| 2007-10-12 11:02:22 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHTS D-1 & D-2 PLEASE INDICATE THE LOCATION OF THE |
| | EXISTING WATER HEATERS FOR EACH UNIT. SECTION 106.1.2. |
| | |
| | 2. SHT P-2POTABLE RISER. WATER HAMMER ARRESTORS ARE |
| | REQUIRED ON BOTH THE HOT & COLD WATER SUPPLY TO THE |
| | WASH MACHINES. SECTION 604.9. ONLY ONE IS SHOWN AT EACH |
| | W/M. |
| | |
| | 3. SHT P-2 SANITARY RISER. ONLY THE FIXTURES WITHIN THE |
| | BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED |
| | HORIZONTAL BRANCH DRAIN. THE KITCHEN SINK SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. SECTION 909.1. |
| | PLEASE SHOW THE KITCHEN SINK CONNECTION DOWNSTREAM OF |
| | THE BATHROOM FIXTURES. |
| | |
| | 4. SHT P-2 SANITARY RISER. A STANDPIPE IS REQUIRED FOR |
| | EACH WASH MACHINE PER SECTIONS 802.4 & 1002.1. PLEASE |
| | INDICATE THE STANDPIPE ON RISER.--A CLEANOUT IS |
| | REQUIRED AT THE BASE OF THE W/M STACK A MINIMUM OF 4 FT |
| | ABOVE THE FLOOR FOR ACCESS. SECTION 708.9. PLEASE |
| | INDICATE CLEANOUTS ON RISER DIAGRAM. |
| | |
| | 5. SHT P-2 SANITARY RISER. THE AIR ADMITTANCE VALVES |
| | SHALL BE LOCATED A MINIMUM OF 4 IN. ABOVE THE FIXTURE |
| | DRAIN BEING VENTED. ON THE WASH MACHINES THEY SHALL BE |
| | LOCATED 4" ABOVE THE AIR GAP OF THE FITTING OR 4" ABOVE |
| | THE STANDPIPE. SECTION 917.4. PLEASE SHOW THE AAV'S |
| | ABOVE THE TOP OF THE STANDPIPE MIN. 4". |
| | |
| | 6. THE SEAL FOR THE PROFESSIONAL ENGINEER SHALL INCLUDE |
| | THE WORD "LICENSE" IN THE SEAL. PLANS SEALED BY JOHN |
| | SYLVIA DO NOT INDICATE "LICENSE" ON THE SEAL. FAC |
| | 61G15-23.001 & FS 471.025. PLEASE RESEAL THE SHEETS AND |
| | MAKE SURE ALL INFORMATION REQUIRED ON THE SEAL IS |
| | IMPRESSED ON EACH SHEET. |
| | |