Plan Review Notes
Plan Review Notes For Permit 07080417
Permit Number 07080417
Review Stop P
Sequence Number 4
Notes
Date Text
2008-03-25 09:11:25PLUMBING PLAN REVIEW:
 DENIED 4TH TIME
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2006 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED ON THE
 PREVIOUS REVIEWS, 9/6/07, 10/17/07 AND 11/27/07:
  
 1. SHEET 2, SANITARY RISER DIAGRAM: THE WASHING
 MACHINE AND SINK IN THE UTILITY ROOM MUST DRAIN
 DOWNSTREAM OF THE NEW WET VENTED BATHROOM GROUP. PER
 FBC, PLUMBING, SECTION *909.1 WET VENT PERMITTED.
  
 ****RESPONSE NOTED, HOWEVER THE RESUBMITTED RISER
 DIAGRAM HAS NOT BEEN REVISED TO INDICATE THE WASHING
 MACHINE AND SINK IN THE UTILITY ROOM TO DRAIN
 DOWNSTREAM OF THE NEW WET VENTED BATHROOM GROUP.
  
 2. **OK** COMMENT ADDRESSED.
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED ON THE
 PREVIOUS REVIEW, 10/17/07 AND 11/27/07:
  
 3. **OK** COMMENT ADDRESSED.
  
 4. THE RESUBMITTED ENERGY CALCULATIONS ARE INCOMPLETE
 FOR THE ADDITION DUE TO THE FACT THAT THE WATER HEATER
 IS IN THE NEW ADDITION UTILITY ROOM AND THE ENERGY
 CALCULATIONS ARE INDICATING PER (14) HOT WATERSYSTEM
 TYPE, N/A. PER THE FOLLOWING CHAPTER 13 ENERGY
 EFFICIENCY SECTION 13-101.0 GENERAL. THIS CODE IS A
 STATEWIDE UNIFORM CODE AND SHALL NOT BE MADE MORE
 STRINGENT OR LENIENT BY LOCAL GOVERNMENT. THE CODE
 PROVIDES FOR A UNIFORM STANDARD OF ENERGY EFFICIENCY
 BY, AT A MINIMUM, SETTING FORTH MINIMUM REQUIREMENTS
 FOR EXTERIOR ENVELOPES, LIGHTING, ELECTRICAL
 DISTRIBUTION, AND SELECTION OF HEATING, LIGHTING,
 VENTILATION, AIR CONDITIONING AND SERVICE WATER HEATING
 SYSTEMS. IT SHALL APPLY TO ALL NEW BUILDINGS, TO
 ADDITIONS TO EXISTING BUILDINGS AND MANUFACTURED HOMES,
 TO RENOVATIONS TO EXISTING BUILDINGS, BOTH PUBLIC AND
 PRIVATE, WITH CERTAIN EXCEPTIONS, TO CHANGES OF
 OCCUPANCY TYPE, TO THE SITE-INSTALLED COMPONENTS AND
 FEATURES OF A MANUFACTURED HOMES AT THEIR FIRST SET-UP,
 AND TO THE INSTALLATION OR REPLACEMENT OF BUILDING
 SYSTEMS AND COMPONENTS WITH NEW PRODUCTS FOR WHICH
 THERMAL EFFICIENCY STANDARDS ARE SET BY THIS CODE. NEW
 BUILDINGS, WITH EXCEPTION OF THOSE EXEMPTED BELOW, AND
 IN ACCORDANCE WITH THE SPECIFIC EXCEPTIONS OF
 INDIVIDUAL SECTIONS SHALL BE DESIGNED TO COMPLY WITH
 SUBCHAPTER 13-4 OR 13-6 OF THIS CODE.
 **NOTE: THE WATER HEATER IN THE NEW ADDITION UTILITY
 ROOM SHALL COMPLY PER THE FOLLOWING AND BE INDICATED ON
 THE RESUBMITTED ENERGY CALCULATIONS:
  
 A} 13-101.2.2 ADDITIONS.
 B} TABLE 13-612.1.ABC.3.2, MINIMUM PERFORMANCE
 STANDARDS, WATER HEATING EQUIPMENT.
  
 ****RESPONSE NOTED, HOWEVER THE ENERGY CALCULATIONS
 NEED TO BE SIGNED BY OWNER/AGENT PER FBC 13-103.3.
  
 5. SEE ATTACHED IMPORTANT NOTICE FS 553.80(2)(B)
 DESIGN PROFESSIONAL DOCUMENTS REGUARDING FOUR (4) TIMES
 THE FEE.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]