Plan Review Notes
Plan Review Notes For Permit 07080572
Permit Number 07080572
Review Stop M
Sequence Number 1
Notes
Date Text
2007-09-06 09:33:01PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) MECHANICAL PLANS, INFORMATION MISSING FROM TITLE
 BLOCK (ENGINEERS PRINTED NAME AND LICENSE NUMBER WHO
 SEALED THE PLAN, AND THE ENGINEERING BUSINESS
 CERTIFICATE OF AUTHORIZATION NUMBER).
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) MECHANICAL PLANS, INFORMATION MISSING IN TITLE BLOCK
 FOR ARCHITECT (ARCHITECT FIRM LICENSE NUMBER, AND JOB
 ADDRESS).
 SEE FAC 61G1-16.004 TITLE BLOCK. A TITLE BLOCK MUST
 APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN DRAWINGS
 AND SPECIFICATION IDENTIFICATION SHEETS. THE TITLE
 BLOCK MUST, AT A MINIMUM, CONTAIN THE FOLLOWING
 INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 3) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE FBC
 13-407.1.ABC.1.
  
 4) ENERGY CALCULATIONS LINE 13A, AND B SHOW THE A/C
 SYSTEMS AS HEAT PUMP SYSTEMS. THE ARI DIRECTORY SHOWS
 THE UNITS ARE STRAIGHT COOL SYSTEMS, PLEASE CORRECT
 ENERGY CAL'S. OR MODEL NUMBERS ON MECHANICAL PLANS.
  
 4) PAGE DMP-1 DETAIL OF CONDENSATE DISCHARGE TO GRADE,
 DRAIN NEEDS TO DISCHARGE 12" FROM THE BUILDING, SEE
 RES. R320.7. PLEASE CORRECT.
  
 5) PAGES M-1 AND M-2 DUCT SCHEDULE ZONES 2, 3, AND 4 DO
 NOT SHOW ALL THE DUCT SIZES (SEE YELLOW HIGH LIGHT ON
 PLAN) PLEASE CORRECT.
  
 6) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 GAS BBQ GRILL AND HOOD, GAS FIRE PLACES, AND GAS LOG
 LIGHTERS IF USED.
  
 7) PLEASE SUBMIT PRODUCT APPROVAL FOR O/A LOUVER FOR
 SAFE ROOM, SEE FS 553.842(1) AND FAC RULE 9B-72,
 9B-72.005, AND FAC 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** INFORNATIONAL: PAGE A.01 SHOWS A GENERATOR NEAR A
 8X8" VENT BLOCK TO THE GARAGE NFPA 37 REQUIRES
 GENERATORS TO BE FIVE FEET FROM BUILDING OPENINGS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]