| Date |
Text |
| 2007-08-22 16:07:31 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET A6 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN ON SHEET A2: PER FBC-2004 |
| | CHAPTER 1, THE CITY OF WEST PALM BEACH AMENDMENTS, |
| | SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELAVENT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | A} THE BRANCH TO THE POWDER ROOM BATH SHOULD BE BEFORE |
| | THE UTIL. THE WAY THE ISOMETRICT IS DRAWN. IF IT IS THE |
| | INTENT TO LEAVE THE BRANCH TO THE POWDER ROOM WHERE IT |
| | IS ON THE ISOMETRIC, PLEASE INDICATE THE REQUIRED |
| | OFFSETS ON THE RESUBMITTAL TO REFLECT THE FLOOR PLAN. |
| | |
| | B} LAV IS MISSING FROM BATH 3. PLEASE CORRECT ON THE |
| | RESUBMITTAL. |
| | |
| | C} DISHWASHER IS INDICATED ON THE WRONG SIDE OF THE |
| | DOUBLE BOWL SINK W/DISP. AND PER FBC-2004 PLUMBING, |
| | SECTION 802.1.6 DOMESTIC DISHWASHING MACHINES SHALL |
| | DISCHARGE INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF |
| | THE KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD |
| | WASTE GRINDER. PLEASE CORRECT ON THE RESUBMITTAL. |
| | |
| | D} HER BATH DOES NOT REFLECT THE FLOOR PLAN ON SHEET |
| | A2: |
| | |
| | A) SHEET A2 DOES NOT INDICATE A BIDET, BUT THE |
| | SANITARY ISOMETRIC IS INDICATING A BIDET ON SHEET A6. |
| | PLEASE CLARIFY AND CORRECT ON THE RESUBMITTAL. |
| | |
| | B) LAV IS BEING INDICATED IN THE WRONG PLACE. PLEASE |
| | CORRECT ON THE RESUBMITTAL. |
| | |
| | 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| | RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A |
| | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| | ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT |
| | LOCATIONS. |
| | NOTE: NOT ALL PIPES OR TRAPS ARE SIZED ON THE SANITARY |
| | ISOMETRIC RISER DIAGRAM ON SHEET A6. PLEASE CORRECT |
| | THIS ON THE RESUBMITTAL. |
| | |
| | 3. SHEET A2 IS INDICATING GAS APPLIANCES: |
| | |
| | **CONTRACTOR INFORMATION** |
| | |
| | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- |
| | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- |
| | TION. ALL GAS INSPECTIONS TO BE COMPLETE |
| | BEFORE FINAL INSPECTION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL= [email protected] |