Plan Review Notes
Plan Review Notes For Permit 07080456
Permit Number 07080456
Review Stop M
Sequence Number 1
Notes
Date Text
2007-08-17 12:18:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) SHOW ON THE MECHANICAL PLAN EQUIPMENT LISTING THE
 HEATER KW OR IF NO HEAT STATE SO ON PLAN.
  
 3) ELECTRICAL PLAN SHOWS EXHAUST FANS IN THE MASTER
 BATHROOM AND THE MAIN BATHROOM, IF THEY ARE BEING
 INSTALLED SHOW THEM ON THE MECHANICAL PLAN WITH THE
 CFM'S. IF NOT BEING INSTALLED REMOVE FROM ELECTRICAL
 PLAN, SEE RES. R303.3 EXEPT.
  