| 2007-12-20 08:25:30 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS |
| | PERMIT: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | |
| | 4. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304.--IF MECHANICAL COMBUSTION AIR |
| | SUPPLY SHOW COMPLIANCE WITH SECTION 304.9 AND ALL |
| | SUBSECTIONS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 5. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2.--ETL TESTING |
| | REPORS STATES, "THE PRODUCT COVERED BY THIS REPORT IS A |
| | PAINT SPRAY BOOTH THAT IS INTENDED TO BE USED WITH A |
| | LISTED NATURAL GAS HEATING/AIR HANDLING UNIT. PLEASE |
| | PROVIDE THE MANUF. SPECIFICATIONS SHOWING LISTING AND |
| | INSTALLATION INSTRUCTIONS FOR THE HEATING/AIR HANDLING |
| | UNIT. |
| | ****NO RESPONSE, NOTE ADDRESSED. |
| | |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | |
| | 10. SUBMIT MANUF. MSDS SHEETS FOR ALL MATERIALS |
| | ASSOCIATED WITH THE PAINT BOOTH AND RELATED CLEANUP. AN |
| | EYE WASH AND/OR EMERGENCY SHOWER MAY BE REQUIRED. |
| | SECTION 106.1.2. |
| | ****NO RESPONSE, NOT ADDRESSED |
| | |