| 2008-06-06 16:55:05 | BUILDING REVIEWCHECKLIST. |
| | 1- ENERGY CALCULATIONS ARE NOT TAKEN THE "DEFAULT" |
| | COEFFICIENTFOR GLASS TYPE U-FACTOR AND SHGC (ITEMS |
| | 7-AAND 7-B), THEREFORE NEED TO PROVIDE PROOF THAT |
| | GLASS IN WINDOWS MEET THE U-FACTOR AND SHGC CALCULATED |
| | BY THE ENGINEER.SEE SEC. 13-104.4.5 FBC 2004. |
| | 2- PROVIDE DETAIL/SPECS SHOWING HOW PROVIDING R-7.1 ON |
| | EXTERIOR CONCRETE WALLS AS SHOWN ON ENERGY CALCULATIONS |
| | ITEM #9A. |
| | 3- REVISE NAME OF CONTRACTOR ON ENERGY CALCULATIONS. |
| | 4- PROVIDE 3 COPIES OF SOIL TEST REPORT. SEC. 1802.1 |
| | FBC 2004. |
| | 5-A) SHINGLES NOA 03-0306.14 NEED TO BE REVIEWED AND |
| | APPROVED BY DESIGNER OF RECORD. SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | B) ROOF VENTS NOA 01-0614.05 IS EXPIRED. PROVIDE |
| | CURRENT NOA AND NEEDS TO BE APPROVED BY THE DESIGNER OF |
| | RECORD. |
| | C) TWO HOUR FIRE RATED CONCRETE BLOCK LETTER NEEDS |
| | TO BE SIGNED BY PERSON RESPONSIBLE FOR LETTER. |
| | D) PROVIDE PRODUCT APPROVAL FOR HARDIPANEL SHOWN ON |
| | ARCHITECTURAL DRAWINGS.DESIGNER OR RECORD TO APPROVE |
| | IT AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC |
| | 2004. |
| | 6- ARCHITECT'S WALL OPENINGS CALCULATIONS NEED TO |
| | HAVE ARCHITECT'SORIGINAL SEAL, SIGNATURE AND |
| | INFORMATION OF ARCHITECT'S SIGNING IT AS REQUIRED BY |
| | 481 FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE |
| | SEC. 61G1-16.003. |
| | 7- PROVIDE CUT SHEETS FOR 90 MINUTE FIRE RATED ENTRY |
| | DOORS AS REQUIRED ON SHEET A408. |
| | 8- OWES $15,105.52FOR UPDATED VALUATION AND RADON |
| | FEES. |
| | 9- NEEDSRECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | |