Notes
Date Text
2007-09-16 09:56:482007-09-16 09:56:48
  
 ** DENIED **
  
 1) NOTE: *** IMPORTANT***
 AS THERE ARE ITEMS WHICH HAVE NOT YET BEEN SUBMITTED
 FOR PLAN REVIEW OR ON PLANS, SOME ITEMS CAN NOT BE
 REVIEWED AT THIS TIME FOR CODE COMPLIANCE.
 REVIEW CAN ONLY BE PERFORMED ON PLANS AND DOCUMENTS
 SUBMITTED AND THERE MAY VERY WELL BE NEW COMMENTS ON
 THE NEXT REVIEW.
  
 2) NOTE:PLEASE SEE THAT PLANS HAVE ONLY BEEN
 SUBMITTED FOR *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED
 FOR PERMIT APPLICATION. ONCE PLANS ARE CODE COMPLIANT
 REVIEW STATUS WILL BE STILL SHOWN IN A FAILED STATUS
 UNTIL PERMIT APPLICATION HAS BEEN APPLIED. AT TIME OF
 PERMIT APPLICATION AND BEFORE ISSUANCE OF PERMIT
 LICENSING ETC IS VERIFIED.
 ** PLEASE ALSO SEE COMMENTS FROM BUILDING REVIEWER AS
 EACH OF THESE BUILDINGS WILL MOSTLIKELY BE REQUIRED TO
 BE UNDER SEPARATE PERMITS.
  
 3) NOTE: PLEASE SEE THE SITE LIGHTING PLANS ARE NOT
 COMPLETE AT THIS TIME. PLEASE COMPLETE CIRCUITING AND
 CORRELATE WITH THE PANEL SCHEDULE WHICH IS NOTED AS
 HOUSE PANEL.
 PLEASE SUBMIT THE LIGHT POLE INFORMATION FOR
 BUILDING/STRUCTURAL REVIEW. PLEASE SEE THAT THE
 LIGHTING WATTAGES ARE REQUIRED TO BE COMPLETED AT THIS
 TIME AS THIS INFORMATION WILL BE NEEDED IN THE ENERGY
 CALCULATIONS WHICH ARE TO BE SUBMITTED.
 LIGHTING LEGEND INDICATES 60WATT FIXTURES FOR THE
 SYMBOL WHICH IS SHOWN ON PLANS FOR POLE LIGHTS, HOW
 DOES THIS PROVIDE THE PHOTO-METRIC LEVELS AS SHOWN?
 PLEASE CLARIFY THE HOUSE PANEL WHICH INDICATES BUILDING
 LIGHTING YET THE ONLY LIGHTING WHICH COULD BE LOCATED
 ON PLANS FOR BUILDING IS THIS LIGHTING FROM EACH UNIT
 AT THE ENTRANCES/EXITS.
 ** PLEASE COORDINATE ALL SITE LIGHTING AND BUILDING
 LIGHTING INFORMATION WITH PANEL, CIRCUITING, TYPES ETC.
 CAN NOT COMPLETE REVIEW ON THESE ITEMS AT THIS TIME.
  
 4) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED. NO
 PANEL SCHEDULE WAS SUBMITTED INDICATING THE MINIMUM
 REQUIRED CIRCUITS AND COORDINATION WITH PLANS CAN NOT
 BE DONE AT THIS TIME.
 PLEASE SEE THE CONDUCTOR SIZES AND OVER CURRENT/BREAKER
 SIZES FOR ALL CAN NOT BE VERIFIED.
 THERE IS A *PROVIDE PER UNIT* CIRCUIT NOTE LOCATED
 ABOVE UNITS ON BUILDING A. THIS IS NOT NEEDED, BUT MAY
 BE LOCATED ON PLANS. IF THIS IS GOING TO REMAIN PLEASE
 SEE THERE ARE SOME ITEMS WHICH DO NOT CORRELATE WITH
 OTHER INFORMATION ON PLANS.
 EXAMPLES:
 A) PLEASE SEE THE DRYER WHICH IS SHOWN AT 5KW,
 INDICATES THE CIRCUIT TO BE 20AMP.
 B) PLEASE SEE THERE IS A NOTE TO PROVIDE CIRCUIT FOR
 DISHWASHER YET NO DW IS SHOWN ON PLANS?
 C) PLEASE SEE MISSING REQUIRED DEDICATED CIRCUIT(S) FOR
 BATHROOMS PER 210.52D, 210.11C3.
 D) PLEASE SEE MISSING DINING ROOM DESIGNATION/CIRCUIT
 PER 210.52B1, 210.11C1, 220.53. AS THE CIRCUITING IS
 NOT SHOWN THIS CAN NOT BE VERIFIED AT THIS TIME FOR
 DINING.
 PLEASE COMPLETE AND SEE SOME NOTES BELOW FOR ITEMS
 WHICH WILL BE NEEDED ON PANEL SCHEDULE.
 408.4, 310.16, 240.4 ETC.
 FBC 106.3.5.4
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY
 FROM THE NEC CODE COMMENTARY.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2, 106.3.5.4.
 BOTH BUILDINGS. (THIS CAN BE A TYPICAL PANEL SCHEDULE
 FOR EACH OF THE UNITS WHICH ARE THE SAME).
  
 5) NOTE: PLEASE CLARIFY THE SYMBOL BEING USED FOR THE
 SMOKE ALARMS. THIS SD IS A TYPICAL UNIVERSAL SYMBOL FOR
 SMOKE DETECTOR WHICH BY DEFINITION IN NFPA-72 IS A
 DEVICE WHICH ONLY DETECTS AND DOES NOT SOUND AN ALARM.
 PLEASE VERIFY.
 BOTH BUILDINGS.
  
 6) NOTE: PLEASE CLARIFY THE LOCATION OF THE DISHWASHER
 AS NOTED ABOVE IN NOTE #4. PLEASE KNOW IF THIS FROM THE
 SAME DEVICE/YOKE AS THE DISPOSAL (DEPENDING ON
 LOCATION) THEN THE BREAKER/OVER CURRENT PROTECTION IN
 THE PANEL SCHEDULE TO BE SUBMITTED WOULD BE REQUIRED TO
 BE 2-POLE.
 210.4B
 BOTH BUILDINGS.
  
 7) NOTE: PLEASE SEE SOME CONDENSING UNITS ARE SHOWN
 WITH THE A/C DISCONNECTS BEHIND THE UNIT. PLEASE SEE
 110.26. THIS IS ONLY ON SOME OF THE UNIT. PLEASE SEE
 UNIT B AND C FOR EXAMPLE.
 BOTH BUILDINGS.
  
 8) NOTE: PLEASE CLARIFY THE SYMBOL BEING USED FOR WATER
 HEATER CONNECTION. THIS IS THE SAME SYMBOL WHICH IS
 USED FOR THE DRYER. THE DRYER IS PERMITTED TO BE CORD
 AND PLUG CONNECTED HOWEVER THE WATER HEATER IS REQUIRED
 TO BE HARDWIRED PER 422.30, 422.31. (DISCONNECT ONLY
 REQUIRED IF NOT WITHIN SITE).
 BOTH BUILDINGS.
  
 9) NOTE: PLEASE SEE THERE ARE SOME RECEPTACLES MISSING
 PER 210.52 FOR WALL SPACES.
 PLEASE SEE WALL SPACE ALONG THE STAIR SIDE OF UNITS IN
 LIVING/DINING ROOMS.
 PLEASE ALSO SEE SOME UNITS IN KITCHENS WHERE THERE IS
 2FT OR MORE OF WALL SPACE. (UNITS B AND C) PLEASE
 VERIFY AND ADJUST IN BOTH BUILDINGS.
  
 10) NOTE: PLEASE SEE THE LOAD FOR THE WATER HEATER IS
 REQUIRED TO BE FIGURED AT 1255 FOR CONTINUOUS LOAD.
 PLEASE SEE 4220.13 AS THIS WAS A CHANGE IN THE 2005
 NEC. PLEASE ADJUST CALCULATIONS.
  
 11) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTION WHICH
 IS REQUIRED FOR ALL OUTLETS IN SLEEPING ROOMS. PLEASE
 SEE 210.12 OF THE 2005 NEC.
 PLANS ONLY INDICATE AFCI PROTECTION ON THE RECEPTACLES
 HOWEVER THE 2002 AND 2005 CODE EXTENDED THIS PROTECTION
 TO SMOKE ALARMS, LIGHTING, FANS ETC.
 PLEASE BE SURE TO LIST EACH ON PANEL SCHEDULE.
  
 12) NOTE: PLEASE SEE MISSING RECEPTACLE FOR 2FT OR MORE
 OF WALL IN BEDROOM #1 ON SECOND FLOOR OF UNITS *C*.
 210.52
 BOTH BUILDINGS.
  
 13) NOTE: PLEASE SUBMIT AIC RATINGS FOR ALL SERVICE
 EQUIPMENT. MAINS, BREAKERS, PANELS ETC ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 NEC 110.9.
 FBC 106.1.2, 106. 3.5.1.2 ETC
  
 14) NOTE: PLEASE SEE THE CONDUIT SIZE OF ONE AND ONE
 QUARTER INCH IS NOT LARGE ENOUGH BASED ON THE
 CONDUCTORS AND CONDUIT TYPE PER TABLES IN CHAPTER 9. AT
 POINT WHERE SCHEDULE 80 PVC MAY BE USED THIS EXCEEDS
 FILL.
 PLEASE ADJUST CONDUIT FOR FEEDERS TO UNITS IN BOTH
 BUILDINGS.
  
 15) NOTE: PLEASE SEE RISER FOR BUILDING A WHICH
 INDICATES 125AMP BREAKERS TYPICAL OF 6, YET THE HOUSE
 PANEL IS ONE OF THESE PANELS WHICH IS BEING FED AND THE
 PANEL IS ONLY RATED FOR 100AMPS WITH FEEDERS ONLY RATED
 FOR 100AMPS.
 PLEASE COORDINATE BY DECREASING OVER CURRENT PROTECTION
 TO HOUSE PANEL OR INCREASE HOUSE PANEL TO 125AMPS ALONG
 WITH FEEDERS.
 PLEASE CORRELATE. 240.4, 310.16, 408, 110.14, 110.3
 ETC
  
 16) NOTE: PLEASE SEE THE CODE SECTION WHICH IS LISTED
 ON LOAD CALCULATIONS ON SHEET E-5 IS NOT FROM THE
 CURRENT CODE. PLEASE SEE 220.32 IS LISTED.
 PLEASE SEE 2005 NEC, (220.84)
  
 17) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS. PLEASE
 SUBMIT DETAILS FOR HOW SITE LIGHTING IS BEING
 CONTROLLED.
 PLEASE SEE 13-415.1.ABC.1.4, 13-415.1.ABC.2,
 13-415.2.ABC.1.3.
 PLEASE ALSO SEE NOTES FROM OTHER TRADES (MECHANICAL AND
 BUILDING) WHICH MAY MAKE COMMENTS ALSO.
 AS THESE ARE NOT SUBMITTED AT THIS TIME, NO REVIEW CAN
 BE DONE.
  
 18) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-16 08:27:512007-09-16 08:27:51
  
 IN PROGRESS
2007-09-15 21:39:422007-09-15 21:39:42
  
 IN ELEC FOR REVIEW.