Plan Review Notes
Plan Review Notes For Permit 07080572
Permit Number 07080572
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-31 10:20:562007-08-31 10:20:56
  
 ** DENIED**
  
  
  
 1) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS DO NOT
 CONTAIN AN ORIGINAL SIGNATURE AND DATE AS REQUIRED PER
 FLORIDA STATUTES 481.221.
 THE PLANS ARE REQUIRED TO BE SIGNED AS ORIGINAL.
 PLACING A RAISED SEAL OVER AN *IMAGED* SIGNATURE IS NOT
 ACCEPTABLE PER THE MINIMUM REQUIREMENTS OF THE FAC AND
 FS.
 **THIS IS REQUIRED FOR ALL SHEETS AND ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWS.
  
 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION ON THE
 TITLE BLOCKS FOR THE ARCHITECTURAL FIRM.
 PLEASE KNOW THAT THE MISSING CERTIFICATE OF
 AUTHORIZATION AS REQUIRED FOR THE FIRM WHICH IS
 REQUIRED TO BE ON THE TITLE BLOCK IS IN FACT DELINQUENT
 WITH THE STATE. PLEASE SEE THE ATTACHED PRINT OUT FROM
 THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
 WHICH INDICATES THIS AS OF THIS REVIEW.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND
 FLORIDA STATUTES 481.219
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND ALL
 SHEETS WHICH CONTAINS THIS TITLE BLOCK WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE(S).
  
 3) NOTE: PLEASE SEE THE TITLE BLOCK FOR THE ENGINEER
 AND FIRM AS SHOWN IS ALSO MISSING INFORMATION. PLEASE
 SEE THE MISSING PRINTED NAME, PRINTED LICENSE NUMBER
 AND MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 **PLEASE KNOW THIS IS REQUIRED FOR ALL MEP SHEETS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE(S).
  
 4) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
  
 5) NOTE: PLEASE SEE THE PLANS ARE SHOWING A NEW
 GENERATOR AND ATS BEING INCLUDED WITH THE SCOPE OF WORK
 FOR HOUSE HOWEVER PLEASE SUBMIT THE MANUFACTURES
 SPEC/CUT SHEETS FOR BOTH.IF THE GENERATOR WILL BE
 UNDER A SEPARATE PERMIT PLEASE ADJUST PLANS TO INDICATE
 THIS.
 PLEASE KNOW THE GENERATOR SPECS/CUT SHEETS ARE TO
 INDICATE THE MINIMUM CLEARANCES FOR UNIT.
 PLEASE SUBMIT AND SEE COMMENTS FROM OTHER TRADES FROM
 ZONING, BUILDING AND PLUMBING.
 FBC 106.1.1, 106.1.2,
 NEC 110.3, 90.7
  
 6) NOTE: PLEASE SEE THERE ARE SEVERAL SPECIFIC
 DEDICATED APPLIANCE LOADS AND MOTORS LOADS ON THE
 ELECTRICAL PANEL SCHEDULES WHERE THE LOADS ARE NOT
 INCLUDED IN THE LOAD CALCULATIONS.
 PLEASE GO OVER CALCULATIONS AND ADJUST AS NEEDED.
 PLEASE SEE FOR EXAMPLE MISSING, WATER PUMP,
 REFRIGERATOR, WASHER, CENTRAL VACUUM, GARAGE DOOR
 OPENER ETC.
 PLEASE SEE NEC 220 AND SEE SOME COMMENTS BELOW FOR SOME
 OTHER LOADS.
  
 7) NOTE:PLEASE SEE 210. 52C2 AND 220.53 FOR MINIMUM
 LOADS FOR THE WASHER/LAUNDRY LOADS AS REQUIRED. PLEASE
 SEE THE PANEL SCHEDULE DOES NOT INDICATE THE MINIMUM OF
 1500VA FOR EACH OF THESE AS SHOWN AND LISTED. PLEASE
 ALSO SEE THE LOADS SHOWN ON THE LOAD CALCULATIONS ON
 THE SERVICE INDICATE (2) LAUNDRY LOADS HOWEVER THE TWO
 ARE SHOWN WITH A TOTAL OF 4500VA?
 IT IS UNCLEAR HOW THESE LOADS ARE BEING DETERMINED AS
 THE PANEL SCHEDULE AND OTHER LOADS ARE NOT THE SAME.
 PLEASE SEE THE SECTIONS AS NOTED FOR THE MINIMUM
 LOADS.
 PLEASE ADJUST.
  
 8) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTION FRO
 ALL OUTLETS IN THE SLEEPING ROOMS INCLUSIVE OF SMOKE
 ALARMS, FANS, LIGHTING ETC.
 PLEASE SEE 210.12
  
 9) NOTE: PLEASE SEE MINIMUM LOADS TO BE FIGURED FOR
 RECESSED LIGHTING. PLEASE SEE THAT THE WATTAGE BASED ON
 THE AMOUNT OF EACH OF THESE TYPES OF FIXTURES DO EXCEED
 THE 3VA PER SQ FT.THIS WAS CONFIRMED BY THE CODE
 PANELIST AND THE AHJ IS THE DETERMINING AUTHORITY.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY
 FROM THE 2005 NEC AND SOME COMMENTARY FROM THE
 HANDBOOK.
  
 *D) LUMINAIRES (LIGHTING FIXTURES) AN OUTLET SUPPLYING
 LUMINAIRE(S) [LIGHTING FIXTURE(S)] SHALL BE CALCULATED
 BASED ON THE MAXIMUM VOLT-AMPERE RATING OF THE
 EQUIPMENT AND LAMPS FOR WHICH THE LUMINAIRE(S)
 [FIXTURE(S)] IS RATED.
 IN GENERAL, NO ADDITIONAL CALCULATION IS REQUIRED FOR
 LUMINAIRES (RECESSED AND SURFACE MOUNTED) INSTALLED IN
 OR ON A DWELLING UNIT, BECAUSE THE LOAD OF SUCH
 LUMINAIRES IS COVERED IN THE 3 VOLT-AMPERES PER SQUARE
 FOOT CALCULATION SPECIFIED BY TABLE 220.12. WHERE THE
 RATING OF THE LUMINAIRES INSTALLED FOR GENERAL LIGHTING
 EXCEEDS THE MINIMUM LOAD PROVIDED FOR IN TABLE 220.12,
 THE MINIMUM GENERAL LIGHTING LOAD FOR THAT PREMISES IS
 TO BE BASED ON THE INSTALLED LUMINAIRES. DISTINGUISHING
 BETWEEN THE LUMINAIRES INSTALLED FOR GENERAL LIGHTING
 VERSUS THOSE INSTALLED FOR ACCENT, SPECIALTY OR DISPLAY
 LIGHTING IS MUCH EASIER TO DELINEATE IN COMMERCIAL
 (PARTICULARLY MERCANTILE) OCCUPANCIES.
  
 AS STATED, *IN GENERAL* AN ADDITIONAL AMOUNT IS NOT
 NEEDED ONLY WHEN THE FIXTURES ARE USED FOR NORMAL
 GENERAL LIGHTING. WHEN THE FIXTURES EXCEED THE GENERAL
 LIGHTING USE AS THIS IS DONE ON THIS PLAN, THEN THE
 ADDITIONAL SHALL BE FIGURED.
 PLEASE SEE THIS SECTION IN THE 2002 NEC WAS 220.3B4
  
 10) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS FOR SMOKE
 DETECTION DEVICES.PLEASE SEE THAT SMOKE DETECTORS ARE
 DEVICES WHICH ONLY DETECT AND DO NOT SOUND AND ALARM
 WHEREAS SMOKE ALARMS ARE DEVICES WHICH DETECT AND SOUND
 AN ALARM.
 AS THE PLAN INDICATES SD FOR SMOKE DETECTORS THIS SEEMS
 IT SHOULD BE SA FOR SMOKE ALARMS.
 PLEASE SEE THE 2002 NFPA-72
  
 11) NOTE: PLEASE SEE THE PLANS DO NOT SHOW ANY OF THE
 MAINS AS SHOWN ON RISER ON THE OUTSIDE OF THE HOUSE.
 ONLY THE METER AND ATS IS SHOWN.
 PLEASE COORDINATE.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE THE POOL PANEL DOES NOT MEET THE
 MINIMUM CLEARANCE REQUIREMENTS PER 110.26.
  
 13) NOTE: PLEASE SEE THE HOT WATER HEATERS ARE BEING
 SHOWN AS CONNECTED BY MEANS OF RECEPTACLES WHICH ARE
 NOT PERMITTED.
 PLEASE SEE 422.30, 422.31.
 PLEASE INDICATE ON PLANS.
  
 14) NOTE: PLEASE SEE 422.13 AS THE LOADS FOR THE WATER
 HEATERS ARE TO BE FIGURED AT 125% FOR CONTINUOUS
 LOADS.
 THIS WAS REVISED IN THE 2005 NEC AND PLEASE SEE CODE
 COMMENTARY IN THE NEC HANDBOOK.
  
 15) NOTE: PLEASE GO OVER FIXTURES AND LOCATIONS IN ALL
 STORAGE CLOSETS FOR MINIMUM CLEARANCES FOR FIXTURES
 FROM CLOSET SHELVING PER 410.8
 PLEASE SEE THERE ARE SOME ON PLANS WHICH AS SHOWN ARE
 TOO CLOSE TO SHELVES.
  
 16) NOTE: PLEASE COMPLETE PANEL SCHEDULES WITH THE
 BRANCH CIRCUIT CONDUCTOR SIZES.
 408.4, 240.4, 310.16.
 FBC 106.1.2, 106.3.5.4
  
 17) NOTE: PLEASE SUBMIT MORE INFORMATION ON THE
 PROPOSED LIGHTING CONTROL PANELS AND SYSTEM. PLEASE SEE
 110.3, 90.7 AS VERIFICATION OF THE TYPE OF SYSTEM,
 LISTING FROM A NRTL, LOCATIONS AND TYPE OF WIRING BEING
 INSTALLED.
  
 18) NOTE: PLEASE SEE SOME 3-WAY SWITCHING LOCATIONS ARE
 SHOWING A S3, (3-WAY DEVICE AT EITHER END WHICH IS OK,
 HOWEVER PLEASE CLARIFY THAT BOTH ENDS ARE SHOWN AS
 BEING DIMMERS?
 IN 3-WAY AND OR 4-WAY WIRING SYSTEMS THE DIMMERS ARE
 TYPICALLY ONLY AT ONE LOCATION BASED ON STANDARD
 DEVICES WHICH IS WHAT IS BEING SHOWN.
 PLEASE SEE THE NOTE #16 ABOVE AS THESE MAY BE A PART OF
 THE LIGHTING CONTROL SYSTEM WHICH IS NOT KNOWN AT THIS
 TIME.
  
 19) NOTE: PLEASE SEE THE LOADS FOR THE AIR HANDLERS ARE
 IN QUESTION. THE A/C DETAILS INDICATE LOADS IN KW WHICH
 ARE SUBSTANTIALLY HIGHER THAN THAT OF THE LOAD SHOWN ON
 THE LOAD CALCULATIONS.
 PLEASE SEE 220.60 AS THE LARGER OF THE HEATING AND
 COOLING LOADS ARE TO BE FIGURED.
  
 20) NOTE: PLEASE KNOW AS FOR INFORMATION THE LOW
 VOLTAGE AS SHOWN ON PLANS WILL BE REQUIRED TO BE UNDER
 SEPARATE PERMITS. THESE PLANS WHICH CONTAIN ITEMS FOR
 MANY LV ITEMS MAY BE USED AS A REFERENCE FOR TURN
 AROUND PERMITS HOWEVER SEPARATE APPLICATION AND FEES
 WILL BE DUE BASED ON THE SEPARATE VALUATIONS OF THESE
 SYSTEMS.
 *ANY LOW VOLTAGE SECURITY IS ALSO UNDER A SEPARATE
 PERMIT. THESE DO NOT NEED PLANS UNLESS CAMERA OR ACCESS
 CONTROL SYSTEMS ARE BEING INSTALLED. THE DEVICE
 LOCATIONS INCLUDING THE LOCATION OF SECURITY PANELS DO
 NOTNEED TO BE INCLUDED ON ANY PANELS.
 THE LV FOR ALARM SYSTEMS IS UNDER SEPARATE FEES BASED
 ON THAT SCOPE OF WORK.
 THIS IS ONLY NOTED FOR INFORMATION AND NO INFORMATION
 AND CHANGES NEED TO BE MADE ON PLANS.
 ** IF THERE IS ANY CLARIFICATION NEEDED PLEASE CONTACT
 THIS OFFICE/REVIEWER.
  
 21) NOTE: PLEASE SEE THE PLANS INDICATE THE RECEPTACLE
 BEING NOTED FOR THE WINE COOLER (MAIN) BEING CIRCUITED
 TO OTHER GENERAL PURPOSE RECEPTACLES IN THE DWELLING.
 PLEASE CLARIFY THIS AS SHOWN.
 PLEASE VERIFY LOAD AND PROVIDE INFORMATION FOR ANY
 CHANGES WITH ANY MOTOR LOADS ON THE GENERAL PURPOSE
 BRANCH RECEPTACLES.
 FBC 106.1.2.
 430.6 AND SEVERAL OTHER CODES IN 430 FOR INFORMATION
 INCLUDING 430.148
  
 22) NOTE: PLEASE SEE THE A/C CLOSET DETAILS ON SHEET
 FOR SECOND FLOOR. THE DISCONNECT SHOWN FOR ONE O OF THE
 AIR HANDLER UNITS DO NOT SEEM TO MEET 110.26.
  
 23) NOTE: PLEASE SEE THE PLANS NOTES *BREAKER LOCK
 DEVICES* FOR SMOKE ALARMS.
 PLEASE KNOW AS NOTED ABOVE THESE REQUIRE ARC FAULT
 PROTECTION REQUIRED, THESE SMOKE DEVICES MAY BE PLACED
 ON THE LIGHTING/RECEPTACLE CIRCUITS FOR BEDROOMS.
  
 24) NOTE: PLEASE PROVIDE A NOTE ON PLANS FOR THE TYPE
 OF RECESSED LIGHTING AS REQUIRED PER FBC
 13-606-1.ABC.1.2.4.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 OR MAY NOT AFFECT ELECTRICAL PLANS.
  
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-08-31 07:58:212007-08-31 07:58:21
  
 REVIEW CONTINUED
2007-08-29 20:50:202007-08-29 20:50:20
  
 ELECTRICAL REVIEW WILL BE PROCESSED INTO A *F* STATUS
 AND NOTES WILL FOLLOW ONCE REVIEW IS COMPLETED ON 8/30
2007-08-29 19:55:582007-08-29 19:55:58
 IN ELEC FOR REVIEW