2007-08-22 09:11:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) THE JOB ADDRESS NEEDS TO BE ON THE PLANS, SEE 2004
 WPB 106.1.3.
  
 2) BEDROOMS (?) SHOW A 3X15 RH BUT NOT THE DUCT SIZE IF
 ALSO 3X15 STATE SO ON PLAN.
  
 3) EQUIPMENT SCHEDULE SHOWS THE SYSTEM AS FPH, DOES
 THAT STAND FOR FLORIDA HEAT PUMP (FHP)?
  
 4) PLEASE ADD A LEGEND TO THE PLAN DEFINING WHAT HR,
 LFM, ETC..
  
 5) IF THE 3X15 GRILLS ARE LINEAR GRILLS STATE SO ON
 PLAN.
  
 6) WERE GRILLS ARE BEING SHOWN AS TWO PARALLEL LINES,
 PLEASE USE A PROPER SYMBOL, SEE EXAMPLE BELOW.
  