Plan Review Notes
Plan Review Notes For Permit 07080630
Permit Number 07080630
Review Stop P
Sequence Number 2
Notes
Date Text
2007-11-01 16:59:46DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW ON THE SUBMITTED SANITARY
 ISOMETRIC RISER DIAGRAM TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004, CHAPTER 1, SECTION
 106.1.3, QUALITY OF BUILDING PLANS: BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. THE
 SUBMITTED PLANS ARE NOT DRAWN TO SCALE. PLEASE CLEARLY
 INDICATE THE SCALE OF WHICH PLANS ARE DRAWN TO AND
 CLEARLY INDICATE THE DIMENSIONS OF THE BATHROOM ON THE
 RESUBMITTAL.
  
 2. PER FBC-2004 W/05 & 06 REVISIONS CHAPTER 7,
 SANITARY DRAINAGE, SECTION 701.1 AND CHAPTER 9, VENTS
 SECTION 401.1 SCOPE. THE SUBMITTED SANITARY ISOMETRIC
 RISER DIAGRAM DESIGN IS NOT CODE COMPLIANT AND DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE REFERENCE THE EXAMPLE
 ISOMETRIC ATTACHED TO THE PLUMBING COMMENTS THAT IS
 CODE COMPLIANT AND REFLECTS THE FLOOR PLAN ON THE
 RESUBMITTAL.
  
 3. THE BRANCH DRAINAGE FITTING FOR THE KITCHEN SINK IS
 GOING THE WRONG WAY. PER *706.3 INSTALLATION OF
 FITTINGS. FITTINGS SHALL BE INSTALLED TO GUIDE SEWAGE
 AND WASTE IN THE DIRECTION OF FLOW.
  
 4. PER *708.3.5 BUILDING DRAIN AND BUILDING SEWER
 JUNCTION. PLEASE INDICATE THE CLEANOUT AS A TWO-WAY
 CLEANOUT ON THE RESUBMITTAL.
  
 5. PER *901.2.1 VENTING REQUIRED. A VENT IS REQUIRED
 FOR THE KITCHEN SINK AND BATHROOM LAVATORY.
  
 6. PER *TABLE 906.1 MAXIMUM DISTANCE OF FIXTURE TRAP
 FROM VENT. DUE TO THE FACT THAT PLANS ARE NOT DRAWN TO
 SCALE (REFERENCE COMMENT #1) IT IS IMPOSSIBLE TO TELL
 WHAT THE TRAP DISTANCE FROM THE VENT IS FOR THE SHOWER.
 NOTE: THE 1-1/2" FIXTURE DRAIN WITH 1-1/2" TRAP FOR THE
 SHOWER CAN ONLY BE 5' FROM VENT. THIS PIPING MAY NEED
 TO BE INCREASED.
  
 7. THE KITCHEN SINK MUST DRAIN DOWNSTREAM OF THE WET
 VENTED BATHROOM GROUP. PER *909.1 WET VENT PERMITTED.
 ONLY THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT.
  
 8. THE "S" TRAP FOR THE BATHROOM LAVATORY IS ILLEGAL.
 PER *1002.3 PROHIBITED TRAPS. (5) "S" TRAPS ARE
 PROHIBITED.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731