| 2007-11-09 09:33:13 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS |
| | TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE ON THE |
| | RESUBMITTED PLANS. |
| | |
| | 1. SHEET A6.0 PLUMBING RISER DIAGRAM: THE BIDET IN THE |
| | MASTER BATH IS NOT VENTED. PER *901.2.1, VENTING |
| | REQUIRED. |
| | |
| | 2. ENERGY CALCULATIONS WERE NOT RESUBMITTED WITH PLANS |
| | PLEASE RESUBMIT ENERGY CALULATIONS WITH WATER HEATING |
| | REQUIREMENTS PER |
| | CHAPTER 13 ENERGY EFFICIENCY SECTION 13-101.0 GENERAL. |
| | THIS CODE IS A STATEWIDE UNIFORM CODE AND SHALL NOT BE |
| | MADE MORE STRINGENT OR LENIENT BY LOCAL GOVERNMENT. THE |
| | CODE PROVIDES FOR A UNIFORM STANDARD OF ENERGY |
| | EFFICIENCY BY, AT A MINIMUM, SETTING FORTH MINIMUM |
| | REQUIREMENTS FOR EXTERIOR ENVELOPES, LIGHTING, |
| | ELECTRICAL DISTRIBUTION, AND SELECTION OF HEATING, |
| | LIGHTING, VENTILATION, AIR CONDITIONING AND SERVICE |
| | WATER HEATING SYSTEMS. IT SHALL APPLY TO ALL NEW |
| | BUILDINGS, TO ADDITIONS TO EXISTING BUILDINGS AND |
| | MANUFACTURED HOMES, TO RENOVATIONS TO EXISTING |
| | BUILDINGS, BOTH PUBLIC AND PRIVATE, WITH CERTAIN |
| | EXCEPTIONS, TO CHANGES OF OCCUPANCY TYPE, TO THE |
| | SITE-INSTALLED COMPONENTS AND FEATURES OF A |
| | MANUFACTURED HOMES AT THEIR FIRST SET-UP, AND TO THE |
| | INSTALLATION OR REPLACEMENT OF BUILDING SYSTEMS AND |
| | COMPONENTS WITH NEW PRODUCTS FOR WHICH THERMAL |
| | EFFICIENCY STANDARDS ARE SET BY THIS CODE. NEW |
| | BUILDINGS, WITH EXCEPTION OF THOSE EXEMPTED BELOW, AND |
| | IN ACCORDANCE WITH THE SPECIFIC EXCEPTIONS OF |
| | INDIVIDUAL SECTIONS SHALL BE DESIGNED TO COMPLY WITH |
| | SUBCHAPTER 13-4 OR 13-6 OF THIS CODE. |
| | |
| | **THE FOLLOWING IS CONTRACTOR INFORMATION ONLY BECAUSE |
| | SHEET A2.0 IS INDICATING GAS APPLIANCES. |
| | |
| | NOTE: GAS PERMIT REQUIRED. PLUMBING OR GAS CONTRACTOR |
| | TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL GAS |
| | INSPECTIONS TO BE COMPLETE BEFORE FINAL INSPECTION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |