| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} IT IS THE DETERMINATION OF THIS OFFICE THAT LOADS |
| | BEING TRANSFERRED AUTOMATICALLY ARE THE LOADS SELECTED |
| | UNDER ARTICLE 702.5. UTILITY POWER CAN BE DISRUPTED AT |
| | ANY TIME, POSSIBLY IN THE OWNERS ABSENCE. THEREFORE ALL |
| | CONNECTED LOADS WILL BE ENERGIZED AS THERE IS NO ONE TO |
| | "SELECT" WHICH CIRCUITS WILL BE ENERGIZED. THEREFORE |
| | ALL CONNECTED LOADS WILL BE ENERGIZED AS THERE IS NOONE |
| | TO "SELECT"WHICH CIRCUITS WILL BE ENERGIZED. THE |
| | CALCULATION GIVEN WOULD INCLUDE THE "LOAD SHEDDING |
| | JUSTIFICATION" OF THE WHIRLPOOL EQUIPMENT AS THEY ARE |
| | IN THE SELECTED PANEL. THE ACCEPTABLE LOAD WILL DEPEND |
| | ON THE GENERATOR SPECIFICATIONS, SEE COMMENT #2. |
| | |
| | 2}PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING |
| | RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S FOR THE |
| | GENERATOR AND TRANSFER SWITCH. |
| | |
| | 3} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON |
| | A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE, |
| | DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH |
| | ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |