| Date |
Text |
| 2008-07-31 14:39:27 | ** DENIED3RD REVIEW ** |
| | |
| | ** THERE ARE STILL COMMENTS FROM PREVIOUS REVIEW ALONG |
| | WITH SEVERAL NEW COMMENTS BASED ON NEW INFORMATION NOW |
| | BEING PROVIDED. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THE BASE BUILDING PERMIT #06011130 |
| | WHICH WAS PREVIOUSLY FOR THE SHELL BUILDING HAS BEEN |
| | EXPIRED DUE TO INACTIVITY UNDER THE FBC 105.3.2 BY |
| | HAROLD PISKURA |
| | PERMIT FOR BASE BUILDING NEEDS TO BE RE-APPLIED FOR |
| | FINALS. |
| | PLEASE ALSO KNOW AS THE BASE BUILDING DESIGN TEAM IS |
| | RESPONSIBLE FOR SUCH BUILDING UNTIL SUCH TIME AS |
| | CERTIFICATE OF COMPLETION OR CERTIFICATE OF OCCUPANCY |
| | IS ISSUED ALL PLANS FOR PERMITTED WORK WHILE A SHELL |
| | BUILDING IS UNDER CONSTRUCTION SHALL CONTAIN A *SHOP |
| | DRAWING* REVIEW STAMP AND SIGNATURE FROM EACH DESIGNER |
| | ON THEIR RESPECTIVE PAGES BEFORE PERMIT MAY BE ISSUED |
| | FOR TENANT BUILD OUT. |
| | FS 471,481. ONCE THE SHELL OBTAINS AS C OF C ETC THEN |
| | THE PLANS DO NOT NEED TO GO BACK TO THE BASE BUILDING |
| | DESIGN TEAM. |
| | |
| | 2) NOTE: PLEASE KNOW AS THE BASE BUILDING/SHELL |
| | CONTRACTOR IS THE SAME AS APPLIED FOR THIS SCOPE OF |
| | WORK A LETTER OF UNDERSTANDING IS NOT REQUIRED. |
| | |
| | 3) NOTE: PLEASE KNOW THIS IS THE FIRST TIME ENERGY |
| | CALCULATIONS ARE BEING SUBMITTED. THE PREVIOUS TWO |
| | REVIEWS REQUESTED LIGHTING PERFORMANCE CALCULATIONS AND |
| | THE SPECIFIC CODE SECTIONS GIVEN WERE |
| | 13-415.2.ABC.1.1,.1.2 AN D.1.3. THE CODE SECTIONS FOR |
| | METHOD OF CALCULATIONS GIVEN WERE 13-400.3.B, |
| | 13-400.3.C. SECTION 13-400.3.A WAS NOT GIVEN AS METHOD |
| | *A* MAY NOT BE USED. |
| | PLANS WERE SUBMITTED WITH METHOD *A*. PLEASE SEE THE |
| | FLORIDA BUILDING CODE 13-400.0.A, 13-101.1.1. PLEASE |
| | EXPLAIN HOW METHOD *A* MAY BE USED WHEN THIS TENANT |
| | BUILDING IS NOT A WHOLE BUILDING. |
| | PLEASE SEE THAT IN ANY CASE THE INFORMATION AS |
| | SUBMITTED AND SHOWN ON THE INPUT DATA REPORT IS NOT |
| | COMPLETE NOR DOES IT COORDINATE WITH PLANS IN SEVERAL |
| | ASPECTS. SOME EXAMPLES WILL BE NOTED BY THIS REVIEWER |
| | AND PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES AS |
| | WELL. |
| | PLEASE SEE 13-103.1. MEETING THE EXCEPTIONS UNDER FS |
| | 471.003 AND THIS SECTION OF THE FBC REQUIRES LICENSED |
| | DESIGNER. |
| | |
| | FOR EXAMPLE: |
| | THE IDR SHOWS ONLY TWO (2) LIGHT FIXTURES ON THE |
| | INTERIOR OF THIS SPACE. HOW IS THIS POSSIBLE WHEN IN |
| | FACT THE PLANS SHOW MANY FIXTURES? THE FACT IS THE ONLY |
| | TWO FIXTURES SHOWN ARE 2 WATTS EACH. THIS IS NOT |
| | POSSIBLE AS THE PLANS DO NOT CORRELATE WITH ANY OF |
| | THIS. |
| | |
| | FORE EXAMPLE; |
| | ONLY ONE WALL UNDER WALLS, NO WINDOWS, NO DOORS, METAL |
| | BUILDING ETC. THESE WILL BE NOTED BY OTHER TRADES |
| | HOWEVER ARE GIVEN FOR INFORMATION AT THIS TIME. |
| | |
| | 4) NOTE: PLEASE KNOW ELECTRICAL SERVICE AS SHOWN ON |
| | THESE PLANS DOES NOT COORDINATE WITH THE ELECTRICAL |
| | SERVICE ON THE BASE BUILDING. IN FACT THE ELECTRICAL |
| | SERVICE ON THE BASE BUILDING WHICH ALREADY HAS A FINAL |
| | CONTAINS MANY ITEMS WHICH ARE NOT THE SAME. |
| | MAINS ARE 125 AMP |
| | THERE IS A HOUSE PANEL NOT SHOWN. |
| | THE SERVICE SIZE IS NOT 400AMPS. |
| | THE GROUNDING ELECTRODE SYSTEM IS NOT THE SAME AND |
| | MEETS 250.50,250.24,250.6 ETC |
| | PLEASE EXPLAIN HOW THE GUTTER HAS AN EQUAL POTENTIAL IF |
| | THE NEUTRAL IS FLOATING TO THE FIRST MEANS OF |
| | DISCONNECT. BASED ON THE CODE AND THE RISER FOR BASE |
| | BUILDING THE SYSTEM AS SHOWN ON THIS RISER MAY NOT BE |
| | DONE TO MEET THE CODE. |
| | PLAN SHOWS THREE DISCONNECTS/MAINS |
| | 215.5, 230.70, 230.71, 230.72, 240.4, 310.16, 250.6, |
| | 250.24 ETC |
| | |
| | 5) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR CONTROL OF |
| | EXTERIOR LIGHTING. PLANS MENTIONS TIME CLOCK HOWEVER |
| | NOT FOR ALL LIGHTS AND ALSO SHOWS STANDARD SINGLE POLE |
| | SWITCH. MUST MEET ONE OF THE TWO MINIMUMS IN SECTION OF |
| | CODE GIVEN OR BOTH. |
| | |
| | ** BASED ON COMMENTS ABOVE ONE SET OF CALCULATIONS |
| | ALONG WITH ONE COPY OF ELECTRICAL PLANS ARE BEING |
| | RETAINED BY THIS OFFICE. |
| | |
| | ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE |
| | NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | ***AS THERE ARE MANY ASPECTS OF THE BUILDING AND |
| | CALCULATIONS NOT COMPLETE AT THIS TIME THERE MAY VERY |
| | WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| | |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |