Plan Review Notes
Plan Review Notes For Permit 07080565
Permit Number 07080565
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-04 07:31:33 
  
 ** DENIED**
  
 1) NOTE: PLEASE BE SURE ELECTRICAL AND ARCHITECTURAL
 SHEETS STATE THE FOLLOWING MINIMUM CODES.
 2006 FBC W/2006 REVISIONS.
 2005 NFPA-70.
 2003 NFPA-101
 2002 NFPA-72
  
 ** THE FBC IS ALREADY ON SOME SHEETS.
  
 2) NOTE: PLEASE SEE THE SEAL IN USE BY THE ENGINEER AS
 LISTED ON THE MECHANICAL AND ELECTRICAL SHEETS IS NO
 LONGER VALID FOR USE IN THE STATE OF FLORIDA.
 PLEASE SEE RULING FROM THE FLORIDA BOARD OF ENGINEERS
 DATED FEB *04* WHICH REQUIRED ALL SEALS FOR ENGINEERS
 TO CHANGE FROM THE WORDING OF *CERTIFICATE* TO THE
 *LICENSE* IN SAID SEAL. AN EXTENSION IN TIME WAS GIVEN
 HOWEVER THAT WAS ONLY UNTIL DECEMBER 31ST, 2005.THIS
 RULING WAS OVER THREE YEARS AGO AND THE SEAL ON PLANS
 IS NO LONGER ACCEPTABLE. PLEASE OBTAIN NEW SEAL AND
 RE-SIGN, DATE AND SEAL PLANS.
 FAC 61G15-23.001, FS 471.025
  
 ** THIS IS REQUIRE FOR ALL SHEETS AND TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADE REVIEWER(S).
  
 3) NOTE: PLEASE PROVIDE INFORMATION ON THE
 EGRESS/ACCESS CONTROL FOR FAIL SAFE OPERATION. PLEASE
 SEE IF THE POWER TO THE LOCAL EM PANEL WHICH IS BEING
 NOTED FOR CIRCUITING FAILS OR ONLY A SINGLE BRANCH
 CIRCUIT FAILS, THERE WILL BE NO POWER TO UNITS WHICH
 WOULD NOT PROVIDE EGRESS UNDER AN EMERGENCY CONDITION.
 PLEASE KNOW THE GENERATOR WILL ONLY PROVIDE BACK UP IN
 THE EVENT THE POWER FAILS FOR THE ENTIRE BUILDING NOT
 PARTS OF THE BUILDING.
 PLEASE SEE LS 101 CHAPTER 7.2.1, 7.2.1.5, 7.2.1.6.2
 ** PLEASE SEE POSSIBLE COMMENTS FROM THE FIRE MARSHAL.
  
 4) NOTE: PLEASE CLARIFY THE CIRCUITING OF EMERGENCY AND
 EXIT LIGHTING PER 700.12F OF THE NEC.
 PLEASE SEE THE NOTE MENTIONS TO THE EM PANELS, HOWEVER
 HOW THE LIGHTING WILL COME ON IF THE NORMAL LIGHTING IN
 THE AREA WHICH IS FED FROM A LOCAL PANEL OR LOCAL
 CIRCUIT FAILS. PLEASE SEE EXCERPT FROM THE NEC.
 *THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.*
  
 5) NOTE: PLEASE PROVIDE NOTE INFORMATION TO VERIFY THE
 LEVELS OF THE STROBES, HORN DEVICES MEETING THE MINIMUM
 LEVELS PER FBC FOR ADA. 11-4.28.1,.2, AND .3(4).
  
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]