| Plan Review Notes For Permit 07080572 |
| Permit Number |
07080572 |
|
| Review Stop |
B |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2009-04-15 10:41:03 | REVISION DENIED BY BUILDING | | | | | | | | | 1) THE REVISION TO CHANGE FRONT DOOR IS OK. FL. PRODUCT | | | APPROVALS WERE SUBMITTED. PLACE COPY OF STAMPED PRODUCT | | | APPROVAL WITH THE PLANS. | | | | | | 2) THE REVISION TO CHANGE SIDE DOOR IS DENIED. THIS | | | DOOR DOES NOT HAVE STATE PRODUCT APPROVAL. LOCAL/SITE | | | SPECIFIC ENGINEERING IS REQUIRED IN ACCORDANCE WITH DCA | | | RULE 9B-72. ORIGINAL SIGNED AND SEALED DOCUMENTS FROM | | | THE ENGINEER ARE REQUIRED. NOTE: THE DESIGN PRESSURES | | | IN THE SUBMITTAL OF +36.0 PSF, -39.3 PSF ARE TOO LOW. | | | THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C THE | | | OPENING PRESSURE OF +47.5 PSF, -51.8 PSF ARE SPECIFIED | | | ON SHEET S3.02 OF THE PLANS FOR A 20 SQFT OPENING. THE | | | STREET NAME ON THE LETTER IS INCORRECT, IT IS DAKOTA | | | CIRCLE. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|