2007-10-12 16:56:51DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - SHOW LENGTH FROM METER TO FIRST TEE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - 150 FT SHOWN, BUT IT
 ADDS UP TO 155 FT NOT COUNTING THE LENGTH FROM THE
 METER TO THE FIRST TEE.--ALSO INDICATE THE LENGTH
 FROM THE METER TO THE MOST REMOTE OUTLET ON THE
 EXISTING LINE AS ALL GAS PIPING SHALL BE SIZED FROM THE
 LONGEST LENGTH.
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.--IF MECHANICAL COMBUSTION AIR
 SUPPLY SHOW COMPLIANCE WITH SECTION 304.9 AND ALL
 SUBSECTIONS.
  
 5. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--ETL TESTING
 REPORS STATES, "THE PRODUCT COVERED BY THIS REPORT IS A
 PAINT SPRAY BOOTH THAT IS INTENDED TO BE USED WITH A
 LISTED NATURAL GAS HEATING/AIR HANDLING UNIT. PLEASE
 PROVIDE THE MANUF. SPECIFICATIONS SHOWING LISTING AND
 INSTALLATION INSTRUCTIONS FOR THE HEATING/AIR HANDLING
 UNIT.
  
 7. A SHUT OFF VALVE IS REQUIRED UPSTREAM OF THE
 REGULATOR. SECTION 409.4. PLEASE SHOW ON RISER
 DIAGRAM.
  
 8. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 REGULATOR AND INDICATE/HIGHLIGHT THE MODEL NUMBER BEING
 USED. SECTION 106.2.1. MORE INFORMATION REQUIRED.
  
 9. THE PERSON DRAWING THE GAS RISER DIAGRAM SHALL PRINT
 THEIR NAME AND SIGN THE RISER DIAGRAM. SECTION
 106.3.4.3.
  
 10 SUBMIT MANUF. MSDS SHEETS FOR ALL MATERIALS
 ASSOCIATED WITH THE PAINT BOOTH AND RELATED CLEANUP. AN
 EYE WASH AND/OR EMERGENCY SHOWER MAY BE REQUIRED.
 SECTION 106.1.2.
  