| 2008-02-06 12:29:48 | BUILDING PLAN REVIEW |
| | PERMIT: 07080669 |
| | ADD: 6215 S DIXIE HWY |
| | CONT: MONARCH |
| | TEL: (561)767-7176 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE2007 SUPPLEMENTS. |
| | |
| | 2) THE PLANS, SHEET # 7 THE FOLLOWING INFORMATION IS |
| | MISSING OR INCORRECT: |
| | |
| | A) THE ROOF SHEATHING BEING NAILED DOWN WITH 8D X 1 |
| | 1/2" RING SHANK NAILS, THE LENGTH OF THE 8D IS 2 1/2" |
| | NOTA 1 1/2". PLEASE SEE FASTENER PENETRATION TABLES |
| | FROM USP OR SIMPSON FOR |
| | FULL SHEAR LOAD VALUES. |
| | |
| | B)PLANS DO NOT INDICATE THE ATTIC VENTING REQUIRED |
| | ABOVE THE EAVE HEIGHT. THE NET FREE VENTILATING AREA |
| | SHALL NOT BE LESS THAN 1 / 150 OF THE AREA OF THE SPACE |
| | VENTILATED, WITH 50 |
| | PERCENT OF THE REQUIRED VENTILATING AREA |
| | PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF |
| | THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM) |
| | ABOVE EAVE OR CORNICE VENTS WITH |
| | THE BALANCE OF THE REQUIRED VENTILATION |
| | PROVIDED BY EAVE OR CORNICE VENTS. |
| | |
| | C) PRODUCT APPROVALS: MISSING REPORTS ARE ON THE |
| | TRUSS ANCHOR AND OR TRUSS STRAPS, RULE 9B-72(31)(G) |
| | TRUSS ANCHORS.WILL ALSO REQUIRE FLORIDA COVER SHEET AND |
| | THE DESIGN PROFESSIONALS |
| | REVIEW AND APPROVAL. |
| | |
| | D) PLANS DO NOT PROVIDE WHAT THE HEADROOM WWITHIN THE |
| | NEW ATTIC SPACE WILL BE WITHIN THE TRUSSED IN AREA, |
| | PLEASE DEMONSTRATE COMPLIANCE WITH 1209.2 ATTIC |
| | SPACES. |
| | |
| | 3) TRUSS DRAWINGS PLEASE REVIEW FAC 61G15-23.002 AND |
| | 61G15-31.003 SIGNING AND SEALING REQUIRED FOR TRUSS |
| | DRAWINGS. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |