Notes
Date Text
2007-10-29 14:05:59DENIED
 REFERENCE: FBC-2004 PLUMBING WITH 2005 & 2006
 REVISIONS
 FBC-2004 CHAPTER 1
  
 1. SHT P-1 UNITS A & B. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUP SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. SECTION 909.1. ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE WET VENT.
 (WASH MACHINE SHALL CONNECT DOWNSTREAM OF THE BATHROOM
 FIXTURES).
  
 2. SHT P-1 FIRST B UNIT ON THE LEFT SHOWS A BRANCH LINE
 FROM THE BUILDING DRAIN AT THE PORCH. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 3. SHT P-2 UNITS A & B. EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE. SECTION 905.3.(SEE VENT
 UPSTREAM OF THE SHOWER IN THE MASTER BATH). PLEASE
 DELETE DRY HORIZONTAL VENT OR SHOW COMPLIANCE.
  
 4. SHT P-3 UNITS A & B. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUP SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. SECTION 909.1. ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE WET VENT.
 (WASH MACHINE SHALL CONNECT DOWNSTREAM OF THE BATHROOM
 FIXTURES).
  
 5. SHT P-4 UNITS A & B. EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE. SECTION 905.3.(SEE VENT
 UPSTREAM OF THE SHOWER IN THE MASTER BATH). PLEASE
 DELETE DRY HORIZONTAL VENT OR SHOW COMPLIANCE.
  
 6. SHT P-5 SANITARY RISER DIAGRAM UNIT A. THE SHOWER
 NOR THE LAV ARE VENTED IN THE FIRST FLOOR SHOWER BATH.
 SECTION 901.2.1.--SHOW ALL PIPE SIZES. MINIMUM 3"
 IS REQUIRED TO THE WASH MACHINE PER 406.3, AND NO SIZE
 TO LAV IN FIRST FLOOR SHOWER BATH IS SHOWN. TABLE
 709.1.--A STANDPIPE IS REQUIRED FOR THE TRAP TO THE
 WASH MACHINE AS WELL AS A CLEANOUT LOCATED A MINIMUM 4'
 ABOVE THE FLOOR. SECTIONS 1002.1 & 708.9.--EVERY
 DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE.
 SECTION 905.3.(SEE VENT UPSTREAM OF THE SHOWER IN THE
 MASTER BATH).--THE LAV IN THE MASTER BATH IS NOT
 VENTED. SECTION 901.2.1. PLEASE CORRECT ALL CODE
 REQUIREMENTS ON THE RISER DIAGRAM.
  
 7. SHT P-5 SANITARY RISER DIAGRAM UNIT B. THE LAV IS
 NOT VENTED IN THE FIRST FLOOR POWDER ROOM. SECTION
 901.2.1.--SHOW ALL PIPE SIZES. MINIMUM 3" IS
 REQUIRED TO THE WASH MACHINE PER 406.3.--A
 STANDPIPE IS REQUIRED FOR THE TRAP TO THE WASH MACHINE
 AS WELL AS A CLEANOUT LOCATED A MINIMUM 4' ABOVE THE
 FLOOR. SECTIONS 1002.1 & 708.9.--EVERY DRY VENT
 CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE
 THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. SECTION
 905.3.(SEE VENT UPSTREAM OF THE SHOWER IN THE MASTER
 BATH).--THE LAV IN THE MASTER BATH IS NOT VENTED.
 SECTION 901.2.1. PLEASE CORRECT ALL CODE REQUIREMENTS
 ON THE RISER DIAGRAM.
  
 8. SHT P-5 SANITARY RISER DIAGRAM UNIT C. THE LAV IS
 NOT VENTED IN THE FIRST FLOOR POWDER ROOM. SECTION
 901.2.1.--SHOW ALL PIPE SIZES. MINIMUM 3" IS
 REQUIRED TO THE WASH MACHINE PER 406.3.--A
 STANDPIPE IS REQUIRED FOR THE TRAP TO THE WASH MACHINE
 AS WELL AS A CLEANOUT LOCATED A MINIMUM 4' ABOVE THE
 FLOOR. SECTIONS 1002.1 & 708.9. PLEASE CORRECT ALL CODE
 REQUIREMENTS ON THE RISER DIAGRAM.
  
 9. SHT P-6 POTABLE RISER DIAGRAM UNIT A. WATER HAMMER
 ARRESTORS ARE REQUIRED ON THE WASH MACHINE HOT & COLD
 WATER SUPPLIES, THE HOT SUPPLY TO THE DISH WASHER AND
 TO THE COLD WATER SUPPLY TO THE ICE MAKER. SECTION
 604.9. PLEASE SHOW THE WATER HAMMER ARRESTORS LOCATED
 NEAR THE FIXTURES, NOT IN THE CEILING PER PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.--A FULL OPEN
 VALVE IS REQUIRED ON THE WATER SUPPLY LINE TO THE WATER
 HEATER PER SECTION 606.1(7). PLEASE SHOW VALVE ON RISER
 DIAGRAM.
  
 10. SHT P-6 POTABLE RISER DIAGRAM UNIT B. WATER HAMMER
 ARRESTORS ARE REQUIRED ON THE WASH MACHINE HOT & COLD
 WATER SUPPLIES, THE HOT SUPPLY TO THE DISH WASHER AND
 TO THE COLD WATER SUPPLY TO THE ICE MAKER. SECTION
 604.9. PLEASE SHOW THE WATER HAMMER ARRESTORS LOCATED
 NEAR THE FIXTURES, NOT IN THE CEILING PER PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.--A FULL OPEN
 VALVE IS REQUIRED ON THE WATER SUPPLY LINE TO THE WATER
 HEATER PER SECTION 606.1(7). PLEASE SHOW VALVE ON RISER
 DIAGRAM.--THE WATER RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN AT THE WATER CLOSET. SECTION 106.1.1.
 PLEASE MAKE SURE THE RISER DIAGRAM RELECTS THE FLOOR
 PLAN.
  
 11. SHT P-6 POTABLE RISER DIAGRAM UNIT C. WATER HAMMER
 ARRESTORS ARE REQUIRED ON THE WASH MACHINE HOT & COLD
 WATER SUPPLIES, THE HOT SUPPLY TO THE DISH WASHER AND
 TO THE COLD WATER SUPPLY TO THE ICE MAKER. SECTION
 604.9. PLEASE SHOW THE WATER HAMMER ARRESTORS LOCATED
 NEAR THE FIXTURES, NOT IN THE CEILING PER PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.--A FULL OPEN
 VALVE IS REQUIRED ON THE WATER SUPPLY LINE TO THE WATER
 HEATER PER SECTION 606.1(7). PLEASE SHOW VALVE ON RISER
 DIAGRAM.--THE WATER RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN AT THE WATER HEATER. SECTION 106.1.1.
 PLEASE MAKE SURE THE RISER DIAGRAM RELECTS THE FLOOR
 PLAN.
  
 12. SHT P-7 WATER HEATER DETAIL INDICATES RUN P/T AND
 PAN DRAIN TO MOP SINK. THERE IS NO MOP SINK ON THE
 PLANS. (PAN NOT REQUIRED ON THE FIRST FLOOR UNLESS ON A
 SHELF). PLEASE CLARIFY. SECTION 106.1.1.--VACUUM
 RELIEF VALVE IS REQUIRED ON ALL BOTTOM FED WATER
 HEATERS. SECTION 504.2. PLEASE INDICATE ON DETAIL IF
 BOTTOM FED AS SHOWN.
  
 13. ENERGY CALCULATIONS ARE REQUIRED FOR THE WATER
 HEATERS EACH UNIT. SECTION 13-103. PLEASE SUBMIT ENERGY
 CALCULATIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  