| 2007-09-28 18:37:11 | ** PROVISO/REVISION NEEDED ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE |
| | STILL IN NEED OF ADDRESSING. |
| | THE *PROVISO* WILL REQUIRE THESE ITEMS TO BE REVISED ON |
| | PLANS ALONG WITH ANY OTHER REVISIONS DONE ON THE |
| | PROJECT. |
| | ** IF PLANS COME BACK WITH ANY OTHER COMMENTS, PLEASE |
| | MAKE CORRECTIONS AT THIS TIME. THIS WILL HELP TO AVOID |
| | ANY REVISION FEES AT A LATER DATE. |
| | |
| | 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW WHICH |
| | REQUESTED THE ARC FAULT PROTECTED CIRCUITS TO BE LISTED |
| | ON PANEL SCHEDULE FOR ROOMS AND AREAS IN WHICH THEY |
| | FEED. |
| | PLANS ARE REQUIRED TO SHOW DETAILED CODE COMPLIANCE. |
| | QUOTING THE CONTRACTOR IS RESPONSIBLE TO PROVIDE AFCI |
| | BREAKERS IS NOT SHOWING CODE COMPLIANCE AS REQUIRED PER |
| | FLORIDA STATUTES 553.73 |
| | NEC 210.12 AND FBC 106.3.5.1.2, 106.1.2, 110.1.2 |
| | |
| | 2) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW; PLEASE |
| | SEE THE AMPERAGE LOAD SHOWN ON THE PANEL SCHEDULE CAN |
| | NOT POSSIBLY BE THE 2KVA AS LISTED ON LOAD |
| | CALCULATIONS. |
| | PLEASE RE-CALCULATE AS 2KVA DIVIDED BY THE VOLTAGE DOES |
| | NOT EQUATE TO THE AMPERAGE AS LISTED ON PANEL SCHEDULE. |
| | |
| | |
| | 3) NOTE: PLEASE SEE CIRCUIT NUMBER 21 WHICH IS PART OF |
| | 210.52B1, HOWEVER BASED ON THE AMPERAGE SHOWN ON PANEL |
| | SCHEDULE THIS DOES NOT MEET THE MINIMUM LOAD AS |
| | REQUIRED PER 210.11C1 AND 220.53 |
| | |
| | 4) NOTE: PLEASE SEE PANEL SCHEDULE CIRCUIT #14 WHICH |
| | STILL INDICATES SMOKE DETECTORS WHEN PLANS SHOW SMOKE |
| | ALARMS. THIS COMMENT IS MINOR AND WAS REDLINED ON |
| | PLANS. |
| | THIS CAN BE REVISED WHEN REVISING PLANS FOR OTHER ITEMS |
| | AS THIS SEEMS TO BE A MISPRINT. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |