| 2008-08-21 15:11:10 | |
| | |
| | 3RD RREVIEW |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07080606 |
| | ADD: 2037 SPRUCE AVE |
| | CONT: JHAMTEC CONSTRUCTION |
| | TEL: (561)602-0009 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 3RD AUGUST 21, 2008 |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) OK |
| | |
| | DUE TO THE FACT THAT PERMIT #06011130 IS AN EXPIRED |
| | PERMIT AND THE BUILDING DOES NOT HAVE A CERTIFICATE OF |
| | OCCUPANCY OR FINAL INSPECTION THE SHALL MEET THE |
| | REQUIREMENTS OF THE SECTION BELOW. |
| | NOTE: THE REVISION #1 TO THE DOOR ON SHEET A-1 DOES NOT |
| | COMPLY WITH FIGURE 24. A 2'-8" X 6'- 8" DOOR WILL NOT |
| | MEET THE 32" MINIMUM REQUIREMENT. THE DISTANCE SHALL BE |
| | MEASURED FROM THE INSIDE FACE OF THE DOOR TO THE FACE |
| | OF THE DOOR STOP. PLEASE TAKE A LOOK AT THE DRAWING |
| | SUBMITTED ON SHEET A-1. SEE CODE SECTION MENTION BELOW. |
| | ACCESSIBLE PARKING SPACES SERVING BUILDINGS SHALL BE |
| | LOCATED ON THE SHORTEST ROUTE. |
| | 4) 11-4.1.6(2) DUTY TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO ALTERED AREAS SHALL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20 % OF THE COST OF THE ALTERATION TO THE |
| | PRIMARY FUNCTION AREA. |
| | (A)(I) OK |
| | (II) AN ACCESSIBLE ROUTE |
| | (III) OK |
| | (IIII) OK |
| | |
| | FRONT ENTRY DOOR, A PAIR OF 5'-0" DOORS, SEE11-4.13.5 |
| | CLEAR WIDTH. DOORWAYS SHALL HAVE A MINIMUM CLEAR |
| | OPENING OF 32 INCHES WITH THE DOOR OPEN 90 DEGREES, |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE |
| | STOP [SEE FIGURE 24 (A), FIGURE 24 (B), FIGURE 24 (C), |
| | AND FIGURE 24 (D)]. OPENINGS MORE THAN 24 INCHES (610 |
| | MM) IN DEPTH SHALL COMPLY WITH SECTIONS 11-4.2.1 AND |
| | 11-4.3.3 [SEE FIGURE 24 (E)]. |
| | |
| | 5) OK |
| | |
| | 6) OK |
| | 7) OK |
| | |
| | **NOTE: ACCESSIBLE PARKING SHALL BE LOCATED ON THE |
| | SHORTEST ROUTE TO THE ENTRANCE OF THE BUILDING. THE |
| | PARKING LOT DOES NOT HAVE A FINAL INSPECTION THEREFORE, |
| | THE ISSUE OF THE ACCESSIBLE PARKING HAS TO BE |
| | ADDRESSED** |
| | 8) THE SITE PLAN DOES NOT INDICATE ANY ACCESSIBLE |
| | PARKING PLEASE INDICATE THE HANDICAPPED PARKING AND |
| | ACCESS ISLE. 11-4.6.2 LOCATION. ACCESSIBLE PARKING |
| | SPACES SERVING A PARTICULAR BUILDING SHALL BE LOCATED |
| | ON THE SHORTEST SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM |
| | ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE. IN PARKING |
| | FACILITIES THAT DO NOT SERVE A PARTICULAR BUILDING, |
| | ACCESSIBLE PARKING SHALL BE LOCATED ON THE SHORTEST |
| | ACCESSIBLE ROUTE OF TRAVEL TO AN ACCESSIBLE PEDESTRIAN |
| | ENTRANCE OF THE PARKING FACILITY. |
| | |
| | **3RD REQUEST** |
| | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| | APPLICABLE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |