| 2008-03-24 10:44:02 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) AS REQUESTED IN LAST TWO REVIEWS 11-17-07 NOTE #1 |
| | AND 10-17-07 NOTE #1. PLEASE SUBMIT THE 'LONG FORM' |
| | "COOLING LOAD CALCULATIONS", (NOT TO BE CONFUSED WITH |
| | THE ENERGY CALCULATIONS) PER 2004 FBC/R M1401.3 HEATING |
| | AND COOLING EQUIPMENT SHALL BE SIZED BASED ON BUILDING |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA "MANUAL J" OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES. THE ENGINEERS RESPONSE LETTER STATES A |
| | NEW LONG FORM ENERGY CALCULATIONS IS ATTACHED. |
| | |
| | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| | ALSO, PER 2004 FBC 13-103.3. |
| | |
| | 3) PLEASE SHOW ON MECHANICAL PLAN HOW RETURN AIR WILL |
| | GET TO THE AIR HANDLER UNIT FROM ANY OF THE ROOMS WHEN |
| | ALL DOORS ARE CLOSED, SEE 2004 FBC/R M1602.4. |
| | |
| | 4) PLEASE BE ADVISED A FOUR TIMES THE FEE WILL BE |
| | CHARGED TO THE PERMIT IF NOTE ONE HAS NOT BEEN |
| | CORRECTED, PER FS 553.80(2)(B). PLEASE CALL IF YOU NEED |
| | ANY ASSISTANCE. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |