2007-10-10 12:29:56PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
  
 1) AS NOTED IN LAST REVIEW 9/6/07. MECHANICAL PLANS,
 INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT
 (ARCHITECT FIRM LICENSE NUMBER AA0002936).
 PER FAC 61G1-16.004 TITLE BLOCK.
  
 2) AS NOTED IN LAST REVIEW 9/6/07 NOTE #3. PLEASE
 SUBMIT COOLING LOAD CALCULATIONS, SEE FBC
 13-407.1.ABC.1.
  
 3) AS NOTED IN LAST REVIEW 9/6/07 NOTE #4. ENERGY
 CALCULATIONS LINE 13A, AND B SHOW THE A/C SYSTEMS AS
 HEAT PUMP SYSTEMS. THE ARI DIRECTORY SHOWS THE UNITS
 ARE STRAIGHT COOL SYSTEMS, PLEASE CORRECT ENERGY CAL'S.
 OR MODEL NUMBERS ON MECHANICAL PLANS.
  
 4) AS NOTED IN LAST REVIEW 9/6/07 NOTE #6. PLEASE
 SUBMIT DETAILED MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR THE GAS BBQ GRILL AND
 HOOD, GAS FIRE PLACES, AND GAS LOG LIGHTERS IF USED.
  
 5) AS NOTED IN LAST REVIEW NOTE #7. PLEASE SUBMIT
 PRODUCT APPROVAL FOR O/A LOUVER FOR SAFE ROOM, SEE FS
 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND FAC
 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 6) WASHER/DRYER DETAIL ON PAGE DMP-1 STATES PER I.M.C.
 2003304.6.1. ALL WORK PERMITTED IN THE CITY OF W.P.B.
 MUST COMPLY WITH THE "2004 F.B.C.", PLEASE CORRECT.
  
 7) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]