Plan Review Notes
Plan Review Notes For Permit 07080678
Permit Number 07080678
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-05 19:04:25BUILDING REVIEW FIRST CHECKLIST FOR NEW R2 RESIDENTIAL
 BUILDING.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 2- ENERGY CALCULATIONS:
 A) NEED TO HAVE ENGINEER'S ORIGINAL SIGNATURE AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 B) CONTRACTOR'S INFORMATION DOESN'T MATCH
 CONTRACTOR'S INFORMATION SHOWN ON PERMIT APPLICATION.
  
 C) REVISE PERMIT NUMBER.
  
 D) REVISE OWNER INFORMATION.
  
 3- PROVIDE THREE COPIES OF SURVEYS. ONLY ONE
 SUBMITTED.
  
 4- A) SHEET A110. DETAIL #19 CALLS FOR GA SYSTEM WP
 1052, WHILE ON TOP OF DETAIL IT CALLS FOR WP 3240.
 REVISE AS REEQUIRED TO MATCH.
  
 B) SHEET A111:FIRE ASSEMBLY DETAIL 16 IS FOR UL
 FIRE ASSEMBLY L523 OR L521.TOP OF DETAIL CALLS FOR
 L521, WHILE BOTTOM OF DETAIL CALLS FOR L563. REVISE AS
 REQUIRED TO MATCH.
  
 5- PROVIDE 3 COPIES OF SOIL TEST REPORT. SEC. 1802.1
 FBC 2004.
  
 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) 700 SERIES LOUVERED ROOF VENTS. NOA01-0614.05
 SUBMITTED EXPIRED ON 08/16/2006. NEED CURRENT ONE.
 ***NOTE:PLEASE MAKE SURE NOAAND FLORIDA PRODUCT
 APPROVAL COVER PAGE SUBMITTED CORRESPOND TO EACH OTHER.
 OTHERWISE PROVIDE NOA ONLY TO BE ADDED TO THE CITY
 PRODUCT APPROVAL REFERENCE LIBRARY.
  
 B) BENCHMARK DOOR NOA 02-0215.04 SUBMITTED EXPIRED
 ON MAY 30, 2007.NEED CURRENT ONE.
 ***NOTE: CLARIFY WHY SUBMITTING SEPARATE PRODUCT
 APPROVAL FOR DOOR FRAME IF THIS NOAINCLUDES THE DOOR
 FRAME?.
  
  
 7- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL
 RE-SUBMITTED PRODUCT APPROVALS AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 8- OWES $15, 853.40 FOR LOW VALUATION AND RADON FEES.
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 9- PROVIDE COMPLETE MANUFACTURER SPECS FOR 2 HOUR FIRE
 RATED CONCRETE BLOCK. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004 AND SEC. 703 FBC 2004.
  
 10- REMOVE PRODUCT APPROVALS FROM PROJECT MANUAL. THESE
 PRODUCT APPROVALS ARE FOR ANOTHER BUILDING.
  
 11- REVISE ROOF FRAMING PLAN IN STRUCTURAL DRAWINGS.
 ARCHITECTURAL PLANS SHOW TENANT SEPARATION WALL GOING
 ALL THE WAY UP TO BOTTOM OF ROOF SHEATHING.REVISE TIE
 BEAM ELEVATION AND PROVIDE SPECIFICATIONS FOR RAKE
 BEAMS WHERE REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712