 ** DENIED **
  
  
  
 1) NOTE:PLEASE KNOW THAT THE CHANGE IN OCCUPANCY
 BASED ON PLANS SUBMITTED AND WORK FROM A BUSINESS TO
 EDUCATION WILL REQUIRE WORK WHICH IS REQUIRED TO BE
 DONE BY CONTRACTORS LICENSED UNDER FLORIDA STATUTES
 489.
  
 2) NOTE: PLEASE KNOW ONCE THE VALUE FOR THE COMPLETE
 SCOPE OF CONSTRUCTION, DESIGN, MATERIALS AND EQUIPMENT
 HAS BEEN DETERMINED, THE APPLIED VALUE IS REQUIRED TO
 MEET FBC 108.3.
  
 3) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS
 SPECIFICALLY THE EXISTING BUILDING CODE CHAPTER 8 FOR
 CHANGES IN OCCUPANCY. THE OCCUPANCY CLASSIFICATION OR
 GROUP IN CHANGING TO A HIGHER HAZARD AND WILL REQUIRE
 SOME SYSTEMS TO BE BROUGHT UP TO CODE IF THEY DO NOT
 MEET THE MINIMUM CODES AT THIS TIME.
 PLEASE SEE SECTION 808.2, 808.3, 808.4 AND 812,
 812.4.1. AS ELECTRICAL OUTLETS WHICH INCLUDE, LIGHTING
 FIXTURES, RECEPTACLES, ELECTRICAL PANELS ETC WHICH DO
 NOT MEET THE CURRENT NATIONAL ELECTRICAL CODE AND FCB
 CHAPTER 27 WILL BE REQUIRED TO BE BROUGHT UP TO CODE OR
 SHOWN AS EXISTING WHICH MEETS THE CURRENT MINIMUM
 CODES.
  
 ** PLEASE SEE NOTES FROM FIRE MARSHAL AND BUILDING
 REVIEWER WHICH WILL REQUIRE SOME OTHER SYSTEMS TO MEET
 THE CURRENT CODES FOR LIFE SAFETY ETC.
  
 4) NOTE: PLEASE SEE NFPA-101 CHAPTER 14 FOR NEW
 EDUCATION OCCUPANCIES.
 PLEASE SEE CHAPTER 7 FOR MINIMUM LIGHTING FOR EGRESS TO
 MEET CURRENT CODES.
 THE AMOUNT OF EMERGENCY LIGHTING FIXTURES SHOWN IN
 STAIR AREA ON THE NORTH SIDE OF SPACE DOES NOT MEET THE
 MINIMUM LEVELS.
 PLEASE SUBMIT PHOTO-METRICS FOR NORMAL AND EMERGENCY
 LEVELS INCLUDING STAIRS UNDER BOTH CONDITIONS. PLEASE
 SEE 7.8.1.3 AND 7.9.2.2.
 FAC 61G15-33.004
 ** PLEASE SEE 700.12F FOR CIRCUITING OF THESE
 FIXTURES.
  
 5) NOTE: PLEASE SEE SECTION 812 AS NOTED ABOVE IN NOTE
 #3 FOR THE FIRE ALARM SYSTEM/DEVICES WHICH IS REQUIRED
 TO MEET CURRENT CODES IF NOT ALREADY MEETING
 NFPA-72/NFPA-70 AND FBC CHAPTER 11.
 PLEASE INDICATE THE MINIMUM LEVELS FOR ALL ADA DEVICES
 PER FBC 11-4.28.1, .2 AND .3(4).
  
 6) NOTE: PLEASE COMPLETE PLANS INDICATING ALL LIGHTING.
 PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, AND .1.3.
 PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE DENSITIES
 REQUIRED.
 FBC, EBC, SECTION 811.
  
 7) NOTE: PLEASE SUBMIT INFORMATION ON THE EXISTING
 ELECTRICAL SERVICE, PANELS AND EQUIPMENT FOR THE
 ELECTRICAL LOADS PROPOSED. EVEN AS LOADS MAY NOT BE
 INCREASING THE VERIFICATION OF THE EXISTING SERVICE
 EQUIPMENT NEEDS TO BE VERIFIED.
 FBC EBC, 808.3 AND FBC CHAPTER 27.
  
 8) NOTE: PLEASE SEE THE SITE PLAN ON THE SHEET AND AREA
 AS SPECIFIED INVOKES PLACES OF ASSEMBLY PER NEC 518.1.
  
 PLEASE SEE LS 101
  
 9) NOTE: PLEASE SEE NOTES FROM BUILDING AND FIRE
 MARSHAL WITH RESPECT TO THE STORAGE ADJACENT TO THIS
 OCCUPANCY. WHAT IS STORED IN THIS ROOM?
  
 10) NOTE: PLEASE KNOW THE APPLICATION IS ALSO BEING
 ROUTED TO OUR ADDRESSING REVIEWER SO THAT A CORRECT
 SUITE/UNIT NUMBER MAY BE AASIGNED.
 PLEASE BE SURE TO INCLUDE THIS ON THE APPLICATION AND
 TITLE BLOCKS ON PLANS ONCE THIS HAS BEEN DETERMINED.
 FBC 106.1.2, 106.1, 110.1.2 ETC
 FAC 61G1-16.004,
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  