| 2008-03-18 12:01:25 | ** DENIED 2ND REVIEW** |
| | |
| | ** PLEASE SEE SOME COMMENTS ARE THE SAME FROM PREVIOUS |
| | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE |
| | ALSO SEE SOME NEW COMMENTS DUE TO NEW INFORMATION NOW |
| | ON PLANS. |
| | |
| | ** PLEASE NOTE: AS THERE IS INFORMATION STILL NOT YET |
| | SUBMITTED FOR REVIEW, A FULL REVIEW CAN NOT BE DONE AND |
| | THERE MAY VERY WELL BE NEW COMMENTS ON THE NEXT |
| | REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE NO ENERGY CALCULATIONS WERE |
| | SUBMITTED, NO LIGHTING PERFORMANCE CALCULATIONS ETC. |
| | PLEASE SEE 13-400.3.B, 13-400.3.C, 13-415.2, |
| | 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE 13-412 FOR WATER HEATING SYSTEMS. |
| | PLEASE SEE MECHANICAL REVIEW COMMENTS FOR THESE |
| | SECTIONS. |
| | |
| | 2) NOTE: PLEASE KNOW ALTHOUGH NOT REQUIRED A RESPONSE |
| | LETTER FROM DESIGN PROFESSIONAL IS HELPFUL IN THE |
| | REVIEW PROCESS. THERE ARE RESPONSES FOR ALL OTHER |
| | TRADES BUT ELECTRICAL. |
| | THIS IS ONLY NOTED AS IT MAY HELP THE REVIEW OF SAID |
| | PLANS. |
| | |
| | 3) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM IS |
| | BEING SHOWN CONNECTED AFTER THE FIRST MEANS OF |
| | DISCONNECT ON THE TENANT MAINS?? |
| | PLEASE SEE 250.6, 250.524 AS THIS IS NOT PERMITTED. |
| | PLEASE SEE THE GE SYSTEM IS ALSO STILL SHOWN TO FOOTER |
| | STEEL, IS THIS AN EXISTING SERVICE OR NEW? IS THERE AND |
| | EXISTING GROUNDING ELECTRODE CONNECTED TO FOOTER? |
| | 250.50 |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 4) NOTE: PLEASE SEE 250.104 AS THE GAS PIPE SHOULD NOT |
| | BE PART OF THE GROUNDING ELECTRODE SYSTEM. IS THIS A |
| | BOND ONLY? |
| | |
| | 5) NOTE: PLEASE SEE THE SHOW WINDOWS WILL REQUIRE |
| | RECEPTACLES ABOVE WINDOW PER 210.62 |
| | PLEASE ADJUST LOAD CALCULATIONS PER 220.43 |
| | |
| | 6) NOTE: PLEASE BE SURE TO ADJUST LOAD CALCULATIONS FOR |
| | MIXED USE AS UPSTAIRS IS SHOWN AS APARTMENT. |
| | 220 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |