| 2007-08-17 07:30:37 | ROOF OVER/RECOVER DECK | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) THE CONDITION OF THE EXISTING ROOF WILL BE REQUIRED | | | TO BE INSPECTED BY THE CONSTRUCTION SERVICES DEPT. | | | | | | 3) THE FASTENERS SPECIFIED IN THE PRODUCT APPROVAL NOA | | | ARE REQUIRED TO BE USED. THEY CAN NOT BE CHANGED BY | | | ANYONE EXCEPT MIAMI-DADE PRODUCT CONTROL. SEE PAGE 74 | | | OF THE NOA. | | | | | | 4) THE APPROVEDASSEMBLY SPECIFIED HAS A DESIGN | | | PRESSURE OF -60 PSF WHICH IS TOO LOW FOR THE CORNER | | | AREAS THAT REQUIRE -89 PSF. HOWEVER GENERAL LIMITATION | | | NUMBER 7 ALLOWS FOR ENHANCED FASTENING TO INCREASE THE | | | DESIGN PRESSUREUSING RAS 117 CALCULATIONS. SEE PAGE 85. | | | THE NOA REQUIRES THESE CALCULATIONS TO BE DONE BY A | | | FLORIDA LICENSED ENGINEER, ARCHITECT OR REGISTERED ROOF | | | CONSULTANT. SUBMIT SIGNED AND SEALED RAS 117 | | | CALCULATIONS. | | | | | | 5)SUBMIT THE FIRST 14 PAGES OF THE NOA WHICH LIST THE | | | MATERIALS, FASTENERS, ETC. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | | |
|