| 2007-09-06 09:33:01 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA |
| | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). |
| | |
| | *** DENIED *** |
| | 1) MECHANICAL PLANS, INFORMATION MISSING FROM TITLE |
| | BLOCK (ENGINEERS PRINTED NAME AND LICENSE NUMBER WHO |
| | SEALED THE PLAN, AND THE ENGINEERING BUSINESS |
| | CERTIFICATE OF AUTHORIZATION NUMBER). |
| | SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET |
| | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE |
| | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND |
| | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. |
| | |
| | 2) MECHANICAL PLANS, INFORMATION MISSING IN TITLE BLOCK |
| | FOR ARCHITECT (ARCHITECT FIRM LICENSE NUMBER, AND JOB |
| | ADDRESS). |
| | SEE FAC 61G1-16.004 TITLE BLOCK. A TITLE BLOCK MUST |
| | APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN DRAWINGS |
| | AND SPECIFICATION IDENTIFICATION SHEETS. THE TITLE |
| | BLOCK MUST, AT A MINIMUM, CONTAIN THE FOLLOWING |
| | INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" |
| | SEE CITY WPB AMEND. 106.1.1). |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | |
| | 3) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE FBC |
| | 13-407.1.ABC.1. |
| | |
| | 4) ENERGY CALCULATIONS LINE 13A, AND B SHOW THE A/C |
| | SYSTEMS AS HEAT PUMP SYSTEMS. THE ARI DIRECTORY SHOWS |
| | THE UNITS ARE STRAIGHT COOL SYSTEMS, PLEASE CORRECT |
| | ENERGY CAL'S. OR MODEL NUMBERS ON MECHANICAL PLANS. |
| | |
| | 4) PAGE DMP-1 DETAIL OF CONDENSATE DISCHARGE TO GRADE, |
| | DRAIN NEEDS TO DISCHARGE 12" FROM THE BUILDING, SEE |
| | RES. R320.7. PLEASE CORRECT. |
| | |
| | 5) PAGES M-1 AND M-2 DUCT SCHEDULE ZONES 2, 3, AND 4 DO |
| | NOT SHOW ALL THE DUCT SIZES (SEE YELLOW HIGH LIGHT ON |
| | PLAN) PLEASE CORRECT. |
| | |
| | 6) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE |
| | GAS BBQ GRILL AND HOOD, GAS FIRE PLACES, AND GAS LOG |
| | LIGHTERS IF USED. |
| | |
| | 7) PLEASE SUBMIT PRODUCT APPROVAL FOR O/A LOUVER FOR |
| | SAFE ROOM, SEE FS 553.842(1) AND FAC RULE 9B-72, |
| | 9B-72.005, AND FAC 9B-72.010(31)(G). |
| | |
| | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| | |
| | *** INFORNATIONAL: PAGE A.01 SHOWS A GENERATOR NEAR A |
| | 8X8" VENT BLOCK TO THE GARAGE NFPA 37 REQUIRES |
| | GENERATORS TO BE FIVE FEET FROM BUILDING OPENINGS. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |