Plan Review Notes
Plan Review Notes For Permit 07080572
Permit Number 07080572
Review Stop E
Sequence Number 4
Notes
Date Text
2009-07-20 14:40:50 
  
 ** DENIED REVISION **
  
 ** THE TITLE BLOCKS INDICATE THERE HAVE BEEN THREE
 REVISIONS SINCE THE LAST REVIEW DONE IN THIS OFFICE
 SINCE 12/03/07 HOWEVER TO DATE NO ELECTRICAL REVISIONS
 HAVE BEEN SUBMITTED FOR BASE BUILDING PLANS.
 THE SERVICE HAS COMPLETELY BEEN REVISED ALONG WITH MANY
 OTHER ITEMS.
  
  
 1) NOTE: PLANS SUBMITTED ARE NOT REVISED BY THE
 ENGINEER OF RECORD PER FS 471.025
 FAC 61G15-23
  
 2) NOTE: PLEASE UPDATE LOAD CALCULATIONS FOR RECESSED
 LIGHTING LOADS PER 220.3B4. THE AMOUNT OF RECESSED
 LIGHTING SHOWN ON PLANS IS ABOVE THE GENERAL LIGHTING
 LOADS. PLEASE ALSO BE SURE THE ADDITIONAL LOADS ON THE
 LIGHTING PANEL IS COORDINATED.
  
 3) NOTE: PLEASE LOOK AT THE NEW 600AMP DISTRIBUTION
 PANEL. ALL PANELS ARE SHOWING FEEDER CONDUCTORS AND
 LOADS WELL BELOW ANY MINIMUMS BY CODE. 240.4,310.16 ETC
 FOR EXAMPLE: PANEL *A* IS SHOWING A 225AMP BREAKER WITH
 #10 CONDUCTORS AS THE FEEDERS WITH A LOAD OF 4.5 KW.
 THIS IS NOT POSSIBLE. ALL OTHER PANELS ON THIS SAME
 600AMP MDP IS THE SAME. CONDUCTORS ARE TOO SMALL AND
 LOADS ARE NOT ACCURATE.
  
 4) NOTE: PANELS FOR ALL LOADS NEED TO BE SUBMITTED AND
 COMPLETE. NO PANEL SCHEDULE FOR EXAMPLE WAS SUBMITTED
 FOR THE NEW POOL PANEL SO LOADS, BRANCH CIRCUITS ETC
 CAN NOT BE VERIFIED AS CODE COMPLIANT.
 408.4,220,310, ETC
  
 5) NOTE: THE RISER HAS BEEN COMPLETELY REVISED FOR A
 NEW 600AMP SERVICE HOWEVER THE PLANS ON SHEETS E- STILL
 INDICATES THE ORIGINAL 400AMP SERVICE, 400AMP MAIN AND
 400AMP TRANSFER SWITCH.
 PLEASE COORDINATE PLANS.
 215.5,230.70,230.71,ETC
  
 6) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW TRANSFER SWITCH WHICH APPEARS TO BE
 UPDATED FROM THE PREVIOUS PLANS.
 110.3, 90.7
  
 7) NOTE: PLEASE SEE SAFE ROOM WHICH WAS/IS THE MASTER
 BEDROOM CLOSET. THE PLANS INDICATE WHAT APPEAR TO BE
 WALL SCONCES. PLEASE SEE 410.8 FOR MINIMUM CLEARANCES
 FROM SHELVING.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  