| Date |
Text |
| 2007-10-29 14:05:59 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING WITH 2005 & 2006 |
| | REVISIONS |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P-1 UNITS A & B. ONLY THE FIXTURES WITHIN THE |
| | BATHROOM GROUP SHALL CONNECT TO THE WET-VENTED |
| | HORIZONTAL BRANCH DRAIN. SECTION 909.1. ADDITIONAL |
| | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | (WASH MACHINE SHALL CONNECT DOWNSTREAM OF THE BATHROOM |
| | FIXTURES). |
| | |
| | 2. SHT P-1 FIRST B UNIT ON THE LEFT SHOWS A BRANCH LINE |
| | FROM THE BUILDING DRAIN AT THE PORCH. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 3. SHT P-2 UNITS A & B. EVERY DRY VENT CONNECTING TO A |
| | HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF |
| | THE HORIZONTAL DRAIN PIPE. SECTION 905.3.(SEE VENT |
| | UPSTREAM OF THE SHOWER IN THE MASTER BATH). PLEASE |
| | DELETE DRY HORIZONTAL VENT OR SHOW COMPLIANCE. |
| | |
| | 4. SHT P-3 UNITS A & B. ONLY THE FIXTURES WITHIN THE |
| | BATHROOM GROUP SHALL CONNECT TO THE WET-VENTED |
| | HORIZONTAL BRANCH DRAIN. SECTION 909.1. ADDITIONAL |
| | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | (WASH MACHINE SHALL CONNECT DOWNSTREAM OF THE BATHROOM |
| | FIXTURES). |
| | |
| | 5. SHT P-4 UNITS A & B. EVERY DRY VENT CONNECTING TO A |
| | HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF |
| | THE HORIZONTAL DRAIN PIPE. SECTION 905.3.(SEE VENT |
| | UPSTREAM OF THE SHOWER IN THE MASTER BATH). PLEASE |
| | DELETE DRY HORIZONTAL VENT OR SHOW COMPLIANCE. |
| | |
| | 6. SHT P-5 SANITARY RISER DIAGRAM UNIT A. THE SHOWER |
| | NOR THE LAV ARE VENTED IN THE FIRST FLOOR SHOWER BATH. |
| | SECTION 901.2.1.--SHOW ALL PIPE SIZES. MINIMUM 3" |
| | IS REQUIRED TO THE WASH MACHINE PER 406.3, AND NO SIZE |
| | TO LAV IN FIRST FLOOR SHOWER BATH IS SHOWN. TABLE |
| | 709.1.--A STANDPIPE IS REQUIRED FOR THE TRAP TO THE |
| | WASH MACHINE AS WELL AS A CLEANOUT LOCATED A MINIMUM 4' |
| | ABOVE THE FLOOR. SECTIONS 1002.1 & 708.9.--EVERY |
| | DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT |
| | ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. |
| | SECTION 905.3.(SEE VENT UPSTREAM OF THE SHOWER IN THE |
| | MASTER BATH).--THE LAV IN THE MASTER BATH IS NOT |
| | VENTED. SECTION 901.2.1. PLEASE CORRECT ALL CODE |
| | REQUIREMENTS ON THE RISER DIAGRAM. |
| | |
| | 7. SHT P-5 SANITARY RISER DIAGRAM UNIT B. THE LAV IS |
| | NOT VENTED IN THE FIRST FLOOR POWDER ROOM. SECTION |
| | 901.2.1.--SHOW ALL PIPE SIZES. MINIMUM 3" IS |
| | REQUIRED TO THE WASH MACHINE PER 406.3.--A |
| | STANDPIPE IS REQUIRED FOR THE TRAP TO THE WASH MACHINE |
| | AS WELL AS A CLEANOUT LOCATED A MINIMUM 4' ABOVE THE |
| | FLOOR. SECTIONS 1002.1 & 708.9.--EVERY DRY VENT |
| | CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE |
| | THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. SECTION |
| | 905.3.(SEE VENT UPSTREAM OF THE SHOWER IN THE MASTER |
| | BATH).--THE LAV IN THE MASTER BATH IS NOT VENTED. |
| | SECTION 901.2.1. PLEASE CORRECT ALL CODE REQUIREMENTS |
| | ON THE RISER DIAGRAM. |
| | |
| | 8. SHT P-5 SANITARY RISER DIAGRAM UNIT C. THE LAV IS |
| | NOT VENTED IN THE FIRST FLOOR POWDER ROOM. SECTION |
| | 901.2.1.--SHOW ALL PIPE SIZES. MINIMUM 3" IS |
| | REQUIRED TO THE WASH MACHINE PER 406.3.--A |
| | STANDPIPE IS REQUIRED FOR THE TRAP TO THE WASH MACHINE |
| | AS WELL AS A CLEANOUT LOCATED A MINIMUM 4' ABOVE THE |
| | FLOOR. SECTIONS 1002.1 & 708.9. PLEASE CORRECT ALL CODE |
| | REQUIREMENTS ON THE RISER DIAGRAM. |
| | |
| | 9. SHT P-6 POTABLE RISER DIAGRAM UNIT A. WATER HAMMER |
| | ARRESTORS ARE REQUIRED ON THE WASH MACHINE HOT & COLD |
| | WATER SUPPLIES, THE HOT SUPPLY TO THE DISH WASHER AND |
| | TO THE COLD WATER SUPPLY TO THE ICE MAKER. SECTION |
| | 604.9. PLEASE SHOW THE WATER HAMMER ARRESTORS LOCATED |
| | NEAR THE FIXTURES, NOT IN THE CEILING PER PDI-WH 201 |
| | AND MANUF. INSTALLATION INSTRUCTIONS.--A FULL OPEN |
| | VALVE IS REQUIRED ON THE WATER SUPPLY LINE TO THE WATER |
| | HEATER PER SECTION 606.1(7). PLEASE SHOW VALVE ON RISER |
| | DIAGRAM. |
| | |
| | 10. SHT P-6 POTABLE RISER DIAGRAM UNIT B. WATER HAMMER |
| | ARRESTORS ARE REQUIRED ON THE WASH MACHINE HOT & COLD |
| | WATER SUPPLIES, THE HOT SUPPLY TO THE DISH WASHER AND |
| | TO THE COLD WATER SUPPLY TO THE ICE MAKER. SECTION |
| | 604.9. PLEASE SHOW THE WATER HAMMER ARRESTORS LOCATED |
| | NEAR THE FIXTURES, NOT IN THE CEILING PER PDI-WH 201 |
| | AND MANUF. INSTALLATION INSTRUCTIONS.--A FULL OPEN |
| | VALVE IS REQUIRED ON THE WATER SUPPLY LINE TO THE WATER |
| | HEATER PER SECTION 606.1(7). PLEASE SHOW VALVE ON RISER |
| | DIAGRAM.--THE WATER RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN AT THE WATER CLOSET. SECTION 106.1.1. |
| | PLEASE MAKE SURE THE RISER DIAGRAM RELECTS THE FLOOR |
| | PLAN. |
| | |
| | 11. SHT P-6 POTABLE RISER DIAGRAM UNIT C. WATER HAMMER |
| | ARRESTORS ARE REQUIRED ON THE WASH MACHINE HOT & COLD |
| | WATER SUPPLIES, THE HOT SUPPLY TO THE DISH WASHER AND |
| | TO THE COLD WATER SUPPLY TO THE ICE MAKER. SECTION |
| | 604.9. PLEASE SHOW THE WATER HAMMER ARRESTORS LOCATED |
| | NEAR THE FIXTURES, NOT IN THE CEILING PER PDI-WH 201 |
| | AND MANUF. INSTALLATION INSTRUCTIONS.--A FULL OPEN |
| | VALVE IS REQUIRED ON THE WATER SUPPLY LINE TO THE WATER |
| | HEATER PER SECTION 606.1(7). PLEASE SHOW VALVE ON RISER |
| | DIAGRAM.--THE WATER RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN AT THE WATER HEATER. SECTION 106.1.1. |
| | PLEASE MAKE SURE THE RISER DIAGRAM RELECTS THE FLOOR |
| | PLAN. |
| | |
| | 12. SHT P-7 WATER HEATER DETAIL INDICATES RUN P/T AND |
| | PAN DRAIN TO MOP SINK. THERE IS NO MOP SINK ON THE |
| | PLANS. (PAN NOT REQUIRED ON THE FIRST FLOOR UNLESS ON A |
| | SHELF). PLEASE CLARIFY. SECTION 106.1.1.--VACUUM |
| | RELIEF VALVE IS REQUIRED ON ALL BOTTOM FED WATER |
| | HEATERS. SECTION 504.2. PLEASE INDICATE ON DETAIL IF |
| | BOTTOM FED AS SHOWN. |
| | |
| | 13. ENERGY CALCULATIONS ARE REQUIRED FOR THE WATER |
| | HEATERS EACH UNIT. SECTION 13-103. PLEASE SUBMIT ENERGY |
| | CALCULATIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |