Plan Review Notes
Plan Review Notes For Permit 07080451
Permit Number 07080451
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-27 20:14:472007-08-27 20:14:47
  
 ** DENIED **
  
 1) NOTE: PLEASE SEE THE SMOKE DEVICES AS SHOWN ARE
 BEING INDICATED AS SD, WHERE THE PLANS ALSO CALL FOR
 THESE AS 120V UNITS. IF THESE ARE DEVICES WHICH DETECT
 AND SOUND AN ALARM, THEY ARE IN FACT SMOKE ALARMS (SA)
 AND NOT SMOKE DETECTORS. PLEASE SEE NFPA-72 DEFINITIONS
 AS THE SD ONLY DETECT AND DO NOT PROVIDE AN AUDIBLE
 ALARM.
 PLEASE SEE NFPA-72 11.8.3 WHICH REQUIRES ALL SMOKE
 DETECTION DEVICES TO BE A MINIMUM OF 20FT AWAY FROM
 COOKING APPLIANCES. THERE IS AN EXCEPTION TO THIS AS
 LONG AS ONE OF TWO SPECIFIC TYPES OF UNITS IS
 INSTALLED. PLEASE SPECIFY
 PLEASE ADJUST.
  
 2) NOTE: PLEASE SEE THE REQUIRED DEDICATED BATH CIRCUIT
 FOR THE GFI IS BEING SHOWN ON THE SAME CIRCUIT AS THE
 SMOKE DETECTION DEVICES WHICH ARE NOT PERMITTED. PLEASE
 SEE 210.52D,210.11C3.
 (MUST BE 20AMP AND #12).
  
 3) NOTE: PLEASE SEE THE MISSING LOAD TO BE FIGURED IN
 THE LOAD CALCULATIONS FOR THE DINING ROOM RECEPTACLES
 PER 210.52B1, 210.11C1, AND 220.53.
 (1500VA MIN)
  
 4) NOTE: PLEASE SEE THERE ARE SEVERAL ITEMS ON THE LOAD
 CALCULATIONS WHICH DO NOT MATCH WITH THE AMPERAGE LOADS
 BEING SHOWN ON THE PANEL SCHEDULE.
 FOR EXAMPLE:
 PLEASE SEE THE MICROWAVE/HOOD ON SCHEDULE SHOWS
 13.5AMPS. THIS AT 120V IS MUCH HIGHER THAN THE 900VA
 SHOWN ON THE LOAD CALCULATIONS.
 THIS IS THE SAME FOR OTHER LOADS SUCH AS WINE COOLER
 JACUZZI ETC.
 PLEASE SEE THE LOAD FOR THE A/C CAN NOT POSSIBLY BE THE
 2KVA AS SHOWN ON LOAD CALCULATIONS WITH AN AMPERAGE
 LOAD OF 18.8AMPS.
 PLEASE SEE SOME LOADS ON THE LOAD CALCULATIONS ARE TO
 COORDINATE WITH THE LOADS ON PANELS.
 NEC 220, 408.4, 240.4, 310.16 TO DETERMINE CIRCUITS.
 FBC 106.3.5.4
 106.1.2, 106.1.1
  
 5) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS PER 210.12. 408.4
 THIS IS REQUIRED FOR ALL OUTLETS, INCLUSIVE OF SMOKE
 DEVICES (120V), RECEPTACLES, LIGHTS, FANS ETC.
  
 6) NOTE: PLEASE SEE MISSING GFI RECEPTACLE ALONG
 KITCHEN COUNTER SPACE WHICH IS REQUIRED PER 210.52C1,
 210.8A6.
 THE PLANS STATE A SCALE OF 3/8 INCH PER FT, AND BASED
 ON THE LENGTH OF COUNTER SPACE ALONG WALL NEAR LIVING
 ROOM, AN ADDITIONAL GFI IS NEEDED
  
 7) NOTE: PLEASE SEE ANY RECEPTACLES WITHIN 6FT OF WET
 BAR SINKS ARE REQUIRED TO BE GFIOR GFI PROTECTED PER
 210.8A7 (DINING ROOM)
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]