Plan Review Notes
Plan Review Notes For Permit 07080572
Permit Number 07080572
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-06 16:56:20 
 *** DENIED2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED.
 ** PLEASE SEE NEW NOTE DUE TO CHANGE IN NOTE ON PLANS.
  
 1) NOTE: PLEASE KNOW ONCE ADDRESS HAS BEEN DETERMINED
 BY THE ADDRESSING REVIEWER THE NEW ADDRESS SHOULD BE
 PLACED ON THE TITLE BLOCKS.
 FBC ADMIN SECT 110.1.2, 106.1.2
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW.
 PLEASE SEE THE ARCHITECTURAL FIRM IS STILL MISSING THE
 REQUIRED LICENSE INFORMATION.
 ** THIS IS REQUIRED. IF PLANS COME BACK WITHOUT THE
 REQUIRED INFORMATION THIS OFFICE WILL HAVE NO CHOICE
 BUT TO TURN THIS OVER TO THE STATE.
 PLEASE ADDRESS.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING LICENSE INFORMATION ON THE TITLE
 BLOCKS FOR THE ARCHITECTURAL FIRM.
 PLEASE KNOW THAT THE MISSING CERTIFICATE OF
 AUTHORIZATION AS REQUIRED FOR THE FIRM WHICH IS
 REQUIRED TO BE ON THE TITLE BLOCK IS IN FACT DELINQUENT
 WITH THE STATE. PLEASE SEE THE ATTACHED PRINT OUT FROM
 THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
 WHICH INDICATES THIS AS OF THIS REVIEW.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND
 FLORIDA STATUTES 481.219
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND ALL
 SHEETS WHICH CONTAIN THIS TITLE BLOCK WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE(S).
  
 3) NOTE: PLEASE SEE THE PLANS ARE NOW CONTAINING A NOTE
 WHICH MENTIONS THE ATS AND GENERATOR WILL BE UNDER
 SEPARATE PERMITS, HOWEVER PLEASE SEE THE PLANS AND
 RISER STILL INDICATE THE ATS BEIGN INSTALLED AT THIS
 TIME.
 IF ONLY THE ATS WILL BE INSTALLED AT THIS TIME WITH THE
 ELECTRICAL FOR THE MAIN HOUSE SERVICE, THEN PLEASE
 SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THIS
 UNIT.
 SOME OTHER SHEETS STILL SHOW THE GENERATOR.
 FBC 106.1.1, 106.1.2,
 NEC 110.3, 90.7
  
 4) NOTE: PLEASE SEE THE ARC FAULT PROTECTION NOTE ON
 THE BOTTOM OF THE PANEL SCHEDULE MENTIONS THIS IS
 REQUIRED FOR *RECEPTACLE CIRCUITS* HOWEVER THIS IS
 REQUIRED FOR ALL AS LISTED ON PREVIOUS REVIEW NOTE FOR
 *ALL*OUTLETS IN THE SLEEPING ROOMS INCLUSIVE OF SMOKE
 ALARMS, FANS, LIGHTING ETC.
 PLEASE SEE 210.12
  
 5) NOTE: PLEASE SEE THE REVISED ITEMS WERE NOT CLOUDED
 OR INDICATED ON THE PLANS. THE NOTES ON THE LOWER RIGHT
 HAND CORNER DO NOT ACTUALLY RESPOND TO ALL PREVIOUS
 NOTES.
  
 6) NOTE: PLEASE SEE NOTE #16 FROM PREVIOUS REVIEW WHICH
 REQUESTED FOR COMPLETION OF THE PANEL SCHEDULE TO SHOW
 THE REQUIRED MINIMUM BRANCH CIRCUIT CONDUCTORS, HOWEVER
 THIS WAS NOT DONE.
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PANEL SCHEDULES WITH THE BRANCH
 CIRCUIT CONDUCTOR SIZES.
 408.4, 240.4, 310.16.
 FBC 106.1.2, 106.3.5.4
  
 7) NOTE:NO INFORMATION ON LIGHTING CONTROL
 PANEL(S)/SYSTEM AS NOTED ON PREVIOUS NOTE #17.
 PLEASE KNOW THAT ANY LIGHTING SYSTEMS OR CONTROLS WHICH
 ARE INSTALLED WHICH AFFECT THE BASE CODE DESIGNED BY
 THE DESIGNER OF RECORD WILL BE REQUIRED TO GO THROUGH
 THE RESPONSIBLE DESIGNER OF RECORD. THESE *FUTURE*
 PLANS WILL BE REQUIRED TO CONTAIN A *SHOP DRAWING*
 REVIEW STAMP IF PLANS ARE NOT DONE BY THE DESIGNER OF
 RECORD. PLEASE ALSO KNOW THAT ANY INSTALLATION OF THESE
 ITEMS WILL ALSO BE REQUIRED TO BE REVISED ON BASE HOUSE
 PLANS FOR REFERENCE OF SYSTEM.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT MORE INFORMATION ON THE PROPOSED LIGHTING
 CONTROL PANELS AND SYSTEM. PLEASE SEE 110.3, 90.7 AS
 VERIFICATION OF THE TYPE OF SYSTEM, LISTING FROM A
 NRTL, LOCATIONS AND TYPE OF WIRING BEING INSTALLED.
  
 8) NOTE: PLEASE PROVIDE A NOTE ON PLANS FOR THE TYPE OF
 RECESSED LIGHTING AS REQUIRED PER FBC
 13-606-1.ABC.1.2.4.
  
 PLEASE KNOW THAT A TYPED WRITTEN RESPONSE WILL HELP IN
 THE REVIEW PROCESS. THIS IS NOT REQUIRED AND ONLY A
 SUGGESTION.
 PLEASE ALSO SEE THE PREVIOUS REVIEW WHICH MENTIONED IF
 THERE ARE ANY QUESTIONS OR COMMENTS TO PLEASE CONTACT
 THIS REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved