Plan Review Notes
Plan Review Notes For Permit 07080572
Permit Number 07080572
Review Stop M
Sequence Number 4
Notes
Date Text
2008-01-11 14:04:27PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ONLY ONE SET OF THE MECHANICAL PLANS PAGE M-1 AND
 M-2 WERE SUBMITTED FOR REVIEW, TWO SETS MUST BE
 SUBMITTED, SEE 2004 FBC/WPB AMEND. 106.1.
  
 2) COOLING LOAD CALCULATIONS ARE CALLING FOR 121,173
 TOTAL COOLING BTU'S, MECHANICAL PLANS ARE SHOWING
 156,400 TOTAL COOLING BTU'S, THE PLANS CAN ONLY CALL
 FOR 15% MORE THAN THE COOLING LOAD CALCULATIONS, SEE
 2004 FBC 13-607.1.ABC.1.1. 13 TONS OF AIR CONDITIONING
 APPEARS TO BE TO MUCH, PLEASE CORRECT.
  
 3) A/C SYSTEM 1 AND 2 ARI CERTIFICATION HAS BEEN
 DISCONTINUED (SEE ATTACHED COPY), SEE 2004 FBC
 13-607.1.ABC.3.1.1, PLEASE CORRECT.
  
 4) THE FIRST FLOOR CLOTHES DRYER VENT MAY NOT DISCHARGE
 ON OR TERMINATE NEAR THE A/C CONDENSER UNIT, SEE 2004
 FBC/R M303.4.2, PLEASE CORRECT.
  
 5) PLEASE ADD JOB ADDRESS TO ANY NEW MECHANICAL PLANS,
 SEE 2004 FBC/WPB AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected] .