| Date |
Text |
| 2008-02-05 10:06:25 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | |
| | 1. SHT 3 THE LOUNGE SINK SHALL BE ACCESSIBLE. PLEASE |
| | PROVIDE A DETAIL WITH ELEVATION SHOWING COMPLIANCE WITH |
| | THE FOLLOWING: |
| | A. OK |
| | B. OK |
| | C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH |
| | REQUIRED. CABINET DOORS NOT APPROVED. |
| | ****NO RESPONSE FOR THE CLEAR FLOOR SPACE. NOT |
| | ADDRESSED. |
| | D. OK |
| | E. OK |
| | |
| | 2. SUBMIT A DETAIL WITH ELEVATION FOR THE DRINKING |
| | FOUNTAIN SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH |
| | ALL SUBSECTIONS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 3. OK |
| | |
| | 4. SHTS 9 & 10 ONLY THE FIXTURES WITHIN THE BATHROOM |
| | GROUPS SHALL CONNECT TO THE WET-VENTED HORIZONTAL |
| | BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL DESCHARGE |
| | DOWNSTREAM OF THE WET VENT. (SEE THE LAB SINK SANT. |
| | RISER 3, AS WELL AS THE XRAY & DARKROOM SINK SANT. |
| | RISER 4. SECTION 909.1. |
| | ****RESPONSE NOTED, BUT THE LAB SINK IS STILL |
| | DISCHARGING INTO THE WET VENT SYSTEM FOR THE TOILET |
| | ROOM. THIS IS SHOWN ON THE SANT. RISER DIAGRAM RISER 3 |
| | AS WELL. |
| | |
| | 5. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |