Plan Review Notes
Plan Review Notes For Permit 07080598
Permit Number 07080598
Review Stop G
Sequence Number 2
Notes
Date Text
2007-12-20 08:25:30DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
  
 1. OK
 2. OK
 3. OK
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.--IF MECHANICAL COMBUSTION AIR
 SUPPLY SHOW COMPLIANCE WITH SECTION 304.9 AND ALL
 SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 5. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--ETL TESTING
 REPORS STATES, "THE PRODUCT COVERED BY THIS REPORT IS A
 PAINT SPRAY BOOTH THAT IS INTENDED TO BE USED WITH A
 LISTED NATURAL GAS HEATING/AIR HANDLING UNIT. PLEASE
 PROVIDE THE MANUF. SPECIFICATIONS SHOWING LISTING AND
 INSTALLATION INSTRUCTIONS FOR THE HEATING/AIR HANDLING
 UNIT.
 ****NO RESPONSE, NOTE ADDRESSED.
  
 7. OK
 8. OK
 9. OK
  
 10. SUBMIT MANUF. MSDS SHEETS FOR ALL MATERIALS
 ASSOCIATED WITH THE PAINT BOOTH AND RELATED CLEANUP. AN
 EYE WASH AND/OR EMERGENCY SHOWER MAY BE REQUIRED.
 SECTION 106.1.2.
 ****NO RESPONSE, NOT ADDRESSED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]