Plan Review Notes
Plan Review Notes For Permit 07080456
Permit Number 07080456
Review Stop B
Sequence Number 1
Notes
Date Text
2007-09-12 12:47:042004 FBC W/2007 SUPPLEMENT
 LEVEL 2 ALTERATION AND ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SPECIFY THE APPLICABLE CODES AND EDITIONS ON THE
 PLANS. SPECIFY WHICH METHODS OF STRUCTURAL DESIGNARE
 BEING USED FOR THIS PROJECT.
  
 4) SHOW COMPLIANCE WITHR806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS. SPECIFY THE LOCATIONS AND SIZES OF THE ATTIC
 VENTS.
  
 5) SPECIFY THE SIZE OF THE ATTIC ACCESS AS REQUIRED BY
 FBC R807.1.
  
 6) SPECIFY THE CLADDING THAT WILL BE INSTALLED ON THE
 SOFFITS. IF ALUMINUM, VINYL OR OTHER TYPE OF CLADDING
 REQUIRING PRODUCT APPROVALS IS USED, SUBMIT THEIR
 PRODUCT APPROVALS.
  
 7) PROVIDE A SIDE ELEVATION WITH DIMENSIONS FOR THE
 STEEL COLUMN TOP UNDER WOOD GIRDER #2. THE SECTION THRU
 TRUSS ON SHEET 4 APPEARS TO SHOW THIS COLUMN TOP.
 PLEASE CLARIFY THIS BY LABELING IT TO TIE TO THE ROOF
 FRAMING PLAN. SPECIFY THE WELD TYPE FOR THIS COLUMN
 CAP.
  
 8) THE OWNER/AGENT IS REQUIRED BY FBC CHAPTER 13 TO
 SIGN THE ENERGY CALCULATION FORMS.
  
 9) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK AND
 THE 8" WIDE LINTELS.
  
 11)THE NOA THAT WAS SUBMITTED FOR THE PGT SINGLE HUNG
 WINDOWS HAS BEEN REVISED BY NOA NO. 07-0322.06. SUBMIT
 CURRENT PRODUCT APPROVAL.
  
 12) PLEASE CIRCLE THE ATTACHMENT METHODS THAT WILL BE
 USED TO INSTALL THE MONIER ROOF TILE ON THE PRODUCT
 APPROVAL NOA. REFER TO SHEET 3 OF THE PLANS.
  
 13) ADDITIONAL FEES OF $ 5.64 ARE DUE TO THE CITY FOR
 RADON FEES.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]