| 2007-10-17 12:01:17 | 2004 FBC W/2007 REVISIONS |
| | LEVEL 1 ALTERATION |
| | |
| | DENIED BY BUILDING |
| | |
| | DUE TO THE FACT THAT THERE IS NO EVIDENCE INDICATING |
| | THAT THE DETACHED GARAGE WAS CONVERTED TO LIVING SPACE |
| | WITH PERMITS, THE REQUIREMENTS OF THE 2004 FLORIDA |
| | BUILDING CODE EXISTING BUILDING CHAPTER 8 WILL NEED TO |
| | BE ADDRESSED. THE WINDLOAD ANALYSIS FROM MICHEAL JOHN |
| | DOCSH, ARCHITECT IS ACCEPTABLE. IT IS NOTED THAT THE |
| | STRUCTURE IS A CONTRIBUTING PROPERTY IN AN OFFICIAL |
| | MUNICIPAL HISTORIC DISTRICT. |
| | |
| | 1) SECTION 812.5 REQUIRES COMPLIANCE WITH FBC CHAPTER |
| | 11. THEREFORE, THE BATHROOM DOOR IS REQUIRED BY FBC |
| | 11-4.22.2 TO HAVE A DOOR WITH A 29" CLEAR OPENING. SHOW |
| | COMPLIANCE. |
| | |
| | 2) THE REQUIREMENTS FOR IMPACT FEES ARE THE |
| | RESPONSIBILITY OF PALM BEACH COUNTY. THEREFORE, THE |
| | INFORMATION WILL NEED TO BE REVIEWED BY THE COUNTY TO |
| | DETERMINE IF ANY IMPACT FEES FOR THE CONVERSION ARE |
| | OWED. PLEASE HAVE THE DRAWINGS STAMPED BY THE COUNTY |
| | FOR IMPACT FEES AND SUBMIT A COPY OF THE IMPACT FEE |
| | RECEIPT. |
| | |
| | 3) THE PLUMBING WILL NEED TO BE REVIEWED AND INSPECTED |
| | FOR CODE COMPLIANCE. SUBMIT PLUMBING PLANS FOR THE |
| | EXISTING BATHROOM AND KITCHEN. |
| | |
| | 4) THE OWNER BUILDER EXEMPTION UNDER FLORIDA STATUTE |
| | 489.103 (7)(A) PROHIBITS THE SALE OR LEASE OF THE |
| | IMPROVED RESIDENCE FOR ONE YEAR. IF THE COTTAGE IS TO |
| | BE RENTED WITHIN ONE YEAR, A LICENSED CONTRACTOR WILL |
| | BE REQUIRED TO APPLY FOR THE PERMIT. PLEASE SHOW |
| | COMPLIANCE. |
| | |
| | - ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |