| 2007-08-31 10:20:56 | 2007-08-31 10:20:56 |
| | |
| | ** DENIED** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS DO NOT |
| | CONTAIN AN ORIGINAL SIGNATURE AND DATE AS REQUIRED PER |
| | FLORIDA STATUTES 481.221. |
| | THE PLANS ARE REQUIRED TO BE SIGNED AS ORIGINAL. |
| | PLACING A RAISED SEAL OVER AN *IMAGED* SIGNATURE IS NOT |
| | ACCEPTABLE PER THE MINIMUM REQUIREMENTS OF THE FAC AND |
| | FS. |
| | **THIS IS REQUIRED FOR ALL SHEETS AND ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWS. |
| | |
| | 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION ON THE |
| | TITLE BLOCKS FOR THE ARCHITECTURAL FIRM. |
| | PLEASE KNOW THAT THE MISSING CERTIFICATE OF |
| | AUTHORIZATION AS REQUIRED FOR THE FIRM WHICH IS |
| | REQUIRED TO BE ON THE TITLE BLOCK IS IN FACT DELINQUENT |
| | WITH THE STATE. PLEASE SEE THE ATTACHED PRINT OUT FROM |
| | THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION |
| | WHICH INDICATES THIS AS OF THIS REVIEW. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND |
| | FLORIDA STATUTES 481.219 |
| | ** PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND ALL |
| | SHEETS WHICH CONTAINS THIS TITLE BLOCK WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER TRADE(S). |
| | |
| | 3) NOTE: PLEASE SEE THE TITLE BLOCK FOR THE ENGINEER |
| | AND FIRM AS SHOWN IS ALSO MISSING INFORMATION. PLEASE |
| | SEE THE MISSING PRINTED NAME, PRINTED LICENSE NUMBER |
| | AND MISSING CERTIFICATE OF AUTHORIZATION NUMBER. |
| | **PLEASE KNOW THIS IS REQUIRED FOR ALL MEP SHEETS |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE(S). |
| | |
| | 4) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | |
| | 5) NOTE: PLEASE SEE THE PLANS ARE SHOWING A NEW |
| | GENERATOR AND ATS BEING INCLUDED WITH THE SCOPE OF WORK |
| | FOR HOUSE HOWEVER PLEASE SUBMIT THE MANUFACTURES |
| | SPEC/CUT SHEETS FOR BOTH.IF THE GENERATOR WILL BE |
| | UNDER A SEPARATE PERMIT PLEASE ADJUST PLANS TO INDICATE |
| | THIS. |
| | PLEASE KNOW THE GENERATOR SPECS/CUT SHEETS ARE TO |
| | INDICATE THE MINIMUM CLEARANCES FOR UNIT. |
| | PLEASE SUBMIT AND SEE COMMENTS FROM OTHER TRADES FROM |
| | ZONING, BUILDING AND PLUMBING. |
| | FBC 106.1.1, 106.1.2, |
| | NEC 110.3, 90.7 |
| | |
| | 6) NOTE: PLEASE SEE THERE ARE SEVERAL SPECIFIC |
| | DEDICATED APPLIANCE LOADS AND MOTORS LOADS ON THE |
| | ELECTRICAL PANEL SCHEDULES WHERE THE LOADS ARE NOT |
| | INCLUDED IN THE LOAD CALCULATIONS. |
| | PLEASE GO OVER CALCULATIONS AND ADJUST AS NEEDED. |
| | PLEASE SEE FOR EXAMPLE MISSING, WATER PUMP, |
| | REFRIGERATOR, WASHER, CENTRAL VACUUM, GARAGE DOOR |
| | OPENER ETC. |
| | PLEASE SEE NEC 220 AND SEE SOME COMMENTS BELOW FOR SOME |
| | OTHER LOADS. |
| | |
| | 7) NOTE:PLEASE SEE 210. 52C2 AND 220.53 FOR MINIMUM |
| | LOADS FOR THE WASHER/LAUNDRY LOADS AS REQUIRED. PLEASE |
| | SEE THE PANEL SCHEDULE DOES NOT INDICATE THE MINIMUM OF |
| | 1500VA FOR EACH OF THESE AS SHOWN AND LISTED. PLEASE |
| | ALSO SEE THE LOADS SHOWN ON THE LOAD CALCULATIONS ON |
| | THE SERVICE INDICATE (2) LAUNDRY LOADS HOWEVER THE TWO |
| | ARE SHOWN WITH A TOTAL OF 4500VA? |
| | IT IS UNCLEAR HOW THESE LOADS ARE BEING DETERMINED AS |
| | THE PANEL SCHEDULE AND OTHER LOADS ARE NOT THE SAME. |
| | PLEASE SEE THE SECTIONS AS NOTED FOR THE MINIMUM |
| | LOADS. |
| | PLEASE ADJUST. |
| | |
| | 8) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTION FRO |
| | ALL OUTLETS IN THE SLEEPING ROOMS INCLUSIVE OF SMOKE |
| | ALARMS, FANS, LIGHTING ETC. |
| | PLEASE SEE 210.12 |
| | |
| | 9) NOTE: PLEASE SEE MINIMUM LOADS TO BE FIGURED FOR |
| | RECESSED LIGHTING. PLEASE SEE THAT THE WATTAGE BASED ON |
| | THE AMOUNT OF EACH OF THESE TYPES OF FIXTURES DO EXCEED |
| | THE 3VA PER SQ FT.THIS WAS CONFIRMED BY THE CODE |
| | PANELIST AND THE AHJ IS THE DETERMINING AUTHORITY. |
| | PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY |
| | FROM THE 2005 NEC AND SOME COMMENTARY FROM THE |
| | HANDBOOK. |
| | |
| | *D) LUMINAIRES (LIGHTING FIXTURES) AN OUTLET SUPPLYING |
| | LUMINAIRE(S) [LIGHTING FIXTURE(S)] SHALL BE CALCULATED |
| | BASED ON THE MAXIMUM VOLT-AMPERE RATING OF THE |
| | EQUIPMENT AND LAMPS FOR WHICH THE LUMINAIRE(S) |
| | [FIXTURE(S)] IS RATED. |
| | IN GENERAL, NO ADDITIONAL CALCULATION IS REQUIRED FOR |
| | LUMINAIRES (RECESSED AND SURFACE MOUNTED) INSTALLED IN |
| | OR ON A DWELLING UNIT, BECAUSE THE LOAD OF SUCH |
| | LUMINAIRES IS COVERED IN THE 3 VOLT-AMPERES PER SQUARE |
| | FOOT CALCULATION SPECIFIED BY TABLE 220.12. WHERE THE |
| | RATING OF THE LUMINAIRES INSTALLED FOR GENERAL LIGHTING |
| | EXCEEDS THE MINIMUM LOAD PROVIDED FOR IN TABLE 220.12, |
| | THE MINIMUM GENERAL LIGHTING LOAD FOR THAT PREMISES IS |
| | TO BE BASED ON THE INSTALLED LUMINAIRES. DISTINGUISHING |
| | BETWEEN THE LUMINAIRES INSTALLED FOR GENERAL LIGHTING |
| | VERSUS THOSE INSTALLED FOR ACCENT, SPECIALTY OR DISPLAY |
| | LIGHTING IS MUCH EASIER TO DELINEATE IN COMMERCIAL |
| | (PARTICULARLY MERCANTILE) OCCUPANCIES. |
| | |
| | AS STATED, *IN GENERAL* AN ADDITIONAL AMOUNT IS NOT |
| | NEEDED ONLY WHEN THE FIXTURES ARE USED FOR NORMAL |
| | GENERAL LIGHTING. WHEN THE FIXTURES EXCEED THE GENERAL |
| | LIGHTING USE AS THIS IS DONE ON THIS PLAN, THEN THE |
| | ADDITIONAL SHALL BE FIGURED. |
| | PLEASE SEE THIS SECTION IN THE 2002 NEC WAS 220.3B4 |
| | |
| | 10) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS FOR SMOKE |
| | DETECTION DEVICES.PLEASE SEE THAT SMOKE DETECTORS ARE |
| | DEVICES WHICH ONLY DETECT AND DO NOT SOUND AND ALARM |
| | WHEREAS SMOKE ALARMS ARE DEVICES WHICH DETECT AND SOUND |
| | AN ALARM. |
| | AS THE PLAN INDICATES SD FOR SMOKE DETECTORS THIS SEEMS |
| | IT SHOULD BE SA FOR SMOKE ALARMS. |
| | PLEASE SEE THE 2002 NFPA-72 |
| | |
| | 11) NOTE: PLEASE SEE THE PLANS DO NOT SHOW ANY OF THE |
| | MAINS AS SHOWN ON RISER ON THE OUTSIDE OF THE HOUSE. |
| | ONLY THE METER AND ATS IS SHOWN. |
| | PLEASE COORDINATE. |
| | FBC 106.1.2 |
| | |
| | 12) NOTE: PLEASE SEE THE POOL PANEL DOES NOT MEET THE |
| | MINIMUM CLEARANCE REQUIREMENTS PER 110.26. |
| | |
| | 13) NOTE: PLEASE SEE THE HOT WATER HEATERS ARE BEING |
| | SHOWN AS CONNECTED BY MEANS OF RECEPTACLES WHICH ARE |
| | NOT PERMITTED. |
| | PLEASE SEE 422.30, 422.31. |
| | PLEASE INDICATE ON PLANS. |
| | |
| | 14) NOTE: PLEASE SEE 422.13 AS THE LOADS FOR THE WATER |
| | HEATERS ARE TO BE FIGURED AT 125% FOR CONTINUOUS |
| | LOADS. |
| | THIS WAS REVISED IN THE 2005 NEC AND PLEASE SEE CODE |
| | COMMENTARY IN THE NEC HANDBOOK. |
| | |
| | 15) NOTE: PLEASE GO OVER FIXTURES AND LOCATIONS IN ALL |
| | STORAGE CLOSETS FOR MINIMUM CLEARANCES FOR FIXTURES |
| | FROM CLOSET SHELVING PER 410.8 |
| | PLEASE SEE THERE ARE SOME ON PLANS WHICH AS SHOWN ARE |
| | TOO CLOSE TO SHELVES. |
| | |
| | 16) NOTE: PLEASE COMPLETE PANEL SCHEDULES WITH THE |
| | BRANCH CIRCUIT CONDUCTOR SIZES. |
| | 408.4, 240.4, 310.16. |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 17) NOTE: PLEASE SUBMIT MORE INFORMATION ON THE |
| | PROPOSED LIGHTING CONTROL PANELS AND SYSTEM. PLEASE SEE |
| | 110.3, 90.7 AS VERIFICATION OF THE TYPE OF SYSTEM, |
| | LISTING FROM A NRTL, LOCATIONS AND TYPE OF WIRING BEING |
| | INSTALLED. |
| | |
| | 18) NOTE: PLEASE SEE SOME 3-WAY SWITCHING LOCATIONS ARE |
| | SHOWING A S3, (3-WAY DEVICE AT EITHER END WHICH IS OK, |
| | HOWEVER PLEASE CLARIFY THAT BOTH ENDS ARE SHOWN AS |
| | BEING DIMMERS? |
| | IN 3-WAY AND OR 4-WAY WIRING SYSTEMS THE DIMMERS ARE |
| | TYPICALLY ONLY AT ONE LOCATION BASED ON STANDARD |
| | DEVICES WHICH IS WHAT IS BEING SHOWN. |
| | PLEASE SEE THE NOTE #16 ABOVE AS THESE MAY BE A PART OF |
| | THE LIGHTING CONTROL SYSTEM WHICH IS NOT KNOWN AT THIS |
| | TIME. |
| | |
| | 19) NOTE: PLEASE SEE THE LOADS FOR THE AIR HANDLERS ARE |
| | IN QUESTION. THE A/C DETAILS INDICATE LOADS IN KW WHICH |
| | ARE SUBSTANTIALLY HIGHER THAN THAT OF THE LOAD SHOWN ON |
| | THE LOAD CALCULATIONS. |
| | PLEASE SEE 220.60 AS THE LARGER OF THE HEATING AND |
| | COOLING LOADS ARE TO BE FIGURED. |
| | |
| | 20) NOTE: PLEASE KNOW AS FOR INFORMATION THE LOW |
| | VOLTAGE AS SHOWN ON PLANS WILL BE REQUIRED TO BE UNDER |
| | SEPARATE PERMITS. THESE PLANS WHICH CONTAIN ITEMS FOR |
| | MANY LV ITEMS MAY BE USED AS A REFERENCE FOR TURN |
| | AROUND PERMITS HOWEVER SEPARATE APPLICATION AND FEES |
| | WILL BE DUE BASED ON THE SEPARATE VALUATIONS OF THESE |
| | SYSTEMS. |
| | *ANY LOW VOLTAGE SECURITY IS ALSO UNDER A SEPARATE |
| | PERMIT. THESE DO NOT NEED PLANS UNLESS CAMERA OR ACCESS |
| | CONTROL SYSTEMS ARE BEING INSTALLED. THE DEVICE |
| | LOCATIONS INCLUDING THE LOCATION OF SECURITY PANELS DO |
| | NOTNEED TO BE INCLUDED ON ANY PANELS. |
| | THE LV FOR ALARM SYSTEMS IS UNDER SEPARATE FEES BASED |
| | ON THAT SCOPE OF WORK. |
| | THIS IS ONLY NOTED FOR INFORMATION AND NO INFORMATION |
| | AND CHANGES NEED TO BE MADE ON PLANS. |
| | ** IF THERE IS ANY CLARIFICATION NEEDED PLEASE CONTACT |
| | THIS OFFICE/REVIEWER. |
| | |
| | 21) NOTE: PLEASE SEE THE PLANS INDICATE THE RECEPTACLE |
| | BEING NOTED FOR THE WINE COOLER (MAIN) BEING CIRCUITED |
| | TO OTHER GENERAL PURPOSE RECEPTACLES IN THE DWELLING. |
| | PLEASE CLARIFY THIS AS SHOWN. |
| | PLEASE VERIFY LOAD AND PROVIDE INFORMATION FOR ANY |
| | CHANGES WITH ANY MOTOR LOADS ON THE GENERAL PURPOSE |
| | BRANCH RECEPTACLES. |
| | FBC 106.1.2. |
| | 430.6 AND SEVERAL OTHER CODES IN 430 FOR INFORMATION |
| | INCLUDING 430.148 |
| | |
| | 22) NOTE: PLEASE SEE THE A/C CLOSET DETAILS ON SHEET |
| | FOR SECOND FLOOR. THE DISCONNECT SHOWN FOR ONE O OF THE |
| | AIR HANDLER UNITS DO NOT SEEM TO MEET 110.26. |
| | |
| | 23) NOTE: PLEASE SEE THE PLANS NOTES *BREAKER LOCK |
| | DEVICES* FOR SMOKE ALARMS. |
| | PLEASE KNOW AS NOTED ABOVE THESE REQUIRE ARC FAULT |
| | PROTECTION REQUIRED, THESE SMOKE DEVICES MAY BE PLACED |
| | ON THE LIGHTING/RECEPTACLE CIRCUITS FOR BEDROOMS. |
| | |
| | 24) NOTE: PLEASE PROVIDE A NOTE ON PLANS FOR THE TYPE |
| | OF RECESSED LIGHTING AS REQUIRED PER FBC |
| | 13-606-1.ABC.1.2.4. |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY |
| | OR MAY NOT AFFECT ELECTRICAL PLANS. |
| | |
| | |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-08-31 07:58:21 | 2007-08-31 07:58:21 |
| | |
| | REVIEW CONTINUED |
| 2007-08-29 20:50:20 | 2007-08-29 20:50:20 |
| | |
| | ELECTRICAL REVIEW WILL BE PROCESSED INTO A *F* STATUS |
| | AND NOTES WILL FOLLOW ONCE REVIEW IS COMPLETED ON 8/30 |
| 2007-08-29 19:55:58 | 2007-08-29 19:55:58 |
| | IN ELEC FOR REVIEW |