| Date |
Text |
| 2007-09-24 14:19:39 | CONSTRUCTION SERVICES DEPARTMENT |
| | 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, |
| | FLORIDA33401 |
| | TEL:561-805-6713FAX: |
| | 561-805-6731 |
| | |
| | |
| | JAMES JOHNSTON, PERMIT NO 07080669 BUILDING |
| | PLAN EXAMINERII |
| | PROJECT MEDICAL BUILDING |
| | E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 6215 S. DIXIE |
| | HIGHWAY |
| | CONTRACTOR MONARCH CONSTRUCTION OF S. F. |
| | DATE SEPTEMBER 21, 2007 |
| | |
| | STRUCTURALPLANREVIEW |
| | CORRECTION SUBMITTAL |
| | WHEN RE-SUBMITTINGCORRECTED PLANS FOR PERMITTING, |
| | PLEASEREMOVE AND REPLACE ANY SHEETS AS NECESSARY. |
| | INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER WITH A DESCRIPTION OF THE |
| | REVISION MADE. IDENTIFY THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND AND INCLUDE THE OLD |
| | SHEETS IN THE RE-SUBMITTAL PACKAGE FOR THE PLAN |
| | REVIEWER?S REFERENCE. |
| | THIS SHALL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | COMMENT-FOR YOUR INFORMATION |
| | |
| | RETAIN ORIGINAL PLANS |
| | ONE SET OF ORIGINAL PLANS AND ONE SET OF REVISIONS WILL |
| | BE RETAINED FOR THE POSSIBILITY OF FORWARDING TO THE |
| | STATE BOARD OF ENGINEERS. REMOVE ALL OLD (VOID) SHEETS |
| | AND RETAIN ONE SET. |
| | COMMENT-FOR YOUR INFORMATION |
| | |
| | |
| | F.S.713.13NOTICE OF COMMENCEMENT |
| | FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION. |
| | IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED |
| | WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL |
| | AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT |
| | ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE |
| | FIRST INSPECTION. |
| | COMMENT-FOR YOUR INFORMATION |
| | |
| | |
| | IMPACT FEES |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, IMPACT FEES |
| | MUST BE PAID TO PALM BEACH COUNTY. |
| | THE PERMITTED SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | PALM BEACH COUNTY ASSESSMENT |
| | PALM BEACH COUNTY IMPACT FEE ASSESSMENT HAS MOVED TO: |
| | 2300 N JOG ROAD, SUITE 2 WPB 33411 |
| | COMMENT-FOR YOUR INFORMATION |
| | |
| | WINDOWS / DOORS PRODUCT APPROVALS |
| | WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE |
| | 9B-72FLORIDA PRODUCT APPROVAL |
| | SUBMIT TWO COPIES OF EACH APPROVAL WITH FLORIDA PRODUCT |
| | APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S |
| | SIGNATURE AS APPLICABLE, STATING ?TO THE BEST OF THEIR |
| | KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH THE PLANS |
| | AND SPECIFICATIONS.SEE:WEB SITE |
| | WWW.FLORIDABUILDING.COM |
| | NOTE: SEE DIVISION FACTOR TO BE USED IN DESIGN PRESSURE |
| | BY LEGACYFPA |
| | COMMENT-SUBMIT TWO COPIES OF EACH PRODUCT APPROVAL |
| | MIAMI-DADE AND FLORIDA PRODUCT APPROVAL |
| | |
| | |
| | 1. PRODUCT APPROVAL |
| | LAWSON INDUSTRIES PRODUCT APPROVALNOA 06-0117.02 |
| | COMMENT-EXPIRED AUGUST 22,2007 |
| | |
| | 2. PRODUCT APPROVALS |
| | COMMENT-MIAMI DADE PRODUCT APPROVALS MISSING FLORIDA |
| | PRODUCT APPROVAL SHEET |
| | |
| | 3. NORDIC FLAT ROOF TILE |
| | COMMENT-IDENTIFY WHICH SYSTEM AND FASTENERS YOU ARE |
| | USING FROM TABLES PROVIDED IN THE PRODUCT APPROVAL |
| | |
| | 4. POLYPROAH160 |
| | COMMENT-IDENTIFY WHICH SYSTEM AND FASTENERS YOU ARE |
| | USING FROM TABLES PROVIDED IN THE PRODUCT APPROVAL |
| | |
| | 5. PRODUCT APPROVAL |
| | LAWSON INDUSTRIES LA PORTE OUT SWING FRENCH DOOR |
| | COMMENT-IDENTIFY UNIT AND COMPONENTS TO BE USED |
| | |
| | 6. PRODUCT APPROVAL |
| | LAWSON INDUSTRIES FIXED WINDOW |
| | COMMENT-IDENTIFY UNIT AND COMPONENTS TO BE USED |
| | |
| | 7. PRODUCT APPROVAL |
| | LAWSON INDUSTRIES SINGLE HUNG WINDOW |
| | COMMENT-IDENTIFY UNIT AND COMPONENTS TO BE USED |
| | |
| | 8. SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | FOLLOWING |
| | FIXED GLASS |
| | WINDOWS |
| | MULLION TUBES |
| | EXTERIORHOLLOW METAL DOORS |
| | EXTERIOR DOORS-OTHER |
| | ROOF COVERING SYSTEMS |
| | |
| | 9. PLEASE PROVIDE ALL NOTES ON COVER SHEET 1 |
| | FBC2004 BUILDING W/ 2005 AND 6 REVISIONS |
| | FBC2004 EXISTING BUILDING |
| | LEVEL OF ALTERATION |
| | TYPE OF CONSTRUCTION / SPRINKLED / UN-SPRINKLED WIND |
| | SPEED AND EXPOSURE |
| | WIND IMPORTANCE FACTOR |
| | TYPE OF OCCUPANCY |
| | OCCUPANT LOAD |
| | GROSS LOAD |
| | NET LOAD |
| | |
| | 10. DOOR NO. 8 NOT NOTED ON DEMOLITION PLAN COMMENT- |
| | IDENTIFY POURED CELLS FOR THIS DOOR |
| | |
| | 11. 704.5 FIRE-RESISTANCE RATINGS. |
| | EXTERIOR WALLS SHALL BE FIRE-RESISTANCE RATED IN |
| | ACCORDANCE WITH TABLES 601 AND 602 . THE |
| | FIRE-RESISTANCE RATING OF EXTERIOR WALLS WITH A FIRE |
| | SEPARATION DISTANCE OF GREATER THAN 5 FEET (1524 MM) |
| | SHALL BE RATED FOR EXPOSURE TO FIRE FROM THE INSIDE. |
| | THE FIRE-RESISTANCE RATING OF EXTERIOR WALLS WITH A |
| | FIRE SEPARATION DISTANCE OF 5 FEET (1524 MM) OR LESS |
| | SHALL BE RATED FOR EXPOSURE TO FIRE FROM BOTH SIDES. |
| | COMMENT-ON SHEET 1 SHOW ADJACENT BUILDINGS AND PUBLIC |
| | ROADS TO DETERMINE FIRE RESISTANCE RATINGS OF OPENINGS |
| | IN THE EXTERIOR TWO HOUR WALL.SEE TABLE704.8TO |
| | DETERMINE PROTECTION OF OPENINGS |
| | |
| | |
| | |
| | 12. PROVIDE TRUSS FRAMING PLAN WITH SHEATHING AND |
| | ANCHORAGE. INFORMATION PROVIDED HEREIN |
| | FBC2304.9.1 FASTENER REQUIREMENTS. |
| | CONNECTIONS FOR WOOD MEMBERS SHALL BE DESIGNED IN |
| | ACCORDANCE WITH THE APPROPRIATE METHODOLOGY IN SECTION |
| | 2301.2 . THE NUMBER AND SIZE OF NAILS CONNECTING WOOD |
| | MEMBERS SHALL NOT BE LESS THAN THAT SET FORTH IN TABLE |
| | 2304.9.1 . |
| | FBC2304.7 FLOOR AND ROOF SHEATHING |
| | FBC2304.7.2 STRUCTURAL ROOF SHEATHING. |
| | COMMENT-STRUCTURAL ROOF SHEATHING SHALL BE DESIGNED |
| | IN ACCORDANCE WITH THE GENERAL PROVISIONS OF THIS CODE |
| | AND THE SPECIAL PROVISIONS IN THIS SECTION. USE RATING |
| | INDICATED IN TABLE.EX.5/8 PANELS EQUAL 19/32 |
| | RATING SEE TABLES IN THIS SECTION. |
| | |
| | 13. FBC EXISTING 601.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE . |
| | (A)13-400.0 GENERAL. |
| | THE PROVISIONS OF THIS CHAPTER APPLY TO ALL NEW |
| | COMMERCIAL OCCUPANCY BUILDINGS, ADDITIONS TO EXISTING |
| | COMMERCIAL OCCUPANCY BUILDINGS, AND MULTIPLE-FAMILY |
| | RESIDENTIAL BUILDINGS OVER THREE STORIES IN HEIGHT. |
| | BUILDING TYPE CLASSIFICATIONS SHALL BE THOSE DEFINED IN |
| | SUBCHAPTER 13-2 OF THIS CODE UNDER ?OCCUPANCY |
| | CLASSIFICATION.? THIS SUBCHAPTER PROVIDES THREE METHODS |
| | BY WHICH COMMERCIAL BUILDINGS MAY BE BROUGHT INTO |
| | COMPLIANCE WITH THIS CODE. |
| | COMMENT-NEW CONSTRUCTION FOR WALLS, ROOF, INTERIOR |
| | MUST COMPLY WITH FBC BUILDING CHAPTER 13-400.0 |
| | |
| | 14. SHEET 7SECTION 2-7 |
| | COMMENT-IDENTIFY NELSON STUD EMBEDMENT INTO BEAM |
| | |
| | 15. SHEET7SECTION 1-7 |
| | COMMENT - DEFINE R VALUE FOR EXTERIOR WALL AND ATTIC |
| | INSULATION |
| | |
| | 16. SHEET 7 CONCRETE TO BE USED FOR THIS PROJECT |
| | COMMENTS - IDENTIFY STRENGTH OF CONCRETE FOR FOOTINGS, |
| | BEAMS, COLUMNS, FILLED CELLS, MASONRY UNITS |
| | |
| | FBC11-4FLORIDA ACCESSIBILITY CODE |
| | |
| | 1A. FBC 11-4.8 RAMPS |
| | COMMENT-RAMP DESIGN REQUIRED WITH ALL ELEMENTS PER |
| | THIS CHAPTER |
| | SEE FIGURE 17 EXAMPLES OF EDGE PROTECTION AND HANDRAIL |
| | EXTENSIONS |
| | |
| | 2A. FBC 11-4.9.4STAIRS |
| | COMMENT-DEFINE HANDRAIL AND LOCATION ON SHEET 6. |
| | IDENTIFY 36? FROM TREAD TO RAILING FOR FIELD USE SEE |
| | FIGURE 19 STAIR HANDRAILS |
| | |
| | 3A. FBC 11-4.13.4 DOUBLE-LEAF DOORWAYS.( DOOR NO.1 |
| | &2ON PLAN ) |
| | COMMENT-IF DOORWAYS HAVE TWO INDEPENDENTLY OPERATED |
| | DOOR LEAVES, THEN AT LEAST ONE LEAF SHALL MEET THE |
| | SPECIFICATIONS IN SECTION 11-4.13.5 AND SECTION |
| | 11-4.13.6 . THAT LEAF SHALL BE AN ACTIVE LEAF. |
| | |
| | (1) 11-4.13.5 CLEAR WIDTH. |
| | DOORWAYS SHALL HAVE A MINIMUM CLEAR OPENING OF 32 |
| | INCHES (813 MM) WITH THE DOOR OPEN 90 DEGREES, MEASURED |
| | BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE STOP SEE |
| | FIGURE 24 (A), FIGURE 24 (B), FIGURE |
| | |
| | 5A. TOILET ROOM NO. 1 |
| | COMMENT-IDENTIFY PASS THRU WINDOW HEIGHT ABOVE |
| | FINISHED FLOOR |