2007-10-16 08:51:55DENIED;
 1.SEE MECHANICAL NOTE #1. ARCHITECT FIRM LICENSE IS
 REQUIRED ON THE TITLE BLOCK.
 2. SANITARY RISER DIAGRAM, CLEANOUT'S REQUIRED ON
 AUTOMATIC CLOTHES WASHER VENT AT 48" ABOVE FINISH
 FLOOR.
 3. DISHWASHERS TO DISCHARGE INDIRECTLY INTO BUILDING
 DRAIN. SECTION 802.1.6.
 4. 1/2 BATH FIRST FLOOR TOILET NOT VENTED AS DRAWN
 CANNOT DISCHARGE INTO THE 2ND FLOOR BRANCH DRAIN.
 5. WATER SANITARY RISER DIAGRAM WATER HAMMER ARRESTORS
 ARE REQUIRED ON ALL QUICK CLOSING VALVES PER 604.9 SHOW
 ON PLANS.
 6. 2 WATER HEATERS SHOWN ON FLOOR PLANS 80 GAL ON 1ST
 FLOOR60 GAL ON 2ND FLOOR, ONLY ONE MODEL # SHOWN ON
 PAGE DMP-1.
 7. SHOW LOCATION OF IN-LINE PUMP FOR MATER SHOWER. THIS
 PUMP MUST BE ACCESSABLE WITH A SHUTOFF VALVE UP STREAM.
  