| Plan Review Notes For Permit 07080669 |
| Permit Number |
07080669 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2008-06-03 15:39:17 | SEE SHEET 7: | | | BUILDING PROVISO 1203.2 ATTIC SPACES THE NET FREE | | | VENTILATING AREA SHALL NOT BE LESS THAN 1 / 150 OF THE | | | AREA OF THE SPACE VENTILATED, WITH 50 PERCENT OF THE | | | REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS | | | LOCATED IN THE UPPER PORTION OF THE SPACE TO BE | | | VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR | | | CORNICE VENTS WITH THE BALANCE OF THE REQUIRED | | | VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. | | | | | | BUILDING PROVISO 1209.2 AN OPENING NOT LESS THAN 20 | | | INCHES BY 30 INCHES (559 MM BY 762 MM) SHALL BE | | | PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF | | | OVER 30 INCHES (762 MM). A 30-INCH (762 MM) MINIMUM | | | CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT | | | OR ABOVE THE ACCESS OPENING. | | | |
|