| 2007-09-04 15:59:37 | 2004 FBC W/2007 SUPPLEMENT |
| | CONVERT TEMPORARY SALES OFFICE BACK TO SFR |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION IS |
| | FOR DRYWALL WORK ONLY.THE PLANS THAT WERE SUBMITTED |
| | INDICATE THAT INTERIOR WALLS WILL NEED TO BE REMOVED |
| | AND NEW ONES INSTALLED, KITCHEN CABINETS TO BE |
| | INSTALLED IN THE DISPLAY AREA, ETC. |
| | |
| | 2) THE VALUE FOR THE WORK LISTED ON THE PERMIT |
| | APPLICATION IS TOO LOW FOR THE AMOUNT OF WORK THAT WILL |
| | BE REQUIRED TO CONVERT THE STRUCTURE FROM THE SALES |
| | OFFICE INTERIOR BUILD OUT TO THE RESIDENTIAL LAYOUT |
| | SHOWN ON THE PLANS THAT WERE SUBMITTED. |
| | |
| | 3) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | DESCRIBING THE WORK WILL BE REQUIRED BECAUSE THE VALUE |
| | OF THE WORK IS OVER $2500.00. FS 713. |
| | |
| | 4) NEW ELECTRICAL, MECHANICAL AND PLUMBING PLANS |
| | SHOWING THE EXISTING CONDITIONS AND PROPOSED CHANGES |
| | WILL BE REQUIRED. FBC* 106.1.2 AMENDED BY W.P.B. |
| | |
| | 5) THE PLANS FROM THE ARCHITECT ARE REQUIRED TO BE |
| | SIGNED, SEALED AND DATED. FBC*106.1 AND FS 481. |
| | |
| | 6) SPECIFY WHICH OF THE ROOM OPTIONS SPECIFIED ON THE |
| | PLANS WILL BE USED. FBC * 106.1.2. |
| | |
| | 7) THE EXISTING FLOOR PLAN INDICATES DOUBLE OUTSWING |
| | FRENCH DOORS AT THE GATHERING ROOM AND THE NEW FLOOR |
| | PLAN SHOWS A DOUBLE WINDOW AT THIS LOCATION. THE |
| | EXISTING FLOOR PLAN SPECIFIES A SMALLER WINDOW AT THE |
| | DISPLAY AREA THAN THE NEW FLOOR PLAN AT THAT LOCATION. |
| | IF DOORS OR WINDOWS ARE BEING CHANGED, SUBMIT PRODUCT |
| | APPROVALS FOR THE NEW ITEMS. |
| | |
| | 8)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9) FBC R301.2.1.2 REQUIRES GLAZED OPENINGS TO BE IMPACT |
| | PROTECTED. PROVIDE PRODUCT APPROVALS FOR IMPACT |
| | PROTECTION PRODUCTS AT NEW GLAZED AREAS. |
| | |
| | - ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |