| 2007-11-01 16:59:46 | DENIED 2ND TIME |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW ON THE SUBMITTED SANITARY |
| | ISOMETRIC RISER DIAGRAM TO MEET CODE COMPLIANCE: |
| | |
| | 1. PER FBC-2004, CHAPTER 1, SECTION |
| | 106.1.3, QUALITY OF BUILDING PLANS: BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. THE |
| | SUBMITTED PLANS ARE NOT DRAWN TO SCALE. PLEASE CLEARLY |
| | INDICATE THE SCALE OF WHICH PLANS ARE DRAWN TO AND |
| | CLEARLY INDICATE THE DIMENSIONS OF THE BATHROOM ON THE |
| | RESUBMITTAL. |
| | |
| | 2. PER FBC-2004 W/05 & 06 REVISIONS CHAPTER 7, |
| | SANITARY DRAINAGE, SECTION 701.1 AND CHAPTER 9, VENTS |
| | SECTION 401.1 SCOPE. THE SUBMITTED SANITARY ISOMETRIC |
| | RISER DIAGRAM DESIGN IS NOT CODE COMPLIANT AND DOES NOT |
| | REFLECT THE FLOOR PLAN. PLEASE REFERENCE THE EXAMPLE |
| | ISOMETRIC ATTACHED TO THE PLUMBING COMMENTS THAT IS |
| | CODE COMPLIANT AND REFLECTS THE FLOOR PLAN ON THE |
| | RESUBMITTAL. |
| | |
| | 3. THE BRANCH DRAINAGE FITTING FOR THE KITCHEN SINK IS |
| | GOING THE WRONG WAY. PER *706.3 INSTALLATION OF |
| | FITTINGS. FITTINGS SHALL BE INSTALLED TO GUIDE SEWAGE |
| | AND WASTE IN THE DIRECTION OF FLOW. |
| | |
| | 4. PER *708.3.5 BUILDING DRAIN AND BUILDING SEWER |
| | JUNCTION. PLEASE INDICATE THE CLEANOUT AS A TWO-WAY |
| | CLEANOUT ON THE RESUBMITTAL. |
| | |
| | 5. PER *901.2.1 VENTING REQUIRED. A VENT IS REQUIRED |
| | FOR THE KITCHEN SINK AND BATHROOM LAVATORY. |
| | |
| | 6. PER *TABLE 906.1 MAXIMUM DISTANCE OF FIXTURE TRAP |
| | FROM VENT. DUE TO THE FACT THAT PLANS ARE NOT DRAWN TO |
| | SCALE (REFERENCE COMMENT #1) IT IS IMPOSSIBLE TO TELL |
| | WHAT THE TRAP DISTANCE FROM THE VENT IS FOR THE SHOWER. |
| | NOTE: THE 1-1/2" FIXTURE DRAIN WITH 1-1/2" TRAP FOR THE |
| | SHOWER CAN ONLY BE 5' FROM VENT. THIS PIPING MAY NEED |
| | TO BE INCREASED. |
| | |
| | 7. THE KITCHEN SINK MUST DRAIN DOWNSTREAM OF THE WET |
| | VENTED BATHROOM GROUP. PER *909.1 WET VENT PERMITTED. |
| | ONLY THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL |
| | CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY |
| | ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE |
| | WET VENT. |
| | |
| | 8. THE "S" TRAP FOR THE BATHROOM LAVATORY IS ILLEGAL. |
| | PER *1002.3 PROHIBITED TRAPS. (5) "S" TRAPS ARE |
| | PROHIBITED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |