| 2007-09-11 15:02:04 | *** DENIED *** |
| | |
| | |
| | 1) NOTE: PLEASE SEE 13-101, 13-415.1.1,.1.2 FOR |
| | REQUIRED LIGHTING CONTROLS FOR NEW LIGHTING. |
| | PLEASE EXPLAIN HOW METHOD *A* IS BEING USED FOR WHOLE |
| | BUILDING WHEN THIS IS AN EXISTING CONDITIONED SPACE. |
| | *FOR ELECTRICAL, ONLY NEED TO MEET THE MAXIMUM |
| | PERFORMANCE LEVELS FOR LIGHTING DENSITIES PER 13-415.2 |
| | AND TABLES 415.2.C.1, 415.2.B.1. |
| | THIS CAN BE SHOWN ON TABLE OF SOME SORT ON PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |