| 2008-04-10 12:51:49 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | MUNICIPAL CODE WPB |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | |
| | 6. SHT P-1 THE GREASE INTERCEPTOR SHALL BE SIZED BY THE |
| | UTILITY DEPT., INDUSTRIAL PRETREATMENT, ENVIRONMENTAL |
| | COMPLIANCE. PLEASE CONTACT EITHER RODNEY COMPO, (561) |
| | 822-2272, E-MAIL [email protected] OR CALVIN WILLIAMS |
| | (561) 822-2284, E-MAIL CWILLIAMS @WPB.ORG. THEIR FAX IS |
| | (561) 822-2287. A PRINTED DETERMINATION SHALL BE |
| | PRODUCED AND SUBMITTED WITH PLANS SHOWING INTERCEPTOR |
| | SIZE APPROVAL. ARTICLE III SECTION 90-124(7)(F). |
| | ****RESPONSE NOTED, NOT ADDRESSED. |
| | |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | |
| | 10. SHT P-2 A SEPARATE GAS PERMIT IS REQUIRED. THE |
| | FOLLOWING INFORMATION IS REQUIRED FOR PERMIT: |
| | |
| | A. OK |
| | B. OK |
| | |
| | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | D. OK |
| | 11. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |