2007-09-21 15:34:29BUILDING PLAN REVIEW
 PERMIT: 07080639
 ADD: 605-609 PBL BLVD.
 CONT:
 TEL: (561)310-1739
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 / 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 NOTE: DUE TO THE FACT THAT A TRUE PROPERTY LINE IS NOT
 SHOWN ON THE DRAWINGS FOR EACH UNIT, AND THE TYPE AND
 OCCUPANCY OF THE BUILDINGS ARE NOT INDICATED ON THE
 DRAWINGS, THE REVIEW WILL BE IN ACCORDANCE WITH THE FBC
 2004 AND THE 2006/2007 FBC REVISIONS. THE TWO BUILDINGS
 DOES NOT MEET THE DEFINITION OF ?TOWNHOUSE? THEREFORE,
 THE WORD SHALL BE REMOVED FROM THE DRAWINGS.
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FBC 106 ALL PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY A DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE,
 PRINTED NAME, SEAL, ADDRESS AND LICENSE NUMBER OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENTS, IN
 ACCORDANCE WITH FLORIDA STATUTES 481 AND 471.
  
 3)2004 FL. BLD CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE
 CONSTRUCTION DRAWINGS,
 1) - BASIC WIND SPEED, MPH
 2) - WIND IMPORTANCE FACTOR, & BUILDING CATEGORY
 3) - WIND EXPOSURE
 4) - INTERNAL PRESSURE COEFFICIENT,
 5) - COMPONENTS & CLADDING, THE DESIGN WIND PRESSURES
 IN TERMS OF PSF.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 . -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF BEDROOMS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
  
 5)109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7)FBC 1802.2.1 QUESTIONABLE SOIL. WHERE THE BEARING
 CAPACITY OF THE SOIL IS NOT DEFINITELY KNOWN OR IS IN
 QUESTION, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. THE INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 OF THE FBC. THE INVESTIGATION SHALL BE
 CERTIFIED BY A GEOTECHNICAL REPORT FROM A DESIGN
 PROFESSIONAL PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 8)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2). IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6).
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 9)FBC 1609.6.2.2 COMPONENTS & CLADDING.PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS FOR THE FOLLOWING A)
 WINDOWS B) SWINGING DOORS C) MULLIONS D) ROOFING
 MATERIALS. SEE POLICY IN PACKAGE, E) F) STRUCTURAL
 COMPONENTS ? WOOD CONNECTORS, ANCHORS SEE RULE 9B-72.
  
 10)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. SUBMIT THE
 PRODUCT APPROVALS FOR WINDOWS, DOORS, ROOFING
 MATERIALS, AND STRUCTURAL COMPONENTS ETC.
  
 11)FBC 1209.2 ATTIC SPACES.
 AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM
 BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A
 CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762
 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT OR ABOVE THE ACCESS OPENING. INDICATE THE
 SIZE OF THE ATTIC ACCESS ON THE PLANS.
  
 12)FBC 2303.4.1 TRUSS CONSTRUCTION DOCUMENTS SHALL
 CONFORM TO THIS SECTION OF THE FBC AND SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL PRIOR TO
 INSTALLATION.
  
 13)FBC 803.5.INTERIOR WALLS AND CEILING FINISH
 SHALL HAVE A FLAME SPREAD INDEX NOT GREATER THAN THAT
 SPECIFIED IN TABLE 803.5. STATE THE INTERIOR FINISH OF
 THE BUILDINGS.
  
 14)FL ENERGY EFFICIENCY CODE 400.ABCD. THE PERSON
 PREPARING THE COMPLIANCE CALCULATION SHALL CERTIFY THAT
 THE CALCULATION IS TRUE AND ACCURATE & DEMONSTRATES
 THAT THE BUILDING IS IN COMPLIANCE. SEE SUBCHAPTER 13-6
 OF THE FBC.
  
 15)FBC 1203.2 INDICATE ON THE DRAWINGS THE CROSS
 VENTILATION OF THE ATTIC SPACE. THE NET FREE
 VENTILATING AREA SHALL NOT BE LESS THAN 1/150 OF THE
 AREA OF THE SPACE VENTILATED. THE MINIMUM OPENINGS
 SHALL BE 1/8 INCH AND SHALL NOT EXCEED ? INCH.
  
 16)THE ROOF AND FLASHING INFORMATION ON SHEET A-15
 SHALL BE REVIEWED TO CH.15 OF THE 2004 FBC.
  
 17)INDICATE THE FIRE-RESISTANCE RATING (HOURS) FOR
 THE MASONRY DEMISING WALLS IN ACCORDANCE WITH TABLE
 721.2.3(1).
  
 104.2.1 W.P.B. ADMINISTRATIVE CODE.DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC AND
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS RQUIVALENT BE
 USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION"
  
 NOTE: THE ABBREVIATION LEGEND ON SHEET SP ? 1 IS NOT
 LEGIBLE.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  