Plan Review Notes
Plan Review Notes For Permit 07080551
Permit Number 07080551
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-10 16:10:14 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} IT IS THE DETERMINATION OF THIS OFFICE THAT LOADS
 BEING TRANSFERRED AUTOMATICALLY ARE THE LOADS SELECTED
 UNDER ARTICLE 702.5. UTILITY POWER CAN BE DISRUPTED AT
 ANY TIME, POSSIBLY IN THE OWNERS ABSENCE. THEREFORE ALL
 CONNECTED LOADS WILL BE ENERGIZED AS THERE IS NO ONE TO
 "SELECT" WHICH CIRCUITS WILL BE ENERGIZED. THEREFORE
 ALL CONNECTED LOADS WILL BE ENERGIZED AS THERE IS NOONE
 TO "SELECT"WHICH CIRCUITS WILL BE ENERGIZED. THE
 CALCULATION GIVEN WOULD INCLUDE THE "LOAD SHEDDING
 JUSTIFICATION" OF THE WHIRLPOOL EQUIPMENT AS THEY ARE
 IN THE SELECTED PANEL. THE ACCEPTABLE LOAD WILL DEPEND
 ON THE GENERATOR SPECIFICATIONS, SEE COMMENT #2.
  
 2}PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING
 RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S FOR THE
 GENERATOR AND TRANSFER SWITCH.
  
 3} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718