Plan Review Notes
Plan Review Notes For Permit 07080572
Permit Number 07080572
Review Stop B
Sequence Number 3
Notes
Date Text
2007-12-20 13:10:302004 FBC W/2007 SUPPLEMENTS
 NSFR
  
 DENIED BY BUILDING
  
 1) COMPLIED
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. WORK MUST COMMENCE WITHIN 90 DAYS
 OF THE DATE THE NOC IS RECORDED. FS 713.13.
  
 3) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4) COMPLIED
  
 5)FBC R401.4AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL. SUBMIT 2 SIGNED AND SEALED COPIES.
  
 6) COMPLIED
  
 7) THE FLOOD ZONE DESIGNATION ON THE SURVEY IS
 SPECIFIED AS A8, WHICH IS INCORRECT. THIS AREA IS
 INCLUDED IN THE LETTER OF MAP REVISION (LOMR) FOR THE
 VILLAGES OF PALM BEACH LAKES AND SPENCER LAKES PLATS
 1,2 AND 3 DATED DECEMBER 3, 1983. PLEASE CORRECT.
 SUBMIT REVISED SURVEY.
  
 8) THE ENERGY CALCULATIONS LIST THE CONDITIONED FLOOR
 AREA AS 8000 SQFT AND THE PLANS SPECIFY 8327 SQFT.
 PLEASE CORRECT. FBC R CHAPTER 11 AND FBC CHAPTER 13.
 THE NEW FORMS HAVE NOT BEEN SIGNED BY THE OWNER/AGENT
 AS REQUIRED BY FBC 13-600.
  
 9)NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED
 EFFECTIVE DECEMBER 8, 2006 (2006 AMENDMENTS TO THE
 FBC), FBC1609.4, FBC R301.2.1.4.
 EXPOSURE C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS, INCLUDING SURFACE UNDULATIONS OR OTHER
 IRREGULARITIES, HAVING HEIGHTS GENERALLY LESS THAN 30
 FEET (9144 MM) EXTENDING MORE THAN 1,500 FEET (457.2 M)
 FROM THE BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE
 SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN
 EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS DIRECTLY
 ADJACENT TO OPEN AREAS OF EXPOSURE C-TYPE TERRAIN IN
 ANY QUADRANT FOR A DISTANCE OF MORE THAN 600 FEET
 (182.9 M). THE STRUCTURE IS LOCATED ADJACENT TO A GOLF
 COURSE WHICH MAY REQUIRE IT TO BE DESIGNED AS EXPOSURE
 C. PLEASE REVISE PLANS OR INDICATE WHY THE EXPOSURE
 CATEGORY SHOULD NOT BE CHANGED. NOTE: ALTHOUGH THE
 GENERAL NOTES (C) (3) ON A.09 HAVE BEEN REVISED TO
 EXPOSURE CATEGORY 'C', THE COMPONENT AND CLADDING
 PRESSURES IN THE TABLE ON S3.02 HAVE NOT BEEN REVISED
 TO CATEGORY 'C'. PLEASE CORRECT.
  
 10) THE WALLS OF THE WINE ROOM ARE REQUIRED TO BE
 WATERPROOFED IN ACCORDANCE WITH FBC R406. INDICATE HOW
 THIS WILL BE ACCOMPLISHED ON THE PLANS. THE SPRAY FOAM
 INSULATION DOES NOT COMPLY WITH THE REQUIREMENTS OF FBC
 R406.
  
 11) COMPLIED
  
 12) COMPLIED
  
 13) COMPLIED
  
 14) COMPLIED
  
 15) COMPLIED
  
 16) COMPLIED
  
 17)COMPLIED
  
 18) COMPLIED
  
 19) COMPLIED
  
 20) COMPLIED
  
 21) COMPLIED
  
 22)COMPLIED
  
 23) COMPLIED
  
 24) COMPLIED
  
 25) REVISE COMPONENT AND CLADDING PRESSURES TO EXPOSURE
 CATEGORY 'C'. SEE ITEM #9.
  
 26) COMPLIED
  
 27) COMPLIED
  
 28) COMPLIED
  
 29) THE SIMPSON H10 OR USP RT16 "R" IN SCHEDULE ON
 S2.02) WILL NOT WORK FOR ATTACHING THE FLOOR TRUSSES TO
 THE LEDGERS. THE FLOOR TRUSSES ARE 3-1/2" WIDE AND THE
 CONNECTORS HAVE A 1-9/16" OPENING FOR THE TRUSS. PLEASE
 CORRECT.
  
 30) N/A
  
 31) COMPLIED
  
 32) COMPLIED
  
 33) COMPLIED
  
 34) CORRECTED
  
 35) THE TRUSS LAYOUT IS REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 STRUCTURE. SEE R802.1.6, FBC106.1.1.2* CITY AMENDMENTS
 AND FAC 61G15-31.003.
  
 36) THE ROOF TRUSSES ARE REQUIRED TO HAVE A MINIMUM
 BOTTOM CORD LIVE LOAD OF 10 PSF. SEE TABLE R301.5.
 PLEASE CORRECT.
  
 37) THE TRUSS DRAWING SUBMITTAL DOES NOT MEET THE
 REQUIREMENTS OF FAC 61G-15-31.003. PLEASE SEPARATE THE
 DRAWINGS AND PLACE THEM WITH THE APPROPRIATE COVER
 SHEETS AND NUMBER THE DRAWINGS TO CORRESPOND TO THE
 NUMBERING ON THE COVERSHEETS. SEE ATTACHMENT.
  
 38) COMPLIED
  
 39)CORRECTED
  
 40) FBC 106.3* CITY AMENDMENTS PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 41) COMPLIED
  
 42)THE GENERIC PRESSURES IN THE SCHEDULE ON S3.02 MAY
 BE TOO HIGH FOR THE GARAGE DOORS WHEN THEY ARE
 INCREASED TO EXPOSURE 'C'. SEE TABLE R301.2(4). PLEASE
 INDICATE THE REQUIRED OPENING PRESSURES FOR THE GARAGE
 DOORS ON THE PLANS.
  
 43)COMPLIED
  
 44) COMPLIED. HOWEVER, PLEASE CLARIFY WHICH WINDOWS THE
 PRODUCT APPROVALS FOR THE WEATHER SHIELD "LEGACY" FIXED
 CASEMENT WINDOWS ARE FOR. THERE DOES NOT TO BE ANY OF
 THESE SPECIFIED ON THE PLANS.
  
 45) CORRECTED
  
 46) COMPLIED
  
 47)COMPLIED
  
 48) COMPLIED
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW