Plan Review Notes
Plan Review Notes For Permit 07080551
Permit Number 07080551
Review Stop G
Sequence Number 2
Notes
Date Text
2007-10-16 09:21:06DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 1. THERE ARE TWO DIFFERENT SETS OF GAS RISER DIAGRAMS
 IN THE RESUBMITTAL. ONE THAT IS SIGNED AND SEALED BY
 JAMES L. MAKO P.E. #54111 USING 1 INCH COPPER PIPE AND
 ONE BY FLORIDA PUBLIC UTILITIES CO. USING 3/4 INCH PE
 PIPE UNDERGROUND AND 3/4 INCH SCH. 40 GALV. PIPE ABOVE
 GROUND. PLEASE NOTE THAT THE SUBMITTED DRAWINGS BY
 FLORIDA PUBLIC UTILITIES CO. ARE CORRECT IN THAT THEY
 INDICATE THE ENTIRE GAS SYSTEM PIPING AND BTU LOAD
 (WHICH IS REQUIRED BY CITY REQUIREMENTS). THE SIGNED
 AND SEALED PLANS DO NOT INDICATE THIS. PLEASE CORRELATE
 THE RESUBMITTAL WITH ONLY ONE SET OF GAS RISER
 DIAGRAMS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  