| 2007-09-16 09:56:48 | 2007-09-16 09:56:48 |
| | |
| | ** DENIED ** |
| | |
| | 1) NOTE: *** IMPORTANT*** |
| | AS THERE ARE ITEMS WHICH HAVE NOT YET BEEN SUBMITTED |
| | FOR PLAN REVIEW OR ON PLANS, SOME ITEMS CAN NOT BE |
| | REVIEWED AT THIS TIME FOR CODE COMPLIANCE. |
| | REVIEW CAN ONLY BE PERFORMED ON PLANS AND DOCUMENTS |
| | SUBMITTED AND THERE MAY VERY WELL BE NEW COMMENTS ON |
| | THE NEXT REVIEW. |
| | |
| | 2) NOTE:PLEASE SEE THAT PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED |
| | FOR PERMIT APPLICATION. ONCE PLANS ARE CODE COMPLIANT |
| | REVIEW STATUS WILL BE STILL SHOWN IN A FAILED STATUS |
| | UNTIL PERMIT APPLICATION HAS BEEN APPLIED. AT TIME OF |
| | PERMIT APPLICATION AND BEFORE ISSUANCE OF PERMIT |
| | LICENSING ETC IS VERIFIED. |
| | ** PLEASE ALSO SEE COMMENTS FROM BUILDING REVIEWER AS |
| | EACH OF THESE BUILDINGS WILL MOSTLIKELY BE REQUIRED TO |
| | BE UNDER SEPARATE PERMITS. |
| | |
| | 3) NOTE: PLEASE SEE THE SITE LIGHTING PLANS ARE NOT |
| | COMPLETE AT THIS TIME. PLEASE COMPLETE CIRCUITING AND |
| | CORRELATE WITH THE PANEL SCHEDULE WHICH IS NOTED AS |
| | HOUSE PANEL. |
| | PLEASE SUBMIT THE LIGHT POLE INFORMATION FOR |
| | BUILDING/STRUCTURAL REVIEW. PLEASE SEE THAT THE |
| | LIGHTING WATTAGES ARE REQUIRED TO BE COMPLETED AT THIS |
| | TIME AS THIS INFORMATION WILL BE NEEDED IN THE ENERGY |
| | CALCULATIONS WHICH ARE TO BE SUBMITTED. |
| | LIGHTING LEGEND INDICATES 60WATT FIXTURES FOR THE |
| | SYMBOL WHICH IS SHOWN ON PLANS FOR POLE LIGHTS, HOW |
| | DOES THIS PROVIDE THE PHOTO-METRIC LEVELS AS SHOWN? |
| | PLEASE CLARIFY THE HOUSE PANEL WHICH INDICATES BUILDING |
| | LIGHTING YET THE ONLY LIGHTING WHICH COULD BE LOCATED |
| | ON PLANS FOR BUILDING IS THIS LIGHTING FROM EACH UNIT |
| | AT THE ENTRANCES/EXITS. |
| | ** PLEASE COORDINATE ALL SITE LIGHTING AND BUILDING |
| | LIGHTING INFORMATION WITH PANEL, CIRCUITING, TYPES ETC. |
| | CAN NOT COMPLETE REVIEW ON THESE ITEMS AT THIS TIME. |
| | |
| | 4) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED. NO |
| | PANEL SCHEDULE WAS SUBMITTED INDICATING THE MINIMUM |
| | REQUIRED CIRCUITS AND COORDINATION WITH PLANS CAN NOT |
| | BE DONE AT THIS TIME. |
| | PLEASE SEE THE CONDUCTOR SIZES AND OVER CURRENT/BREAKER |
| | SIZES FOR ALL CAN NOT BE VERIFIED. |
| | THERE IS A *PROVIDE PER UNIT* CIRCUIT NOTE LOCATED |
| | ABOVE UNITS ON BUILDING A. THIS IS NOT NEEDED, BUT MAY |
| | BE LOCATED ON PLANS. IF THIS IS GOING TO REMAIN PLEASE |
| | SEE THERE ARE SOME ITEMS WHICH DO NOT CORRELATE WITH |
| | OTHER INFORMATION ON PLANS. |
| | EXAMPLES: |
| | A) PLEASE SEE THE DRYER WHICH IS SHOWN AT 5KW, |
| | INDICATES THE CIRCUIT TO BE 20AMP. |
| | B) PLEASE SEE THERE IS A NOTE TO PROVIDE CIRCUIT FOR |
| | DISHWASHER YET NO DW IS SHOWN ON PLANS? |
| | C) PLEASE SEE MISSING REQUIRED DEDICATED CIRCUIT(S) FOR |
| | BATHROOMS PER 210.52D, 210.11C3. |
| | D) PLEASE SEE MISSING DINING ROOM DESIGNATION/CIRCUIT |
| | PER 210.52B1, 210.11C1, 220.53. AS THE CIRCUITING IS |
| | NOT SHOWN THIS CAN NOT BE VERIFIED AT THIS TIME FOR |
| | DINING. |
| | PLEASE COMPLETE AND SEE SOME NOTES BELOW FOR ITEMS |
| | WHICH WILL BE NEEDED ON PANEL SCHEDULE. |
| | 408.4, 310.16, 240.4 ETC. |
| | FBC 106.3.5.4 |
| | PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY |
| | FROM THE NEC CODE COMMENTARY. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.1.2, 106.3.5.4. |
| | BOTH BUILDINGS. (THIS CAN BE A TYPICAL PANEL SCHEDULE |
| | FOR EACH OF THE UNITS WHICH ARE THE SAME). |
| | |
| | 5) NOTE: PLEASE CLARIFY THE SYMBOL BEING USED FOR THE |
| | SMOKE ALARMS. THIS SD IS A TYPICAL UNIVERSAL SYMBOL FOR |
| | SMOKE DETECTOR WHICH BY DEFINITION IN NFPA-72 IS A |
| | DEVICE WHICH ONLY DETECTS AND DOES NOT SOUND AN ALARM. |
| | PLEASE VERIFY. |
| | BOTH BUILDINGS. |
| | |
| | 6) NOTE: PLEASE CLARIFY THE LOCATION OF THE DISHWASHER |
| | AS NOTED ABOVE IN NOTE #4. PLEASE KNOW IF THIS FROM THE |
| | SAME DEVICE/YOKE AS THE DISPOSAL (DEPENDING ON |
| | LOCATION) THEN THE BREAKER/OVER CURRENT PROTECTION IN |
| | THE PANEL SCHEDULE TO BE SUBMITTED WOULD BE REQUIRED TO |
| | BE 2-POLE. |
| | 210.4B |
| | BOTH BUILDINGS. |
| | |
| | 7) NOTE: PLEASE SEE SOME CONDENSING UNITS ARE SHOWN |
| | WITH THE A/C DISCONNECTS BEHIND THE UNIT. PLEASE SEE |
| | 110.26. THIS IS ONLY ON SOME OF THE UNIT. PLEASE SEE |
| | UNIT B AND C FOR EXAMPLE. |
| | BOTH BUILDINGS. |
| | |
| | 8) NOTE: PLEASE CLARIFY THE SYMBOL BEING USED FOR WATER |
| | HEATER CONNECTION. THIS IS THE SAME SYMBOL WHICH IS |
| | USED FOR THE DRYER. THE DRYER IS PERMITTED TO BE CORD |
| | AND PLUG CONNECTED HOWEVER THE WATER HEATER IS REQUIRED |
| | TO BE HARDWIRED PER 422.30, 422.31. (DISCONNECT ONLY |
| | REQUIRED IF NOT WITHIN SITE). |
| | BOTH BUILDINGS. |
| | |
| | 9) NOTE: PLEASE SEE THERE ARE SOME RECEPTACLES MISSING |
| | PER 210.52 FOR WALL SPACES. |
| | PLEASE SEE WALL SPACE ALONG THE STAIR SIDE OF UNITS IN |
| | LIVING/DINING ROOMS. |
| | PLEASE ALSO SEE SOME UNITS IN KITCHENS WHERE THERE IS |
| | 2FT OR MORE OF WALL SPACE. (UNITS B AND C) PLEASE |
| | VERIFY AND ADJUST IN BOTH BUILDINGS. |
| | |
| | 10) NOTE: PLEASE SEE THE LOAD FOR THE WATER HEATER IS |
| | REQUIRED TO BE FIGURED AT 1255 FOR CONTINUOUS LOAD. |
| | PLEASE SEE 4220.13 AS THIS WAS A CHANGE IN THE 2005 |
| | NEC. PLEASE ADJUST CALCULATIONS. |
| | |
| | 11) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTION WHICH |
| | IS REQUIRED FOR ALL OUTLETS IN SLEEPING ROOMS. PLEASE |
| | SEE 210.12 OF THE 2005 NEC. |
| | PLANS ONLY INDICATE AFCI PROTECTION ON THE RECEPTACLES |
| | HOWEVER THE 2002 AND 2005 CODE EXTENDED THIS PROTECTION |
| | TO SMOKE ALARMS, LIGHTING, FANS ETC. |
| | PLEASE BE SURE TO LIST EACH ON PANEL SCHEDULE. |
| | |
| | 12) NOTE: PLEASE SEE MISSING RECEPTACLE FOR 2FT OR MORE |
| | OF WALL IN BEDROOM #1 ON SECOND FLOOR OF UNITS *C*. |
| | 210.52 |
| | BOTH BUILDINGS. |
| | |
| | 13) NOTE: PLEASE SUBMIT AIC RATINGS FOR ALL SERVICE |
| | EQUIPMENT. MAINS, BREAKERS, PANELS ETC ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | NEC 110.9. |
| | FBC 106.1.2, 106. 3.5.1.2 ETC |
| | |
| | 14) NOTE: PLEASE SEE THE CONDUIT SIZE OF ONE AND ONE |
| | QUARTER INCH IS NOT LARGE ENOUGH BASED ON THE |
| | CONDUCTORS AND CONDUIT TYPE PER TABLES IN CHAPTER 9. AT |
| | POINT WHERE SCHEDULE 80 PVC MAY BE USED THIS EXCEEDS |
| | FILL. |
| | PLEASE ADJUST CONDUIT FOR FEEDERS TO UNITS IN BOTH |
| | BUILDINGS. |
| | |
| | 15) NOTE: PLEASE SEE RISER FOR BUILDING A WHICH |
| | INDICATES 125AMP BREAKERS TYPICAL OF 6, YET THE HOUSE |
| | PANEL IS ONE OF THESE PANELS WHICH IS BEING FED AND THE |
| | PANEL IS ONLY RATED FOR 100AMPS WITH FEEDERS ONLY RATED |
| | FOR 100AMPS. |
| | PLEASE COORDINATE BY DECREASING OVER CURRENT PROTECTION |
| | TO HOUSE PANEL OR INCREASE HOUSE PANEL TO 125AMPS ALONG |
| | WITH FEEDERS. |
| | PLEASE CORRELATE. 240.4, 310.16, 408, 110.14, 110.3 |
| | ETC |
| | |
| | 16) NOTE: PLEASE SEE THE CODE SECTION WHICH IS LISTED |
| | ON LOAD CALCULATIONS ON SHEET E-5 IS NOT FROM THE |
| | CURRENT CODE. PLEASE SEE 220.32 IS LISTED. |
| | PLEASE SEE 2005 NEC, (220.84) |
| | |
| | 17) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS. PLEASE |
| | SUBMIT DETAILS FOR HOW SITE LIGHTING IS BEING |
| | CONTROLLED. |
| | PLEASE SEE 13-415.1.ABC.1.4, 13-415.1.ABC.2, |
| | 13-415.2.ABC.1.3. |
| | PLEASE ALSO SEE NOTES FROM OTHER TRADES (MECHANICAL AND |
| | BUILDING) WHICH MAY MAKE COMMENTS ALSO. |
| | AS THESE ARE NOT SUBMITTED AT THIS TIME, NO REVIEW CAN |
| | BE DONE. |
| | |
| | 18) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS |
| | OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. |
| | IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY |
| | WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, |
| | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND |
| | THIS REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |