| 2007-09-21 15:34:29 | BUILDING PLAN REVIEW |
| | PERMIT: 07080639 |
| | ADD: 605-609 PBL BLVD. |
| | CONT: |
| | TEL: (561)310-1739 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 / 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | NOTE: DUE TO THE FACT THAT A TRUE PROPERTY LINE IS NOT |
| | SHOWN ON THE DRAWINGS FOR EACH UNIT, AND THE TYPE AND |
| | OCCUPANCY OF THE BUILDINGS ARE NOT INDICATED ON THE |
| | DRAWINGS, THE REVIEW WILL BE IN ACCORDANCE WITH THE FBC |
| | 2004 AND THE 2006/2007 FBC REVISIONS. THE TWO BUILDINGS |
| | DOES NOT MEET THE DEFINITION OF ?TOWNHOUSE? THEREFORE, |
| | THE WORD SHALL BE REMOVED FROM THE DRAWINGS. |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FBC 106 ALL PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS PREPARED BY A DESIGN PROFESSIONAL AND BEING |
| | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE, |
| | PRINTED NAME, SEAL, ADDRESS AND LICENSE NUMBER OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENTS, IN |
| | ACCORDANCE WITH FLORIDA STATUTES 481 AND 471. |
| | |
| | 3)2004 FL. BLD CODE 1603.1.4 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE |
| | CONSTRUCTION DRAWINGS, |
| | 1) - BASIC WIND SPEED, MPH |
| | 2) - WIND IMPORTANCE FACTOR, & BUILDING CATEGORY |
| | 3) - WIND EXPOSURE |
| | 4) - INTERNAL PRESSURE COEFFICIENT, |
| | 5) - COMPONENTS & CLADDING, THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF. |
| | |
| | 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| | TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT |
| | . ------------------------------------- |
| | ) NUMBER OF UNITS |
| | ) NUMBER OF FLOORS |
| | ) NUMBER OF BEDROOMS |
| | ) NUMBER OF ROOMS |
| | ) NUMBER OF BEDROOMS |
| | ) SQ. FT. LIV SPACE/ FL |
| | ) SQ. FT. FOOTPRINT |
| | |
| | 5)109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, |
| | DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 6)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 7)FBC 1802.2.1 QUESTIONABLE SOIL. WHERE THE BEARING |
| | CAPACITY OF THE SOIL IS NOT DEFINITELY KNOWN OR IS IN |
| | QUESTION, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| | NECESSARY INVESTIGATION BE MADE. THE INVESTIGATION |
| | SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4 |
| | THROUGH 1802.6 OF THE FBC. THE INVESTIGATION SHALL BE |
| | CERTIFIED BY A GEOTECHNICAL REPORT FROM A DESIGN |
| | PROFESSIONAL PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 8)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2). IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6). |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 9)FBC 1609.6.2.2 COMPONENTS & CLADDING.PROVIDE 2 |
| | COPIES OF PRODUCT TESTING REPORTS FOR THE FOLLOWING A) |
| | WINDOWS B) SWINGING DOORS C) MULLIONS D) ROOFING |
| | MATERIALS. SEE POLICY IN PACKAGE, E) F) STRUCTURAL |
| | COMPONENTS ? WOOD CONNECTORS, ANCHORS SEE RULE 9B-72. |
| | |
| | 10)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS |
| | THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. SUBMIT THE |
| | PRODUCT APPROVALS FOR WINDOWS, DOORS, ROOFING |
| | MATERIALS, AND STRUCTURAL COMPONENTS ETC. |
| | |
| | 11)FBC 1209.2 ATTIC SPACES. |
| | AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM |
| | BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A |
| | CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762 |
| | MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE |
| | PROVIDED AT OR ABOVE THE ACCESS OPENING. INDICATE THE |
| | SIZE OF THE ATTIC ACCESS ON THE PLANS. |
| | |
| | 12)FBC 2303.4.1 TRUSS CONSTRUCTION DOCUMENTS SHALL |
| | CONFORM TO THIS SECTION OF THE FBC AND SHALL BE |
| | PREPARED BY A REGISTERED DESIGN PROFESSIONAL AND |
| | SUBMITTED TO THE BUILDING OFFICIAL PRIOR TO |
| | INSTALLATION. |
| | |
| | 13)FBC 803.5.INTERIOR WALLS AND CEILING FINISH |
| | SHALL HAVE A FLAME SPREAD INDEX NOT GREATER THAN THAT |
| | SPECIFIED IN TABLE 803.5. STATE THE INTERIOR FINISH OF |
| | THE BUILDINGS. |
| | |
| | 14)FL ENERGY EFFICIENCY CODE 400.ABCD. THE PERSON |
| | PREPARING THE COMPLIANCE CALCULATION SHALL CERTIFY THAT |
| | THE CALCULATION IS TRUE AND ACCURATE & DEMONSTRATES |
| | THAT THE BUILDING IS IN COMPLIANCE. SEE SUBCHAPTER 13-6 |
| | OF THE FBC. |
| | |
| | 15)FBC 1203.2 INDICATE ON THE DRAWINGS THE CROSS |
| | VENTILATION OF THE ATTIC SPACE. THE NET FREE |
| | VENTILATING AREA SHALL NOT BE LESS THAN 1/150 OF THE |
| | AREA OF THE SPACE VENTILATED. THE MINIMUM OPENINGS |
| | SHALL BE 1/8 INCH AND SHALL NOT EXCEED ? INCH. |
| | |
| | 16)THE ROOF AND FLASHING INFORMATION ON SHEET A-15 |
| | SHALL BE REVIEWED TO CH.15 OF THE 2004 FBC. |
| | |
| | 17)INDICATE THE FIRE-RESISTANCE RATING (HOURS) FOR |
| | THE MASONRY DEMISING WALLS IN ACCORDANCE WITH TABLE |
| | 721.2.3(1). |
| | |
| | 104.2.1 W.P.B. ADMINISTRATIVE CODE.DRAWINGS & |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC AND |
| | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| | IN PART, NOR THE TERM "LEGAL" OR ITS RQUIVALENT BE |
| | USED |
| | AS A SUBSTITUTE FOR SPECIFIC INFORMATION" |
| | |
| | NOTE: THE ABBREVIATION LEGEND ON SHEET SP ? 1 IS NOT |
| | LEGIBLE. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |