Plan Review Notes
Plan Review Notes For Permit 07080598
Permit Number 07080598
Review Stop M
Sequence Number 1
Notes
Date Text
2007-09-26 17:30:181- PLEASE PROVIDE EXHAUST AND INTAKE DUCT SIZE ON THE
 MECHANICALPLANS .
 2- PLEASE PROVIDE A FAN SCHEDULE FOR EXHAUST AND SUPPLY
 FANS ON MECHANICAL PLANS .
 3- PLEASE PROVIDE A DETAIL FORCURB TIE DOWN TO ROOF
 ON MECHANICAL PLANS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732