| Date |
Text |
| 2007-09-13 15:45:28 | *****DENIED***** |
| | PLEASE BE ADVISED THAT EDUCATIONAL OCCUPANCIES SHALL |
| | INCLUDE ALL BUILDINGS USED FOR EDUCATIONAL PURPOSES |
| | THROUGH THE TWELFTH GRADE BY SIX OR MORE PERSONS FOR 4 |
| | OR MORE HOURS PER DAY OR MORE THAN 12 HOUS PER WEEK. |
| | NFPA 101 -2003 EDITION - CHAPTER 14 (NEW EDUCATIONAL |
| | OCCUPANCIES) SHALL BE REFERENCED. |
| | |
| | 01. SPECIFY THE CONTENTS OF THE NEW OCCUPANCY AS BEING |
| | CLASSIFIED AS LOW, ORDINARY, OR HIGH HAZARD. |
| | |
| | 02.PROVIDE AN APPROVED AISLE OR SEATING/CLASSROOM |
| | DIAGRAM TO SUBSTANTIATE THE OCCUPANCY MODIFICATION. |
| | |
| | 03.NO HANDRAILS/GUARDRAILS SHOWN IN NORTH STAIRWAY. |
| | |
| | 04.EXIT ACCESS CORRIDORS SHALL HAVE NOT LESS THAN 72" |
| | OF OF CLEAR WIDTH. |
| | |
| | 05.AISLES SHALL NOT BE LESS THAN 30" WIDE. |
| | |
| | 06.IT IS INDICATED THAT THE STORAGE ROOM IS NOT PART |
| | OF THE TENANT SPACE.IF THIS IS SO, PLEASE EXPLAIN HOW |
| | CAN CONTENTS POSSIBLY STORED BY OTHER TENANT(S) BE |
| | ASSURED AS TO NOT NEGATIVELY IMPACT LIFE SAFETY IN YOUR |
| | TENENT SPACE. |
| | |
| | 07.PROVIDE A LAYOUT OF THE FIRE SPRINKLERS FOR THIS |
| | PROJECT SITE.IF THE ERECTION/INSTALLATION OF DIVIDING |
| | WALLS HAS CAUSE FOR THE FIRE SPRINKLERS TO BE |
| | RELOCATED, A SEPARATE PLAN AND PERMIT WILL BE |
| | REQUIRED. |
| | |
| | 08.IT IS SHOWN OF ONE EXISTING FIRE ALARM HORN AND |
| | STROBE IN THE OPEN AREA;HOWEVER, IN THE EVENT OF THE |
| | ERECTION/INSTALLATION OF DIVIDING WALLS TO CREATE |
| | CLASSROOMS, ADDITIONAL FIRE ALARMS SHALL BE REQUIRED. |
| | SEPARATE PLAN AND PERMIT ARE NEEDED. |
| | |
| | 09.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE |
| | WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR |
| | CLASS C.SPECIFY INTERIOR FLOOR FINISH IN TERMS OF |
| | CLASS I OR CLASS II. |
| | |
| | 10.INDICATE WHAT THE UNIDENTIFIED ROOMS AND/OR SPACES |
| | ARE. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | 4. |