| 2007-11-30 07:18:31 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. SHT P-2POTABLE RISER. WATER HAMMER ARRESTORS ARE |
| | REQUIRED ON BOTH THE HOT & COLD WATER SUPPLY TO THE |
| | WASH MACHINES. SECTION 604.9. ONLY ONE IS SHOWN AT EACH |
| | W/M. |
| | ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTOR IS |
| | ONLY SHOWN ON THE HOT SUPPLY ONLY. PLEASE SHOW THE |
| | WATER HAMMER ARRESTORS ON BOTH THE HOT AND COLD WATER |
| | SUPPLIES TO THE WASH MACHINE. |
| | |
| | 3. SHT P-2 SANITARY RISER. ONLY THE FIXTURES WITHIN THE |
| | BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED |
| | HORIZONTAL BRANCH DRAIN. THE KITCHEN SINK SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. SECTION 909.1. |
| | PLEASE SHOW THE KITCHEN SINK CONNECTION DOWNSTREAM OF |
| | THE BATHROOM FIXTURES. |
| | ****RESPONSE NOTED, BUT THE TUB IS NOT VENTED AS SHOWN. |
| | THE VENT DOWNSTREAM OF THE OF THE TUB DOES NOT VENT THE |
| | TUB. IF THE TUB IS CONNECTED TO THE BRANCH LINE |
| | UPSTREAM OF THE KITCHEN SINK THE PLANS WILL MEET THE |
| | CODE REQUIREMENT OR A SEPARATE VENT AT THE TUB WILL BE |
| | REQUIRED. |
| | |
| | 4. OK |
| | 5. OK |
| | |
| | 6. THE SEAL FOR THE PROFESSIONAL ENGINEER SHALL INCLUDE |
| | THE WORD "LICENSE" IN THE SEAL. PLANS SEALED BY JOHN |
| | SYLVIA DO NOT INDICATE "LICENSE" ON THE SEAL. FAC |
| | 61G15-23.001 & FS 471.025. PLEASE RESEAL THE SHEETS AND |
| | MAKE SURE ALL INFORMATION REQUIRED ON THE SEAL IS |
| | IMPRESSED ON EACH SHEET. |
| | ****RESPONSE NOTED, BUT SHEETS P-1 & P-3 HAVE NOT BEEN |
| | RESEALED AND DO NOT HAVE THE WORD "LICENSE" IMPRESSED |
| | ON THE SHEETS AS REQUIRED. |
| | |
| | REVIEW BY KEN STEVENS |