2007-08-22 13:23:55 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE IF THE SERVICE IS EXISTING OR PART OF THIS
 APPLICATION.
  
 2} REGARDING SMOKE DETECTORS, SEE R313.1.1 ALTERATIONS,
 REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE
 ON THE PLANS.ALSO SEE THE DEFINITION OF "SMOKE
 DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS
 OR ALARMS, TO AVOID CONFUSION IN THE FIELD. IF USING
 DETECTORS INDICATE THE LOCATIONS OF THE SOUNDING
 DEVICES.
  
 3} 210.52(A)(2)(2) REQUIRES FLOOR RECEPTACLES IN THE
 DINING ROOM FOR SPACING REQUIREMENTS OF 210.52(A).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  