| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE THE SMOKE DEVICES AS SHOWN ARE |
| | BEING INDICATED AS SD, WHERE THE PLANS ALSO CALL FOR |
| | THESE AS 120V UNITS. IF THESE ARE DEVICES WHICH DETECT |
| | AND SOUND AN ALARM, THEY ARE IN FACT SMOKE ALARMS (SA) |
| | AND NOT SMOKE DETECTORS. PLEASE SEE NFPA-72 DEFINITIONS |
| | AS THE SD ONLY DETECT AND DO NOT PROVIDE AN AUDIBLE |
| | ALARM. |
| | PLEASE SEE NFPA-72 11.8.3 WHICH REQUIRES ALL SMOKE |
| | DETECTION DEVICES TO BE A MINIMUM OF 20FT AWAY FROM |
| | COOKING APPLIANCES. THERE IS AN EXCEPTION TO THIS AS |
| | LONG AS ONE OF TWO SPECIFIC TYPES OF UNITS IS |
| | INSTALLED. PLEASE SPECIFY |
| | PLEASE ADJUST. |
| | |
| | 2) NOTE: PLEASE SEE THE REQUIRED DEDICATED BATH CIRCUIT |
| | FOR THE GFI IS BEING SHOWN ON THE SAME CIRCUIT AS THE |
| | SMOKE DETECTION DEVICES WHICH ARE NOT PERMITTED. PLEASE |
| | SEE 210.52D,210.11C3. |
| | (MUST BE 20AMP AND #12). |
| | |
| | 3) NOTE: PLEASE SEE THE MISSING LOAD TO BE FIGURED IN |
| | THE LOAD CALCULATIONS FOR THE DINING ROOM RECEPTACLES |
| | PER 210.52B1, 210.11C1, AND 220.53. |
| | (1500VA MIN) |
| | |
| | 4) NOTE: PLEASE SEE THERE ARE SEVERAL ITEMS ON THE LOAD |
| | CALCULATIONS WHICH DO NOT MATCH WITH THE AMPERAGE LOADS |
| | BEING SHOWN ON THE PANEL SCHEDULE. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE MICROWAVE/HOOD ON SCHEDULE SHOWS |
| | 13.5AMPS. THIS AT 120V IS MUCH HIGHER THAN THE 900VA |
| | SHOWN ON THE LOAD CALCULATIONS. |
| | THIS IS THE SAME FOR OTHER LOADS SUCH AS WINE COOLER |
| | JACUZZI ETC. |
| | PLEASE SEE THE LOAD FOR THE A/C CAN NOT POSSIBLY BE THE |
| | 2KVA AS SHOWN ON LOAD CALCULATIONS WITH AN AMPERAGE |
| | LOAD OF 18.8AMPS. |
| | PLEASE SEE SOME LOADS ON THE LOAD CALCULATIONS ARE TO |
| | COORDINATE WITH THE LOADS ON PANELS. |
| | NEC 220, 408.4, 240.4, 310.16 TO DETERMINE CIRCUITS. |
| | FBC 106.3.5.4 |
| | 106.1.2, 106.1.1 |
| | |
| | 5) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED |
| | CIRCUITS PER 210.12. 408.4 |
| | THIS IS REQUIRED FOR ALL OUTLETS, INCLUSIVE OF SMOKE |
| | DEVICES (120V), RECEPTACLES, LIGHTS, FANS ETC. |
| | |
| | 6) NOTE: PLEASE SEE MISSING GFI RECEPTACLE ALONG |
| | KITCHEN COUNTER SPACE WHICH IS REQUIRED PER 210.52C1, |
| | 210.8A6. |
| | THE PLANS STATE A SCALE OF 3/8 INCH PER FT, AND BASED |
| | ON THE LENGTH OF COUNTER SPACE ALONG WALL NEAR LIVING |
| | ROOM, AN ADDITIONAL GFI IS NEEDED |
| | |
| | 7) NOTE: PLEASE SEE ANY RECEPTACLES WITHIN 6FT OF WET |
| | BAR SINKS ARE REQUIRED TO BE GFIOR GFI PROTECTED PER |
| | 210.8A7 (DINING ROOM) |
| | |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |