Plan Review Notes
Plan Review Notes For Permit 07080679
Permit Number 07080679
Review Stop B
Sequence Number 2
Notes
Date Text
2008-06-06 16:55:05BUILDING REVIEWCHECKLIST.
 1- ENERGY CALCULATIONS ARE NOT TAKEN THE "DEFAULT"
 COEFFICIENTFOR GLASS TYPE U-FACTOR AND SHGC (ITEMS
 7-AAND 7-B), THEREFORE NEED TO PROVIDE PROOF THAT
 GLASS IN WINDOWS MEET THE U-FACTOR AND SHGC CALCULATED
 BY THE ENGINEER.SEE SEC. 13-104.4.5 FBC 2004.
 2- PROVIDE DETAIL/SPECS SHOWING HOW PROVIDING R-7.1 ON
 EXTERIOR CONCRETE WALLS AS SHOWN ON ENERGY CALCULATIONS
 ITEM #9A.
 3- REVISE NAME OF CONTRACTOR ON ENERGY CALCULATIONS.
 4- PROVIDE 3 COPIES OF SOIL TEST REPORT. SEC. 1802.1
 FBC 2004.
 5-A) SHINGLES NOA 03-0306.14 NEED TO BE REVIEWED AND
 APPROVED BY DESIGNER OF RECORD. SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
 B) ROOF VENTS NOA 01-0614.05 IS EXPIRED. PROVIDE
 CURRENT NOA AND NEEDS TO BE APPROVED BY THE DESIGNER OF
 RECORD.
 C) TWO HOUR FIRE RATED CONCRETE BLOCK LETTER NEEDS
 TO BE SIGNED BY PERSON RESPONSIBLE FOR LETTER.
 D) PROVIDE PRODUCT APPROVAL FOR HARDIPANEL SHOWN ON
 ARCHITECTURAL DRAWINGS.DESIGNER OR RECORD TO APPROVE
 IT AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC
 2004.
 6- ARCHITECT'S WALL OPENINGS CALCULATIONS NEED TO
 HAVE ARCHITECT'SORIGINAL SEAL, SIGNATURE AND
 INFORMATION OF ARCHITECT'S SIGNING IT AS REQUIRED BY
 481 FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE
 SEC. 61G1-16.003.
 7- PROVIDE CUT SHEETS FOR 90 MINUTE FIRE RATED ENTRY
 DOORS AS REQUIRED ON SHEET A408.
 8- OWES $15,105.52FOR UPDATED VALUATION AND RADON
 FEES.
 9- NEEDSRECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712