2004. |
| | |
| | 10- REMOVE PRODUCT APPROVALS FROM PROJECT MANUAL. THESE |
| | PRODUCT APPROVALS ARE FOR ANOTHER BUILDING. |
| | |
| | 11- REVISE ROOF FRAMING PLAN IN STRUCTURALDRAWINGS. |
| | ARCHITECTURAL PLANS SHOW TENANT SEPARATION WALLGOING |
| | ALL THE WAY UP TO BOTTOM OF ROOF SHEATHING.REVISE TIE |
| | BEAM ELEVATION AND SPECIFY RAKE BEAMS WHERE REQUIRED. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |