| Plan Review Notes For Permit 07080679 |
| Permit Number |
07080679 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-05-13 08:45:13 | ** DENIED 2ND REVIEW** | | | | | | ** PLEASE SEE THE COMMENTS BELOW ARE THE SAME COMMENTS | | | FROM THE PREVIOUS REVIEW. | | | | | | 1) NOTE:PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO | | | THE REQUIRED MINIMUM CODES. THE MINIMUM REQUIRED DESIGN | | | FOR PROJECT PERMITTED AFTER DECEMBER 6TH, 2008 IS THE | | | 2005 NEC/ NFPA-70 | | | PLEASE SEE FOR EXAMPLE THE SHEET E202 WHICH STILL | | | REFLECTS DESIGN FROM THE 2002 CODE. | | | PLEASE SEE ITEMS LISTED IN THE FOLLOWING COMMENTS WHICH | | | WERE CHANGED IN THE 2005 NEC. | | | PLANS MUST STATE THE CODES RELEVANT FOR DESIGN. | | | FS 553.73 | | | FBC 106.1.2, 106.5 ADMIN SECTIONS ADOPTED BY THE CITY | | | OF WEST PALM BEACH | | | | | | 2) NOTE: PLEASE SEE THE REQUIRED DISCONNECTING MEANS | | | FOR APPLIANCES ARE STILL NOT SHOWN ON PLANS. | | | FOR EXAMPLE: | | | DISHWASHER, | | | DISPOSAL, | | | HOOD FAN ETC | | | 422.30, 422.31 | | | THESE ARE SOME EXAMPLES ONLY AND ARE NOT AN EXHAUSTED | | | LIST. THESE ARE ONLY GIVEN AS A BENEFIT. | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|